17
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Table 17-1:
O.D. of pipe and tubing
Nom.
Dia.
Standard
pipe
Copper
tubing
SST
tubing
I.D. of
hose
1¼"
(30 mm)
1.660
1.375
-
-
1½"
(38 mm)
1.900
1.625
1.500
1.50
2"
(50 mm)
2.375
2.125
2.000
2.00
2½"
(65 mm)
2.875
2.625
3.000
3.00
Note: Pipe thread and fl ange tubing adapters
are available from DriSteem.
Piping
STEAM FROM A PRESSURIZED STEAM
Ultra-sorb panels for pressurized steam have a threaded pipe nipple that
extends outside the framework for a steam supply connection. The steam
supply line should be dripped immediately ahead of the steam valve through a
steam trap. See Figure 14-3.
RECOMMENDED TRAP FOR STEAM MAIN DRIP LEG
Use a fl oat and thermostatic (F&T) trap on the steam supply ≤15 psi and
inverted bucket if > 15 psi.
DRIEST STEAM
To ensure driest steam, take humidifi er steam off the top of the steam main (not
the side or bottom).