Page 4 • DRI-STEEM STS/LTS, DI Water, Service Kit Manual

S T S / LT S ,   D I   w a t e r,   s e r v i c e   i n s t r u c t i o n s

Annually 

(also recommended when maintenance is performed)

1.  All safety devices in the control circuit should be cycled on 

and off to verify they are functioning. These include:
•  High limit switch
•  Airflow proving switch

2.  Inspect tank and gaskets for leaks. 
3.  Verify that the float valve is closing off. If the float valve 

will not shut off, there may be particulate on the valve seat, 

or the stopper may be worn and need replacing.

As long as mineral‑free water is used in the humidifier, no 

cleaning or flushing should be necessary. 

Off-season maintenance

 

1.  Perform a complete inspection of the following:

•  Heat exchanger
•  Float valve
•  Humidifier tank and gaskets

2.  After inspection, leave the humidifier empty until 

humidification is required.

After the humidification season, DRI‑STEEM recommends a 

complete inspection and cleaning of the heat exchanger and 

water chamber. After cleaning, the unit should remain empty 

until humidification is required. 

mc_060208_0708

  Shut down humidifier

Follow the procedure below before performing service or 

maintenance procedures, (after the tank has cooled down and 

drained):
1.   Use the Vapor‑logic3 controller keypad to change the 

control mode to Standby. 

2.   Shut off all electrical power to the humidifier using 

the field‑installed fused disconnect, and lock all power 

disconnect switches in the OFF position.

3.   Close the field‑installed manual water supply shut‑off 

valve.

4.   Close the manual inlet steam supply (on STS) or inlet hot 

liquid supply (on LTS) shut‑off valve.

mc_060208_1440

Before performing any maintenance, allow the tank to cool 

down. Insulated and uninsulated tanks will have hot surfaces.

Note:

   Fresh make‑up water is used to speed up cooling. Do 

not close the manual water supply before cooling down 

the humidifier; otherwise the tank could stay hot for 

several hours. 

1.  Close the manual shut‑off valve on the inlet steam supply 

(STS humidifiers) or the inlet hot liquid supply (LTS 

humidifiers).

2.  Drain the tank:

Models with a standard drain valve:

a.  Manually open the drain valve. The fill valve will open 

after enough water has drained out of the tank.

b.  Let the fill water run until the tank is cooled; then shut 

off the field installed manual supply water shut‑off 

valve.

c.  Let the tank drain; then manually close the drain valve.

For models with end-of-season drain option

 (must have 

Vapor‑logic3 controller), use the keypad to perform the 

cool down procedure. Refer to the 

Vapor-logic3 Installation 

and Operation Manual

 for more information:

a.  Select Manual Drain in the control modes screen.
b  Allow approximately half the water to drain out of the 

tank.

c.  Select Auto in the control modes screen; the fill valve 

opens and the humidifier cools down.

d.  When the fill valve closes, select Manual Drain in 

the control modes screen and allow the tank to drain 

completely dry. The humidifier should be cool enough 

to work on.

mc_060308_0700

  Cool down humidifier

Inspection and maintenance 

On units with Teflon coated heat exchangers, do not use 

a sharp object when cleaning. 

Cuts or scratches on the heat 

exchanger will impair its ability to shed scale during operation 

and could cause the Teflon to separate from the metal surface.

mc_060208_0715

Summary of Contents for LTS Series

Page 1: ...ot as 212 F 100 C To avoid severe burns allow the entire humidification system to cool Follow the cool down procedure in the humidifier s IOM before performing service or maintenance procedures on any...

Page 2: ...Qty 1 Silicone clear not shown 320000 1 2 Seat black EPDM see Float Valve inset 505210 003 1 3 Probe plate gasket 308416 001 1 4 Cleanout plate gasket 308015 002 1 5 Cover gasket 160692 003 1 6 Heat...

Page 3: ...EM humidifier operating at peak performance This Service Kit Manual provides important safety and service instructions it is intended to supplement not replace the humidifier s Installation Operation...

Page 4: ...on STS or inlet hot liquid supply on LTS shut off valve mc_060208_1440 Before performing any maintenance allow the tank to cool down Insulated and uninsulated tanks will have hot surfaces Note Fresh...

Page 5: ...nd of a humidification season either by manually opening the drain valve or by programming the humidifier to automatically drain at end of season electric drain valve and Vapor logic3 required mc_0603...

Page 6: ...13 DRI STEEM Corporation Humidifier De scaling Solution Scale buildup on humidifier heat exchangers acts as an insulator reducing humidifier performance while increasing energy costs To keep humidifie...

Page 7: ...de br lures graves laisser refroidir tout le syst me d humidification Suivre la proc dure de refroidissement d crite dans l IOM de l humidificateur avant d effectuer des interventions d entretien ou...

Page 8: ...0000 1 2 Si ge thyl ne propyl ne di ne monom re EPDM noir voir l encart Robinet flotteur 505210 003 1 3 Joint d tanch it de la plaque de sonde 308416 001 1 4 Joint d tanch it de la plaque de nettoyage...

Page 9: ...e continuer fonctionner au maximum de ses performances Ce Manuel du n cessaire d entretien fournit des consignes de s curit et d entretien importantes il est con u pour compl ter non remplacer le Manu...

Page 10: ...ge manuelle l cran Control Modes modes de commande et laisser la cuve se vidanger compl tement L humidificateur devrait avoir suffisamment refroidi pour pouvoir effectuer la t che Vapor logic3 pour ba...

Page 11: ...dang s soit en ouvrant manuellement le robinet de vidange soit en programmant l humidificateur de fa on ce qu il effectue automatiquement une vidange la fin de la saison robinet de vidange lectrique e...

Page 12: ...Corporation poursuit une politique d am lioration continue de ses produits Par cons quent les caract ristiques et les sp cifications des produits peuvent changer sans pr avis DRI STEEM LTS STS et Vapo...

Page 13: ...anks Elektrozylindern Dampfrohren und Verteilmodulen kann bis zu 100 C hei sein Daher das gesamte Befeuchtersystem zuerst abk hlen um Verbr hungen zu vermeiden Das Abk hlverfahren in der Befeuchter Be...

Page 14: ...on klar nicht dargestellt 320000 1 2 Sitz schwarz EPDM siehe Einzelheit F llventil 505210 003 1 3 Dichtung Abdeckung Sonde 308416 001 1 4 Dichtung Abdeckung Reinigungs ffnung 308015 002 1 5 Dichtung A...

Page 15: ...eichnung f r einen optimalen Betrieb Ihres DRI STEEM Befeuchters Die vorliegende Anleitung enth lt wichtige Sicherheits und Wartungsanweisungen und ist kein Ersatz f r die mit dem Befeuchter geliefert...

Page 16: ...r jegliche Wartungsarbeiten ausgef hrt werden Nachdem der Tank abgek hlt hat und entw ssert ist 1 Mit Hilfe des Vapor logic3 Steuerger ts den Befeuchter in Modus Standby schalten 2 Die komplette Strom...

Page 17: ...ten am Ende der Saison entw ssert werden entweder durch manuelles ffnen des Ablaufventils oder durch Programmierung des Befeuchters eine automatische Entw sserung am Ende der Saison durchzuf hren erfo...

Page 18: ...3200 Fax DRI STEEM Corporation praktiziert eine fortw hrende Produktentwicklung deshalb behalten wir uns Produkt nderungen ohne Vorank ndigung vor DRI STEEM LTS STS und Vapor logic sind eingetragene W...

Reviews: