Drehmo i-matic Installation And Operating Manual Download Page 6

Supplement operating manual for DREHMO i-Matic actuators with integrated  

MODBUS fieldbus interface  

 

 
Wenden, 21.03.12 

 

Page 6 of 18 

Prepared by: Ste 

 

Register  Bit 

Coil 

Signal 

Meaning 

0x204 

49 

Torque warning OPEN  

Torque higher than torque warning level 
set 

 

50 

Torque warning CLOSED 

Torque higher than torque warning level 
set 

 

51 

No signal of reference value  

If imxx5, message if no reference value 

 

52 

Hardware fault 

Warning message 

 

53 

Combined sensor defective 

Warning message 

 

54 

system check error 

During self-check the electronic unit has 
detected an error. The unit then performs 
a reset and tries to enter the state fail-
safe. The indication can be cleared by 
using the acyclic bit „Reset system test 
error“ in slot 1 index 240, or by using the 
local reset in system>reset, or by a 
power off on cycle. The kind of error 
(refer to operating manual of 

i-matic

) can 

be read out by using the acyclic service 
“system test error code” in slot 1 index 
195 or the system entry under actual 
value diagnosis on the local control 
station. This indication is important for 
safety related systems, if due to an error 
the system needs to be brought to a safe 
state. 

 

55 

Maintenance required 

Perm. operating data are exceeded 

 

56 

Actuator is served 

Logged in user is specialist or 
manufacturer for service reasons 

 

57 

Regulating time too long  

Regulating time longer than max. running 
time  

 

58 

Max. valve stroke exceeded  

Regulating distance longer than stroke of 
valves 

 

10 

59 

Hand wheel operation 

Actuators hand wheel is in usage 

 

11 

60 

Rotation monitor 

Set if rotation direction is wrong 

 

12 

61 

Data exchange channel 1 

Data exchange on channel 1 active 

 

13 

62 

Data exchange channel 2 

Data exchange on channel 2 active 

 

14 

63 

Channel 1 primary 

Channel 1 commands are in use due to 
highest channel priority 

 

15 

64 

Channel 2 primary 

Channel 2 commands are in use due to 
highest channel priority 

0x205 

0..15 

65..80 

Torque value 

0...1000ppt of the torque value at power 
output 

0x206 

0..7 

81..96 

Position value low byte 

0...1000ppt of analogue input 1 

8..15 

Position value high byte 

0x207 

0..7 

97..112 

Position value low byte 

0...1000ppt of analogue input 2 

8..15 

Position value high byte 

0x208 

113 

Process input 1 

State of digital input 1 

114 

Process input 2 

State of digital input 2 

115 

Process input 3 

State of digital input 3 

116 

Process input 4 

State of digital input 4 

117 

 

 

118 

 

 

119 

 

 

120 

 

 

8..15 

121..128   

 

0x209.. 
0x220 

 

129..512   

 

 
In order to access the feedback signals, the function codes FC 05 (Force Single Coil) or FC 06 (Preset Single 
Register) have to be used. The following tables give telegram examples for these function codes. 

Summary of Contents for i-matic

Page 1: ...for actuators with MODBUS interface part number 166 671 Installation Manual Version 03 Operating Manual Date Oct 18 th 2006 INFORMATION This installation manual should only be used in conjunction with...

Page 2: ...2 4 2 Number of channels bus profile 10 2 4 3 Redundancy modes line redundant vs master redundant 10 2 4 4 Function Fail Safe Timeout setting 10 2 4 5 Fault messages 11 2 5 Electrical connection 12 2...

Page 3: ...ate 2 wire RS485 modbus channels The baud rate and parity settings are common for both channels Each of the channels can be assigned an individual slave address in the range of 1 to 247 different addr...

Page 4: ...rce Single Coil write single bit of master output data command FC 06 Preset Single Register write single data of master output data command FC 15 Force Multiple Coils write multiple bit of master outp...

Page 5: ...travel message only acc to position 11 28 Drive in end of travel position CLOSED End of travel message only acc to position 12 29 Drive in end of travel position OPEN Drehmo End of travel message onl...

Page 6: ...xceeded 7 56 Actuator is served Logged in user is specialist or manufacturer for service reasons 8 57 Regulating time too long Regulating time longer than max running time 9 58 Max valve stroke exceed...

Page 7: ...word feedback Request C8 04 02 00 00 08 E1 ED Checksum number of data high lowbyte database address decimal 512 function code 04 slave address 200 in example Response C8 04 10 03 C4 00 0F 42 84 50 A0...

Page 8: ...V01 05 0048 9 15 26 32 unused unused 0x203 0x220 33 512 In order to access the command signals the function codes FC 05 Force Single Coil or FC 06 Preset Single Register are recommended to be used The...

Page 9: ...00 00 00 00 00 00 00 00 00 00 00 00 00 A6 6D Checksum discrete coil command check information 0 lowbyte highbyte order number of databytes function code 01 read coil status command check slave address...

Page 10: ...possible to set up two different redundancy modes The different modes have a different reply behaviour For line redundant mode it is possible to block the reply of the inactive channel by setting the...

Page 11: ...25 5 seconds In case of fail safe the actuator action can be parameterised as explained in the i Matic instruction manual 2 4 5 Fault messages Fault messages can be reset depending on the active faul...

Page 12: ...en below 1 Optional external 24 VDC supply of i Matic unit input with tolerance 10 5 and less than 500mA load Optional auxiliary 24 VDC supply output for external use allows 60mA load Mounting plate f...

Page 13: ...e to be wired to the output terminals labeled OUT The connection of the shielding for incoming or outgoing cables has to be done in the same manner Mounting plate with electric assembly front side vie...

Page 14: ...S3 S4 on DiM 19 connection board channel 1 without termination bus connection forward to next device channel 2 termination activated last device on bus segment 2 5 1 3 Grounding of the cables shields...

Page 15: ...The core of the optical fibres might be of diameter 50 m or 62 5 m To connect the fibre optic cables open the cover of the extended compact plug Using the maximum of four cable glands M20x1 5 the cab...

Page 16: ...available double terminals A1 B1 A2 B2 which are electrically connected A bridge between incoming and outgoing bus signals has to be made to achieve the required T piece The bus terminator always has...

Page 17: ...ant to keep the size of the breakout small enough to be able to push it through a cable gland of the size M20 The standard connector is of type F SMA The following pictures show the inside of the wiri...

Page 18: ...ground are galvanically isolated from the electronic potential by optocouplers The nominal current of the discrete inputs is 12 mA for an input voltage of 24 V DC The following picture shows the stru...

Reviews: