Drehmo i-matic Installation And Operating Manual Download Page 5

Supplement operating manual for DREHMO i-Matic actuators with integrated  

MODBUS fieldbus interface  

 

 
Wenden, 21.03.12 

 

Page 5 of 18 

Prepared by: Ste 

2.3.1  Accesses for master input data ( actuator feedback signals) 

 
The following table gives detailed information about the addresses of the actuator feedback signals. 
 

Register  Bit 

Coil 

Signal 

Meaning 

0x201 

0..7 

1..16 

Position value Low-Byte 

0...1000ppt actual position value 

8..15 

Position value High-Byte 

0x202 
 

17 

General fault signal 1 

General fault signal 1 is active 

18 

General fault signal 2 

General fault signal 2 is active  

19 

Phase failure 

One of the three phases has failed   

20 

Failure internal 24 V DC 

Only possible in case of external supply  

21 

Failure externally supplied 24 V 
DC 

Only possible in case of external supply 

22 

Torque in OPEN direction   

Max. torque in the OPEN direction 
exceeded 

23 

Torque in CLOSED direction  

Max. torque in the CLOSED direction 
exceeded 

24 

Drive in fail-safe 

Drive is in the fail-safe mode 

25 

Drive moves to OPEN (only 
statically) 

Movement in direction to OPEN position 
signal  

26 

Drive moves to CLOSED (only 
statically) 

Movement in direction to CLOSE position 
signal 

10 

27 

Drive in end of travel position 
OPEN  

End of travel message only acc. to 
position 

11 

28 

Drive in end of travel position 
CLOSED 

End of travel message only acc. to 
position 

12 

29 

Drive in end of travel position 
OPEN+Drehmo 

End of travel message only if path and 
torque 

13 

30 

Drive in end of travel position 
TORQUE 

End of travel message only if path and 
torque 

14 

31 

Motor too hot 

Signal excess temperature motor 

15 

32 

Drive in the remote mode 

Display of the operating mode   

0x203 

33 

Drive in the local mode 

Display of the operating mode   

 

34 

Drive locally controlled   

Drive is locally controlled  

 

35 

Activation of discrete commands 

A remote command OPEN or CLOSE 
can be given (Automatic mode = 0) 

 

36 

Drive in the learn mode 

Display of the operating mode   

 

37 

Locking 

Parameter setting for remote command  

 

38 

Torque limit deactivation in OPEN 

Parameter setting for deactivation 

 

39 

Torque limit deactivation in 
CLOSED 

Parameter setting for deactivation 

 

40 

Start-up bridging in OPEN active  

Parameter display 

 

41 

Start-up bridging in CLOSED 
active 

Parameter display 

 

42 

Local_ind = NOT Remote 

Drive is not in the remote mode 

 

10 

43 

Emergency travel active 

Status indication 

 

11 

44 

Approach fail-safe position  

Parameter display 

 

12 

45 

Pulse generator active 

Parameter display 

 

13 

46 

Intermediate position 1 

Message active between Z and ZS 1 

 

14 

47 

Intermediate position 2 

Message active between ZS 2 and 
OPEN 

 

15 

48 

Drive does not start  

Warning message 

Summary of Contents for i-matic

Page 1: ...for actuators with MODBUS interface part number 166 671 Installation Manual Version 03 Operating Manual Date Oct 18 th 2006 INFORMATION This installation manual should only be used in conjunction with...

Page 2: ...2 4 2 Number of channels bus profile 10 2 4 3 Redundancy modes line redundant vs master redundant 10 2 4 4 Function Fail Safe Timeout setting 10 2 4 5 Fault messages 11 2 5 Electrical connection 12 2...

Page 3: ...ate 2 wire RS485 modbus channels The baud rate and parity settings are common for both channels Each of the channels can be assigned an individual slave address in the range of 1 to 247 different addr...

Page 4: ...rce Single Coil write single bit of master output data command FC 06 Preset Single Register write single data of master output data command FC 15 Force Multiple Coils write multiple bit of master outp...

Page 5: ...travel message only acc to position 11 28 Drive in end of travel position CLOSED End of travel message only acc to position 12 29 Drive in end of travel position OPEN Drehmo End of travel message onl...

Page 6: ...xceeded 7 56 Actuator is served Logged in user is specialist or manufacturer for service reasons 8 57 Regulating time too long Regulating time longer than max running time 9 58 Max valve stroke exceed...

Page 7: ...word feedback Request C8 04 02 00 00 08 E1 ED Checksum number of data high lowbyte database address decimal 512 function code 04 slave address 200 in example Response C8 04 10 03 C4 00 0F 42 84 50 A0...

Page 8: ...V01 05 0048 9 15 26 32 unused unused 0x203 0x220 33 512 In order to access the command signals the function codes FC 05 Force Single Coil or FC 06 Preset Single Register are recommended to be used The...

Page 9: ...00 00 00 00 00 00 00 00 00 00 00 00 00 A6 6D Checksum discrete coil command check information 0 lowbyte highbyte order number of databytes function code 01 read coil status command check slave address...

Page 10: ...possible to set up two different redundancy modes The different modes have a different reply behaviour For line redundant mode it is possible to block the reply of the inactive channel by setting the...

Page 11: ...25 5 seconds In case of fail safe the actuator action can be parameterised as explained in the i Matic instruction manual 2 4 5 Fault messages Fault messages can be reset depending on the active faul...

Page 12: ...en below 1 Optional external 24 VDC supply of i Matic unit input with tolerance 10 5 and less than 500mA load Optional auxiliary 24 VDC supply output for external use allows 60mA load Mounting plate f...

Page 13: ...e to be wired to the output terminals labeled OUT The connection of the shielding for incoming or outgoing cables has to be done in the same manner Mounting plate with electric assembly front side vie...

Page 14: ...S3 S4 on DiM 19 connection board channel 1 without termination bus connection forward to next device channel 2 termination activated last device on bus segment 2 5 1 3 Grounding of the cables shields...

Page 15: ...The core of the optical fibres might be of diameter 50 m or 62 5 m To connect the fibre optic cables open the cover of the extended compact plug Using the maximum of four cable glands M20x1 5 the cab...

Page 16: ...available double terminals A1 B1 A2 B2 which are electrically connected A bridge between incoming and outgoing bus signals has to be made to achieve the required T piece The bus terminator always has...

Page 17: ...ant to keep the size of the breakout small enough to be able to push it through a cable gland of the size M20 The standard connector is of type F SMA The following pictures show the inside of the wiri...

Page 18: ...ground are galvanically isolated from the electronic potential by optocouplers The nominal current of the discrete inputs is 12 mA for an input voltage of 24 V DC The following picture shows the stru...

Reviews: