
Instructions for use Movita
39
Technical data
Technical data
Product characteristics
Ceiling mounting
Movita lift height adjustment
Fuses
Electromagnetic brake
Lighting
Ambient conditions
Suspended ceiling depth up to 1200 mm
(47.24 in)
Mounting on concrete
structural ceiling
by means of heavy duty
anchors (other
construction also
possible)
12500 Nm
Drilling template
470 mm (18.5 in),
6 x M16
By electric motor:
100 V~ to 240 V~,
50/60 Hz,
432 VA
Primary fuse
T 6.3 A H 250 V~
(G37689)
Secondary fuse
F 10A H 250 V~
(G35162)
Fuse for floor light
T 630 mA H 250 V~
(G38947)
Fuse for Vimar power
socket
F 16A H 250 V~
1500 A
Built-in power supply
unit
100 V~ to 240 V~,
50/60 Hz, 460 VA
Built-in power supply
unit for indirect ceiling
light or floor light
100 V~ to 240 V~,
50/60 Hz, 50 W
During operation
Temperature
+10 °C to +35 °C
(+50 °F to +95 °F)
Relative humidity
5 % to 95 %
(non-condensing)
Atmospheric
pressure
700 hPa to 1060 hPa
(10.2 psi to 15.4 psi)
During storage
1)
and
transport (up to
15 weeks)
1) Storage only in enclosed or roofed areas
Temperature
–20 °C to +60 °C
(–4 °F to +140 °F)
Relative humidity
5 % to 95 %
(non-condensing)
Atmospheric
pressure
500 hPa to 1060 hPa
(7.25 psi to 15.4 psi)