53
Basic Analog Configuration
ID
Analog ID number.
Enab
Check this box to enable the analog.
Description
User-definable description for the analog channel.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Analog Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each log of each
analog value to history.
Deadband
The amount (in volts) that the channel needs to go above or below a threshold in order
to cause an alarm.
On Set
User-definable description (condition) that will appear for the temperature alarm on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the temperature alarm Clear.
Example: "Alarm Cleared".
Qual Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Units
User-definable display units or optional choice between Fahrenheit and Celsius
temperatures. The most common are:
VDC = Voltage
%H = Humidity
F = Fahrenheit
C = Celsius
Low Ref
User-definable lower reference/scaling level. This scales the information collected by
the sensor (in mA or VDC) to a meaningful unit for the user. For example, for a
temperature sensor, the lower input collected by the sensor may be 4mA (for a 4-
20mA sensor), which would correspond to a specific temperature you define in this
field.
High Ref
User-definable upper reference/scaling level. This scales the information collected by
the sensor (in mA or VDC) to a meaningful unit for the user. For example, for a
temperature sensor, the upper input collected by the sensor may be 20mA (for a 4-
20mA sensor), which would correspond to a specific temperature you define in this
field.
Thresholds
These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed. Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).
Analog Gauge Type
Select the color-coded gauge that best represents your data. Selecting
None
will
disable the analog gauge and only a numerical representation of the value will be
displayed under
Monitor
>
Analogs
.
Summary of Contents for D-PK-C16V2
Page 5: ...Technical Support 18 82 End User License Agreement 19 83...
Page 6: ......
Page 15: ...9 Amphenol connector pinout...
Page 17: ...11 Optional 66 block connector pinout for controls...
Page 51: ...45 The Provisioning Phone List menu...
Page 53: ...47 you will have to enter the relevant authentication information the fields below...
Page 90: ...84...
Page 91: ...85...
Page 92: ......