14
Installation • Software Provisioning
2.4.3 Monitoring the Expansion Alarm Points
Now that the Expansion points have been provisioned with all of the appropriate information, they may be moni-
tored. (This is helpful to verify the installation.)
1.
From the main menu, select C)onfig, then M)onitor, then A)larms, then E)xpansions.
2.
Enter the display number that you would like to monitor (12=Expansion shelf 1, 14=shelf 2, and 16=shelf 3,
see section 3.2 for display mapping details).
3.
The list of alarms and their status will be displayed, 16 alarms at a time. Press any key to scroll to the next
group of 16 alarms.
4.
press ESC to exit the monitoring list.
Fig. 2.4.3 –
Monitor the Expansion points from the M)onitor, E)xpansions menu.
s(Y)stem L)ogin P)orts pa(G)ers A)larms R)elays
a(N)alogs p(I)ng info T)imers D)ate/time n(V)ram (ESC) ? A
B)ase E)xpansions (ESC) ? E
Active Displays : 12, 14, 16
Display Number : 12
ID
Description
Status
1
DOOR ALARM
Alarm
2
COMMERCIAL POWER OUT
Clear
3
UPS GNRTR RUNNING
Clear
4
RECTIFIER 1
Clear
5
RECTIFIER 2
Clear
6
ICY CONDITION
Clear
7
GE2 DE-ICER 1 ON
Clear
8
GE2 DE-ICER 2 ON
Clear
9
GE2 DE-ICER 3 ON
Clear
10
GE2 DE-ICER 4 ON
Clear
11
Clear
12
Clear
13
Clear
14
Clear
15
Clear
16
Clear
ESC to exit Any key to continue
2.4.4 Saving Changes
After are provisioning information has been entered, you must write the changes to NVRAM.
1.
Type ‘V’ for n(V)ram from the E)dit menu.
2.
Type ‘W’ to W)rite the changes into memory.
3.
Once this is completed, reboot the Net Guardian.The configuration will not take effect until the Net Guardian