TECHNICAL REFERENCE
ENGINEERED FOR STORES WITH AMBIENT
CONDITIONS NOT TO EXCEED 75° AND 55%
RELATIVE HUMIDITY. DUE TO ENGINEERING
IMPROVEMENTS SPECIFICATIONS MAY CHANGE
WITHOUT NOTICE. ALL MEASUREMENTS ARE
TAKEN PER ASHRAE-72-2005 SPECIFICATIONS.
HILLPHOENIX REFRIGERATED DISPLAY CASES
FOR SALE IN THE UNITED STATES MEET OR EXCEED
DEPARTMENT OF ENERGY 2017 REQUIREMENTS.
NUMBERS ARE BASED ON STANDARD CASE SIZES.
CONSULT ENGINEERING.
AGB-RG
Service Multi-Deck Merchandiser w/ Rear Load Doors
4', 6' & 8' (Cheese/Meat)
AGB-RG
Rev. Date
Rev. #
Rev. Title
06-27-19
1
NEW STANDARDS
ELECTRICAL DATA
Case
Length
Fans
Per
Case
High Efficiency
Fans
Anti-Condensate
Fans
Drain
Heaters
Optional Defrost
Heaters
Humidification
120 Volts
120 Volts
120 Volts
208 Volts
120 Volts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
Amps
Watts
4'
---
---
---
---
---
---
---
---
---
---
---
6'
---
---
---
---
---
---
---
---
---
---
---
8'
---
---
---
---
---
---
---
---
---
---
---
LIGHTING DATA
Case
Length
Lights
Per
Row
Light
Length
Clearvoyant 4 LED Lighting
(Per Light Row)
Standard Power
(Cornice or Shelf)
High Power
(Cornice)
120 Volts
120 Volts
Amps
Watts
Amps
Watts
4'
2
3'
0.08
9.4
0.20
23.8
6'
2
3'
0.08
9.4
0.20
23.8
8'
3
3'
0.12
14.1
0.30
35.7
GUIDELINES AND CONTROL SETTINGS (DX)
BTUH/ft
Superheat
Set Point @ Bulb
(°F)
Evaporator
(°F)
Discharge Air
(°F)
Discharge Air
Velocity
(FPM)
Conventional
Parallel
RRS
255
200
8 - 10
---
28
---
RRS
255
200
8 - 10
---
28
---
NOTES:
• "---" Indicates that the feature is not an option on this case model and/or the data is not yet available at this time.
• Optional humidification system available to boost humidity. Humidity levels are determined by store aged beef programs.
• RRS - Refrigerated Rear Storage.
• Listed BTUH indicates unlighted shelves. Add the following for lighted shelves:
4' Shelf LED: 36 BTUH
4' Canopy LED: 72 BTUH
3' Shelf LED: 27 BTUH
3' Hi-Output LED: 54 BTUH
• EPR valve for the Serpentine is factory installed.
• Listed discharge air velocity represents the average velocity at the peak of defrost.
• Listed defrost for the Serpentine is tied to the gravity coil.
• DX units equipped with RH systems require 2 defrosts per day with a fail-safe of 120 minutes.
• Glycol units equipped with RH systems require 3 defrosts per day with a fail-safe of 120 minutes.
3