WN 059729 45532 – 2018-11
DE
SLON-DR
Mounting instructions
Contents
1
About this document
1.1 Contents and purpose
This document describes the mounting of the SLON-
DR network adapter (SafeRoute® Local Operation
Network for DIN rail mounting).
1.2 Target group
This document is intended for assembling technicians
and specialists authorized for mounting by
dormakaba.
1.3 Other applicable documents
• Instructions for devices intended for networking
1.4 Symbols used
Components may be damaged by
electrostatic discharge. Ground
your own body before touching a
component!
2 Safety
2.1 Intended use
dormakaba control modules intended for networking
are networked in one building with the help of SLON-
DR network adapters.
2.2 Personnel qualification
Mounting may only be carried out by persons
authorized by dormakaba.
3 Product description
The SLON-DR network adapter enables the
integration of dormakaba control modules into LON
networks. The mounting takes place on a 35 mm DIN
rail in a housing. The housing must at least meet the
requirements of IP 30.
The LON application is loaded in the module ex works.
The control, parameterization and visualization for
the connected devices is carried out via TMS Soft®.
The assignment of network variables (binding) can
be linked to other sensors/actuators (including
external systems). Commissioning takes place with
a commissioning tool (e.g. OpenLNS Commissioning
Tool).
3.1 Parts included
106
92
65
Neuron-ID
xx xx xx xx xx xx