SLON-DR

2018-11

WN 059729 45532

dormakaba Mounting instructions

Mounting

Mounting

3.2  Technical information

Supply voltage:

24 V DC +/- 15 %

Power consumption:

18 mA

Ambient temperature:

-10 °C to +55 °C

Rel. humidity:

up to 93 %  
(non condensing)

Protection class:

Dependent on the 
housing used

3.3  LED display

The LED lights up and flashes red. When the service 
button is pressed, the LED lights up green.
LED on 

    LED flashes              LED off 

    

Module is not configured/no 
application loaded

Module is not configured/ 
application is loaded

                             

Module is fully configured

4  Mounting

The mounting takes place by clipping onto a 35 mm 
DIN rail.

4.1  Requirements for mounting 

Prerequisite for the mounting is compliance with the 
LON specifications regarding transceivers, network 
topology, network lengths, cable specifications, etc.
•  The mounting location of the modules must be 

selected so that the modules’ ambient temperature 
range is maintained and any heat generated can be 
dissipated.

•  A minimum distance of 200 mm to high-energy 

sources of interference, e.g. frequency converters, is 
recommended. 

•  To avoid condensation, modules that have been 

stored at very different temperatures must be 
adjusted to the operating temperature before 
commissioning. 

•  If tools for network management are already used 

in the network, any potential conflicts must be 
identified and excluded before connecting further 

tools.

4.2  Assignment of terminals and button

Neu

ron

-ID

xx x

x xx

xx x

x xx

2

4

V

G

N

D

T

x

D

1

T

x

D

2

G

N

D

T

x

D

3

R

x

D

3

G

N

D

R

x

D

2

R

x

D

1

G

N

D

2

4

V

X1

Service

Status

LED

X302

T

x

2

R

x

2

G

N

D

T

x

3

R

x

3

X300

N

e

B

N

e

t

A

N

e

B

N

e

t

A

Neuron-ID

xx xx xx xx xx xx

Fig. 1 

View of the boards

Summary of Contents for SLON-DR

Page 1: ... Intended use dormakaba control modules intended for networking are networked in one building with the help of SLON DR network adapters 2 2 Personnel qualification Mounting may only be carried out by persons authorized by dormakaba 3 Product description The SLON DR network adapter enables the integration of dormakaba control modules into LON networks The mounting takes place on a 35 mm DIN rail in...

Page 2: ...tions regarding transceivers network topology network lengths cable specifications etc The mounting location of the modules must be selected so that the modules ambient temperature range is maintained and any heat generated can be dissipated A minimum distance of 200 mm to high energy sources of interference e g frequency converters is recommended To avoid condensation modules that have been store...

Page 3: ... port e g dormakaba control module 1 max 15m TxD2 RxD2 RS232 port e g dormakaba control module 2 max 15m RxD3 TxD3 RS232 port e g dormakaba control module 3 max 15m S1 Service button Neuron ID is sent Neuron ID xx xx xx xx xx xx X302 Tx2 Rx2 GND Tx3 Rx3 X300 24V GND TxD1 TxD2 GND TxD3 RxD3 GND RxD2 RxD1 GND 24V X1 Net B Net A Net B Net A 24 V DC GND TxD RxD dormakaba control module Connection to a...

Page 4: ...osal Disassembly is carried out in the reverse order of mounting and must be carried out by qualified personnel The product must be disposed of in an environmentally friendly manner Electro technical parts and batteries must not be disposed of as domestic waste Dispose of electrotechnical parts and batteries in the designated acceptance and collection points Refer to the statutory regulations for ...

Reviews: