G-Ubivis XEA

2020-11

WN 058974 45532

dormakaba Operating instructions

Maintenance from dormakaba

8.1  Replacing battery

The battery must be replaced annually.
•  Observe the warnings on the battery pack.
•  Only use the dormakaba battery pack with item 

number 57650000.

•  The battery may only be replaced by trained 

specialists.

•  Please note date of manufacture on the battery 

pack. The battery may only be installed within 12 
months of the date of manufacture. The battery 
pack must be replaced during annual maintenance.

 1 

1. 

Press the decorative panel at the height of the 
reset button.

2. 

Pull off the decorative panel. 

3. 

Loosen the battery packs’ screws so that the 
battery packs’ holders can be moved.  

4. 

Slide the battery packs to the side and remove 
the battery packs.

 2 

1. 

Wait 30 s before attaching the new battery packs 
so that the control unit can start properly.

2. 

Plug the two new battery packs together. 

3. 

Place the battery packs on the screws and push 
them in the direction of the board. 

 

‣ The LED lights up white for about 2 s. 

 3 

1. 

Fix the battery packs with the screws. 

2. 

Secure the decorative panel to the beam.

3. 

Perform a function test according to Section 5.1.

 

The hold-open system is now in operation. The 
operation indicator flashes green 1 x every 
28 s.

9  Maintenance from dormakaba

Regular maintenance of your units pays off: weak 
points are detected and eliminated at an early stage 
and your unit’s service life is increased.
dormakaba and our authorized partners offer 
premium maintenance service for automatic doors 
and hold-open systems, which gives the building 
operators reliable security through the official seal 
of approval. Because if not all door units have been 
properly tested, the building operator may be liable 
for property damage and personal injury in the event 
of an accident. Regardless of safety aspects, regular 
maintenance also makes sense from an economic 
point of view. Any damage or wear can thus be 
detected and repaired at an early stage. The risk 
of unforeseen costs, such as high repair costs, can 
be minimized – and we help you to keep an eye on 
your budget – always with the aim of increasing the 
service life of your door units. 
dormakaba takes over the complete organization and 
execution of maintenance for you. The advantage 
to you: all units – including units from other 
manufacturers – are tested by trained experts at the 
scheduled regular intervals. The operator does not 
have to worry about anything else; legal requirements 
are reliably fulfilled.
A maintenance contract around the door ensures 
tested functionality with a premium standard!
We want to win you over too – get a non-binding and 
free offer for a maintenance contract. 
Further information on this and many other topics 
of the dormakaba service can be found on our 
homepage at www.dormakaba.com

0 800 524 0246

24h Service Hotline

10  Disassembly, recycling and 

disposal

Disassembly is carried out in the reverse order of 
mounting and must be carried out by qualified 
personnel.

The product must be disposed of in an 
environmentally friendly manner. Electro-
technical parts and batteries must not be 
disposed of as domestic waste. Dispose of 

electrotechnical parts and batteries in the designated 
acceptance and collection points. Refer to the 
statutory regulations for your country.

Summary of Contents for G-Ubivis XEA

Page 1: ...Operating instructions G Ubivis XEA WN 058974 4553215291 2020 11 EN ...

Page 2: ...l 1 4 Documents storage This manual must be kept during the service life of the product and must be passed on with the product Contents 1 About this document 2 2 Safety 3 3 Product description 4 4 Mounting 7 5 Check hold open system 9 6 Completion of mounting 9 7 Operating 9 8 Maintenance and care 9 9 Maintenance from dormakaba 10 10 Disassembly recycling and disposal 10 2 G Ubivis XEA 2020 11 WN ...

Page 3: ...m may only be mounted and used if the underside of the ceiling on both sides of the door is less than 1 m above the lower edge of the lintel Fig 1 1 m Distance to ceiling For smoke permeable subsurface constructions measure the distance to the smoke impermeable ceiling The smoke chamber must be above the clear passage area of the door A separate verification of suitability is required for the resp...

Page 4: ...nleitu ng G U bivis XEA WN 0589 73 4553 2 2018 05 DE 6 7 9 10 11 8 2 3 4 5 1 Parts included Components 1 End caps 2 Beam with smoke detector and battery holder 3 Lever 4 Slide rail with door holding device 5 Mounting plate with control unit 6 Decorative panel 7 Battery pack item no 57650000 Please note date of manufacture on the battery pack The battery may only be installed within 12 months of th...

Page 5: ...ry 28 s TIPS AND RECOMMENDATIONS After changing switch B the battery must be disconnected and reconnected after 30 s to take over the set function 3 2 2 Reset button and control LEDs 3 2 2 1 Reset button The reset buttons are located on the top and bottom of the beam The reset buttons both have the same functions Arming with manual reset To arm the smoke detector after the alarm has been triggered...

Page 6: ... by dormakaba Service 4 x every 7 s Battery almost empty Have the battery replaced by dormakaba Service 5 x every 7 s Magnet system dropped Press the reset button If the door holder is not working call dormakaba Service 6 x every 7 s Door holder failed Press the reset button with the door closed LED flashes red 4 x every 28 s Battery voltage too high if the door holder is not working call the dorm...

Page 7: ...s made 5B TIPS AND RECOMMENDATIONS Mount the slide rail flush with the mounting plate 1 Mount the slide rail on the mounting plate according to DIN R mounting 2 Plug in plug A connection between the slide rail and the control unit is made 6A B 1 Determine the desired size of the door opening angle If the door opening angle is less than 105 then only partially break the perforated area Only break t...

Page 8: ...er fits behind the screws 3 Place the battery packs on the screws and push them in the direction of the board The LED lights up white for about 2 s 4 Fix the battery packs with the screws The hold open system is now in operation The operation indicator flashes green 1 x every 28 s 14 ATTENTION Risk of unit damage Setting a release force too high may result in damage to the door hinges and the fast...

Page 9: ... for hold open systems 6 Completion of mounting If further structural work is carried out protect the smoke detector from dust 1 1 Stick the reset sticker next to the reset button on the bottom 2 Place the supplied dust cover on the smoke slots 3 Before the final commissioning remove the dust cover and carry out a further function test according to Section 5 1 7 Operating 7 1 Open and hold door 1 ...

Page 10: ...n systems which gives the building operators reliable security through the official seal of approval Because if not all door units have been properly tested the building operator may be liable for property damage and personal injury in the event of an accident Regardless of safety aspects regular maintenance also makes sense from an economic point of view Any damage or wear can thus be detected an...

Page 11: ... 11 160 75 428 150 81 58 43 16 11 142 160 8 75 142 428 160 8 16 11 43 81 58 150 75 428 160 43 16 11 43 81 71 150 75 428 150 43 81 71 43 16 11 160 75 max 16 max 16 max 26 max 26 10 10 10 10 min 860 min 860 min 860 107 107 11 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions 4 Mounting min 860 1B 1A 4 Mounting ...

Page 12: ...5 x 30 mm M5 x 20 mm 5 x 30 mm M5 x 20 mm A A B B 1 1 2 2 12 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 3B 3A 2A 2B 4A 4B ...

Page 13: ...M5 x 38 mm 2 0 2 5 Nm M5 x 38 mm 2 0 2 5 Nm M5 x 38 mm 2 0 2 5 Nm M5 x 38 mm 2 0 2 5 Nm 1 1 2 2 13 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 5B 5A ...

Page 14: ... 105 105 105 105 105 105 105 105 M5 x 10 mm 1 5 Nm M5 x 10 mm 1 5 Nm 1 4 4 3 14 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 6B 6A 7 ...

Page 15: ...2 5 5 2 5 8 10 Nm 2 5 3 Nm 140 8 0 1 1 1 3 3 3 2 2 2 4 15 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 9 10 11 8 ...

Page 16: ...1 1 3 3 2 2 4 4 approx 2 s 0 5 Nm 16 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 13 12 ...

Page 17: ...Nm Nm M4 x 10 mm 1 Nm M4 x 10 mm 1 Nm 1 1 1 3 2 2 2 17 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions Maintenance from dormakaba 14 15 16 M3 x 4 mm 1 Nm ...

Page 18: ...918 5 R e s e t 1 0 1 5 c m 1x 1 2 1 2 3 3 18 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions 5 Check hold open system 1 1 5 Check hold open system 6 Completion of mounting ...

Page 19: ...5 1 19 G Ubivis XEA 2020 11 WN 058974 45532 dormakaba Operating instructions 8 Maintenance and care 1 2 3 approx 2 s 0 5 Nm 1 1 1 3 3 3 2 2 2 2 4 8 Maintenance and care ...

Page 20: ...www dormakaba com dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 Translation of original manual subject to change without notice ...

Reviews: