3  Product description

The GSR‑EMF XEA comprises the following 
components: 
•  Slide rail systems
•   Built‑in electromechanical locking device
The G‑EMF XEA is intended for the mounting on the 
hinge side or the opposite hinge side. The GSR‑EMF 
XEA is suitable for DIN‑L and DIN‑R doors.  
When mounting in the opposite hinge side,
a proof of suitability in conjunction with the 
respective
fire/ smoke protection door is required.

3.1  EMF

The EMF is an electromechanical locking mechanism 
with adjustable release force, which enables locking 
the door without spring back. After a cut‑off of power 
supply, the locking device disengages and the door will 
be closed securely through the door closer.

3.2  Technical data

Operating voltage:

24 V DC  
in France also 48 V DC

Power consumption:

1.4 W 
in France also 2.2 W

Duty cycle:

100 % ED

Release torque:

approx. 25 – 65 Nm at 90°  
opening angle (dependent 
on the set closing force on 
the closer)

Door opening angle:

max. 140°

The drive happens via an external RMZ.

4  Installation

The mounting of the slide rail system takes place 
directly on the base of the door lintel or optionally 
with an additional mounting plate (extras).

4.1  Prepare the mounting of the 

slide rail

The slide rail can be mounted in two different options:
Option 

A

 = Mounting on the hinge side 

Option 

B

 = Mounting on the opposite hinge side

1. 

Prepare the power supply (24 V/48 V DC) from the 
smoke detection panel to the EMF in version with 
EMF.

2. 

Mark the fixing points for the closer and the slide 
rails according to the hole pattern.

3. 

Drill the holes.

4. 

Drill the hole for the connection cable 
24/48‑V‑Anschlusskabel with Ø 8 mm.

5. 

 Lay  the  lines.

4.2  Mount the slide rail

1. 

Mount the base.

2. 

Insert all cables into the intended openings.

3. 

Lead the connection cable downwards.

4. 

Tighten the slide rail.

5. 

Clamp the 24/48‑V connection cable to the slide 
rail. 

6. 

Put the cable into the hollow space of the end 
piece.

4.3  Mount the door closer

1. 

Mount the door closer and lever to the door leaf 
according to the enclosed instructions for the 
door closer. 

2. 

Adjust the door closer.

3

G-EMF XEA

2017-10

dormakaba Installation manual

WN 059411 45532

Product description

Summary of Contents for G-EMF XEA

Page 1: ...ation of catching devices 2 3 Product description 3 3 1 EMF 3 3 2 Technical data 3 4 Installation 3 4 1 Prepare the mounting of the slide rail 3 4 2 Mount the slide rail 3 4 3 Mount the door closer 3 5 Start up 4 5 1 Set the fixture point 4 5 2 Set the release force 4 5 3 Mount the paneling 4 5 4 Check locking 4 6 Operating 4 6 1 Open and lock door 4 6 2 Close door 4 7 Dismounting recycling and di...

Page 2: ...nverted Illustration shows mounting DIN R on the hinge side Mounting DIN L takes place mirror inverted 1 4 3 Tool symbols Allen wrench e g wrench size 3 1 5 Glossary EMF Electromechanical locking device RMZ Smoke detection panel TS Door closer 2 Safety 2 1 Intended use The catching device is used to keep open door leaves The locking mechanism is used in conjunction with external RMZ to keep open f...

Page 3: ...xternal RMZ 4 Installation The mounting of the slide rail system takes place directly on the base of the door lintel or optionally with an additional mounting plate extras 4 1 Prepare the mounting of the slide rail The slide rail can be mounted in two different options Option A Mounting on the hinge side Option B Mounting on the opposite hinge side 1 Prepare the power supply 24 V 48 V DC from the ...

Page 4: ...width and the selected size of the closing contact According to the DIN EN 1155 the release force must not be less than 40 Nm at a door opening angle of 90 and not more than 120 Nm 1 Set the release force 2 Control the release force 5 3 Mount the paneling 1 Attach the end caps 2 Mount the paneling of the glide rail 5 4 Check locking 1 Open the door leaf and lock it 2 Cut off power supply The door ...

Reviews: