Installation
Technical Manual
24
1220013692 - 11/2017
dormakaba digital cylinder
4.2.3
Function check on anti-panic digital cylinder
After installing an anti-panic digital cylinder, a function check must be carried out.
WARNING
Risk of personal injury or death.
•
After installing the digital cylinder in a panic lock, a function check must be carried out.
It must be possible to open the lock with the lever handle in all cam rest areas.
•
For emergency exit or panic door locks, it is vital that the specifications of the lock and fit-
tings manufacturers are observed.
A spring mechanism in the locking cylinder ensures that the cam cannot be positioned in an
area that is not authorised for panic locks.
3
9
6
12
a)
upper authorised rest area
3
9
6
12
b)
lower authorised rest area
Check the reset function as shown:
Check that the lock functions correctly
3
9
6
12
1.
Turn the inner door knob upwards until it cannot be reset.
(Rest area pointing up at 12 o'clock).
Note:
If there is no inner door knob, use the outer door
knob.
2.
Press the handle.
The lock should unlock.
3
9
6
12
3.
4.
Turn the inner knob downwards until it cannot be reset.
(Rest area pointing down at 6 o'clock.)
Press the handle.
The lock should unlock.
Check that the locking cylinder is functioning correctly
3
6
12
1.
Turn the inner door knob to the 11 o'clock position and re-
lease it.
The inner door knob should turn back automatically.
3
6
12
2.
Turn the inner door knob to the 1 o'clock position and re-
lease it.
The inner door knob should turn back automatically.