G-SR EMR
—
4
DORMA
Fixing Instructions
Technical Data RMZ
Input:
230 V AC +10% / –15%
120 mA / 28 VA / 50 Hz
Output:
24 V DC / 460 mA / 11 W
Type of protection: IP 30
Protection class:
II
Smoke switch:
24 V DC / 50 mA
Temperature:
–20°C / +60°C
Rel. air humidity: max. 93% without condensation
Technical Data EMF
Operating voltage: 24 V DC
Power input:
1,4 W (GSR EMR2 = 2,8 W)
Rated for
continuous duty:
100% ED
Release torque:
approx. 25 – 65 Nm at an opening angle
of 90° (dependent upon the strength
setting of the door closer).
Door opening angle: max. 130°
The unit is controlled by the RMZ smoke detector.
Work on electrical equipment and systems may only be
performed by properly trained specialist personnel.
•
Check to ensure that the line power supply (230 V AC)
has been disconnected and is no longer live.
•
10A/B miniature circuit breaker must be provided in
the supply circuit. This can also be used as the isolator
for disconnecting the RMZ and making it dead.
•
The power cable leading to the RMZ must be properly
secured to ensure effective strain relief.
•
The power cable (NYM) conductor cross section should
not be greater than max. 1.5 mm
2
. The PE conductor
is not electrically utilised. The terminal (PE) should,
however, be used where a PE conductor is provided.
•
Fire/smoke detectors controlling hold-open systems
must not be used to actuate any further alarm devices
(e.g. fire alarm transmission systems).
+
1)
•
If the optional alarm module is installed, the cable
connecting it to the smoke switch must be led over and
across the measurement chamber in order to ensure
that smoke penetration is in no way hindered.
Approval certification
The G-SR has been approved by the State Material Testing
Authority, Dortmund, for use on double (two-leaf) fire/smoke
check doors in Germany.
A separate approval certificate is required in conjunction
with the fire/smoke check door concerned (e.g. where DIN
standards apply) – check local regulations.
Abbreviations
G
= Active leaf
S
= Inactive leaf
GSR
= Slide channel-type door co-ordinator
GSR EMR 1
= with electro-mechanical hold-open
for the inactive leaf
GSR EMR 2
= with electro-mechanical hold-open
for the inactive and active leaves
GSR EMR 1G = with electro-mechanical hold-open
for the active leaf
À
RMZ smoke detector
Á
Electro-magnetic hold-open device
Â
RM smoke detector
Ã
DORMA HT manual release pushbutton
for hold-open devices (optional).
This pushbutton must not be concealed by the door
when in its hold-open position.
+
1)
a
Installation arrangement of the RMZ lintel-mounted
smoke detector for applications where the bottom
surface of the ceiling is less than 1 m above the
bottom edge of the lintel on one or both sides of the
door.
+
1)
See separate sheet for associated connection diagrams.
b
If the bottom surface of the ceiling is more than 1 m
above the bottom edge of the lintel on one or both
sides of the door, two ceiling-mounted smoke detectors
must be installed in addition to the lintel-mounted
detector.
+
1)
See separate sheet for associated connection diagrams.
The slide channels are non-handed, i.e. suitable for
LH and RH doors.
The following describes the fixing process for a
left-handed (ISO 6) active leaf. The procedure for a
right-handed (ISO 5) active leaf should be adapted
accordingly.
1
Drill all the fixing holes for the closer, slide channel
and base unit.
2
Drill holes for the 10 mm dia. 230 V AC power
feed cable by others and for 8 mm dia. cabling for
connection of any ceiling-mounted smoke detectors
and manual pushbuttons.
3
Fix inactive leaf slide channel.
4
Lead EMF cable from inactive leaf and cable supplied
for connecting the RMZ through/in behind the base
unit, using the clips in the base unit to hold both
cables in place
À
.
Lead all other cables through the base unit
Á
and fix
base unit in place
Â
ready for mounting the RMZ.
Secure cables to frame to prevent damage during the
installation work
Ã
.
5
Fix active leaf slide channel.
Fit the closer body and arm in accordance with the
TS 93 B fixing instructions, and adjust both door
closers as required.
6
Measure dimension X
À
.
Shorten connecting rod
Á
to
X-47 (TS 93 EN 2-5)
X-43 (TS 93 EN 5-7).
7
Open both door leaves
À Á
.
Ensure that the adjustment sleeve has been fully
wound in
Â
.
Insert the connecting rod into the adjustment sleeve
of the active leaf slide channel
Ã
, and then place in
the plastic slider of the inactive leaf slide channel
Ä
.
EN
1)
AAuPZF of the Deutsches Institut für Bautechnik, Berlin
Summary of Contents for G-SR EMR
Page 26: ...G SR EMR 26 DORMA ...
Page 27: ...G SR EMR 27 DORMA ...