background image

NO

NC

N.O.

N.C.

C.

NO

NC

NO

NC

GREASE SIDES OF KEEPER

BEFORE ASSEMBLY

GREASE PINS

AND BOTTOM OF CASE

GREASE
BOTTOM OF CAM

AND PLUNGER PIN

 FRONT VIEW
 FAIL SAFE

SHOWN LOCKED

GREASE
CAM SLOT AND BOTH
CAM SURFACES
BETWEEN PLUNGER

   FRONTVIEW
 NON-FAIL SAFE

SHOWN UNLOCKED

LOCK

UNLOCK

PUSH BUTTON SWITCH CONDITIONS

VOLTAGE

N.A.

.06

6.3

2100

120

N.A.

.13

6.1

380

48

N.A.

.25

6

96

24

N.A.

.51

6.1

23.5

12

DC

AC

N.A.

.97

5.8

6.2

6

12

24

120

.16

.06

6.3

500

5.8

.24

23.5

.69

1.33

.45

5.4

6.2

AMPS INRUSH

AMPS SEATED

WATTS SEATED

ELECTRICAL RATINGS FOR

ALL 110 STRIKE SOLENOIDS

RESISTANCE IN OHMS ± 10%

NOTE:

1. * = WIRES COLOR CODE:

    6 THRU 120 VDC - YELLOW / BLACK TRACER
    12 & 24 VAC - GRAY
    120 VAC - WHITE

2. UNUSED WIRES TO BE INDIVDUALLY
    ISOLATED WITH A WIRE NUT OR EQUAL.

3. NUMBERED FIELD CONNECTIONS REFER

    TO PIN LOCATION IN FIELD RECEPTACLE.

Door shown closed and locked

GREEN LIGHT - CLOSED (LOCKED)

RED LIGHT - OPEN (UNLOCKED)

G

CONTROLS SHOWN FOR REFERENCE ONLY

R

   Door shown closed
 and locked. Dead Bolt

extended into faceplate

ORANGE    5

GRAY    7

PURPLE     8

         OPTIONAL
       DBS SWITCH

Not available with LCBMA

PIN LOCATION

FIELD RECEPTACLE

9

8

7

6

5

4

3

1

2

DC SOLENOID

ATTACHMENT OF NEW RECTIFIER

DC SOLENOID

(Required when supplying AC power

to a unit with a DC solenoid)

(Required when supplying AC power

to a unit with a DC solenoid)

ATTACHMENT OF OLD RECTIFIER

BROWN

-

BLAC

K

Y *

BROWN

TERMINAL
STRIP

YELLOW

YELLOW

BROWN

+

Y *

TERMINAL
STRIP

-

+

BRIDGE
RECTIFIER

Rating:

Two Amps At Any
Solenoid Voltage

BROWN

YELLOW

BL

AC

K/

YEL

L

O

W

RE

D

Rating:

Two Amps At Any
Solenoid Voltage

BRIDGE
RECTIFIER

BL

AC

K/

YEL

L

O

W

     T

R

A

C

E

R

BL

AC

K/

YEL

L

O

W

     T

R

A

C

E

R

R B Y *

+   -

CONTROL
POWER

+   -  G

INDICATION

  POWER

FAIL SAFE CONTROLS

R G

Typical Control
Schematic for

Reference Only

PUSH
BUTTON

TERMINAL
STRIP

08101631

4 of 7

05/09

INS NO.

PAGE

Rev.

Summary of Contents for ES 110-4 Series

Page 1: ...for use in fire rated doors can only be operated by momentary contact switching energized only when the push button is held depressed and cannot be held in the unlocked position 2 FAIL SAFE When powe...

Page 2: ...heck for proper voltage being supplied to the strike Check all wiring Check the coil resistance of the solenoid and compare it to the chart located on the wiring diagram to ensure the correct solenoid...

Page 3: ...24 x 3 8 HEX WASHER HEAD CAP SCS 2 Remove the upper cover held on by two 2 4 40 x 3 16 PHMS Removal of the upper cover should be done slowly because the locking cam spring may snap out of place Also...

Page 4: ...PIN LOCATION IN FIELD RECEPTACLE Door shown closed and locked GREEN LIGHT CLOSED LOCKED RED LIGHT OPEN UNLOCKED G CONTROLS SHOWN FOR REFERENCE ONLY R Door shown closed and locked Dead Bolt extended in...

Page 5: ...IRING DIAGRAM R G Typical Control Schematic for Reference Only PUSH BUTTON TERMINAL STRIP AUXILIARY SWITCH LBM PURPLE ORANGE BROWN 9 3 6 1 4 Y R B BLACK RED YELLOW BLUE SOLENOID Lock Cam Bolt Monitor...

Page 6: ...TRIKE PREP LOCATION Measure distance from the mounting surface to tip of bolt This is DIM X DIM Y DIM X 3 32 2mm DIM Y is from edge of stop to centerline of prep Calculation assumes 3 32 2mm thick sil...

Page 7: ...ILL VARY PER FEATURES OF STRIKE 2 CUT OFF ALL EXCESS WIRE NOT REQD FOR INSTALLATION 3 WIRES TO BE RUN FROM SIDE REAR OF STRIKE TO CONDUIT CONNECTION 4 ALL WIRING CONNECTIONS TO BE MADE AT THIS END OF...