EM 3000-EW AH 

 

 
 
 

EARLY WARNING 

ELECTROMAGNETIC LOCK 

 
 

 
 
 

INSTALLATION 

 
 
 
 
 
 
 
 
 
 

Version 1.8 EN / 03/2008 / www.dorma.com/fr

 

 

A. INTRODUCTION 

 

The EM 3000-EW AH is a specialized electromagnetic lock equipped with an “Early Warning 
Alarm Functions” intended for use as “A Security Door Lock” which capable of detecting early 
intruders before the attempted break-in. 
 
It can also works as a “Delay Egress Functions” intended for use as “An Emergency Delayed 
Exit Door Lock”. It has a built in Exit Delay Timer using initiate device and our patented 
special mechanism and hardware to operate the Local Alarm Relay and the Remote Alarm 
Relay. In the normal position, the door is fail safe (power to lock), we do not need any touch 
sense bar or look for a exit button to exit, just by a slight push to the door will start the exit 
sequence, the push would displaced the micro-switch operating arm which is the initiate 
device from it’s original position of being pressed to the open position, this is done thru the 
bearing screwhead that glide the entire lock within the aluminum body cast and stretchy 
screw bolt to retracts the magnetic lock back to it’s original position.   

------------------------------------------------------------------------------------------------------ 

EM 3000-EW AH can be selected function as: : 

ƒ

 

A Security Door Lock :   

 

 

 

Dip Switch 5 is set to ON   

ƒ

 

An Emergency Delayed Exit Door Lock :   

Dip Switch 5 is set to OFF. 

------------------------------------------------------------------------------------------------------ 

 

B. DELAY EGRESS FUNCTIONS 

 

In the normal condition, the door is fail safe (power to lock) and locked, the local buzzer is off, 
the Local Alarm Relay (SPDT, 1C) is deenergized and the Remote Alarm Relay (DPDT, 2C) is 
energized. 
   
The system will start the exit sequences by just slightly pushing the door to enter the 
Nuisance Delay Period which can be set for 0, 1, 2 or 3 seconds depends on the building 
codes, at the same time the Local Alarm Buzzer will sound pulsingly and the Local Alarm 
Relay will be energized, warning that someone may want to exit, if that person wants to exit, 
he or she must maintain pressure on the door until the end of the Nuisance Delay Period and 
if he or she backs off before the time set, both the Local Alarm Buzzer and the Local Alarm 
Relay will stop/be deenergized, and revert to normal operation. The purpose of Nuisance 
Delay Period is to take the accidental triggering the sequence into consideration. 
 
Once the Nuisance Delay Period time out, the Release Delay Period begins and can be set 
for 15 or 30 seconds depends on the building codes, at the same time the Remote Alarm 
Relay will be deenergized and the Local Alarm Buzzer will go from pulsing to steady to inform 
the person at the door that he needs no longer to push the door. Please note the total 
Release Delay Time also includes the Nuisance Delay Time. 

 

Once the Release Delay Period time out, the lock is released, at the same time both the Local 
Alarm Buzzer and the Local Alarm Relay will stop/be deenergized. 

 

Once the lock is released, Reset Switch Input from OPEN to CLOSE resets the system to the 

Summary of Contents for EM 3000-EW AH

Page 1: ...on the door is fail safe power to lock and locked the local buzzer is off the Local Alarm Relay SPDT 1C is deenergized and the Remote Alarm Relay DPDT 2C is energized The system will start the exit se...

Page 2: ...fast Sound pulsingly Voice IV ON OFF Exit Switch to Open Red on OFF Voice III OFF OFF Local Normal Condition Nuisance Delay Release Delay Door Release Reset to Power on Door Locked Period Normal Condi...

Page 3: ...ry setting Not BOCA Dip switch 4 ON 1 5 S e c R e le a s e D e la y D ip S w itc h 1 3 0 S e c 1 O N 0 S e c N u is a n c e D e la y D ip S w itc h 2 3 2 3 4 1 S e c 2 S e c 3 S e c N o n B O C A B O...

Page 4: ...t Max 8 second periods for Voice III Voice IV Illegal intruder The security alarm is activated Security personnel has been alerted and would arrive momentarily Max 10 second periods for Voice IV Voice...

Page 5: ...em will start the delay sequences only when these two inputs are shorted Voice Control Output S2 S1 G 5V Four terminal block outputs to control Voice Module Request to Exit Input EXIT Normally Open Th...

Page 6: ...message by speaking to the microphone on the voice module or by connecting ANA to computer earphone output and playback the voice message thru such as Windows Media Player The messages can also be rec...

Page 7: ...nly when Reset Switch Input from open to close NOTE NOTE N Buzzer Off Buzzer Off Flow Chart for NFPA 101 N Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Di...

Page 8: ...Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Dip Switch Setting Dip1 On 15 Sec Off 30 Sec Dip2 Dip3 On Off 1 Second Dip4 Off Power On Locked Door Pushing...

Page 9: ...to close NOTE NOTE N for CANADA Buzzer Off Buzzer Off Flow Chart for BURGLAR ALARM N Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Power On Locked Door Pus...

Reviews: