Conversion to a different gas category
Instruction Manual DR-FC
37
is
n
Remark
In the event the supply pressure for a gas category is the same as the burner
pressure (see the gas tables in paragraph
) then the gas control must be
fitted with a flat sealing plate with cork gasket. A burner pressure that
deviates in comparison to the supply pressure requires the use of a burner
pressure regulator with rubber gasket. Each conversion kit contains all the
necessary components.
12. If the flat sealing plate or burner pressure regulator need to be replaced:
-
Unscrew the connector
from the gas control.
-
If necessary, remove the flat sealing plate
or burner pressure
regulator
.
-
If necessary, fit the flat sealing plate or burner pressure regulator
supplied with the conversion kit.
-
Refit the connector to the gas control.
13. Refit the connector
of the hot surface igniter and flame probe to the
controller.
14. Re-fit the three-part gas coupling
c
Note
15. Check the burner and supply pressure (see paragraph
).
16. Replace the cover.
Legend
g
burner pressure regulator
h
burner pressure control cap
i
burner pressure control
adjusting screw
jJ
connector
k
flat sealing plate
l
supply pressure test nipple
m
burner pressure test nipple
Figure 3.13
Conversion of gas control
!
7
0
@
#
8
9
IMD-0079
Summary of Contents for DR-FC 25
Page 2: ...2...
Page 16: ...Functioning of the water heater 16 Instruction Manual DR FC 2 gis...
Page 42: ...Filling and draining 42 Instruction Manual DR FC 4 gis...
Page 46: ...The control panel 46 Instruction Manual DR FC 5 gis...
Page 50: ...Status of the water heater 50 Instruction Manual DR FC 6 gis...
Page 56: ...Starting up and shutting down 56 Instruction Manual DR FC 7 gis...
Page 68: ...Main menu 68 Instruction Manual DR FC 8 gis...
Page 72: ...Service program 72 Instruction Manual DR FC 9 is...
Page 88: ...Troubleshooting 88 Instruction Manual DR FC 10 gis...
Page 90: ...Maintenance frequency 90 Instruction Manual DR FC 11 gs...