Donaldson BOFA AD 350 User Manual Download Page 12

Installation 

 
 
 

Optional added features 

The unit can be configured to suit customer specification. 
These optional extras would be discussed, arranged and 
installed prior to delivery.  
(

If unsure what features your system is equipped with 

please contact the seller with the unit serial number, 

(Refer to section

 

2

 

for location) 

who will be able to advise 

what specification has been supplied.

 

 

Remote Stop/Start feature 

Enables the extraction unit to be remotely turned On / Off 
via an external signal. 

Note: Care must be taken to ensure that the system is 
correctly wired in order for the extraction unit to function 
correctly. 

DC Voltage input 

This configuration requires the Black & Red cores of the 
signal cable (Refer to section 

1

 

for location) to be connected 

to a known and tested DC power supply, in order to start the 
extractor. The signal needs to be connected to a double 
insulated DC power supply. 
 
The operating voltage for this signal is 24VDC. Only this 
voltage should be connected. Voltages connected outside of 
this range may cause irreversible damage to the relay. 

Red cable = V+ 
Black cable = V- 

When the extractor is provided with the correct DC voltage 
the motor will start and maintain the set flow rate (Refer to 
section 

5

 for how to set the flow) when the DC voltage is 

removed the motor will slow down and come to a stop. 

The extractor will need to be turned on (See section 

5

 

for 

turning the extractor on) in order for this feature to operate. 

Override 

Enables the extractor to operate fully with or without either 
DC voltage input or the Volt free input. 
The override feature can be toggled On / Off by a switch 
mounted on the internal motor access panel (see below for 
switch location)  
 

Switch in “On” position

 

In this position the extractor will require a start signal (either 

Voltage input or Volt free, depending on the requested 
specification) to enable the motor within the extraction unit. 

Switch in “Off” position

 

In this position the extractor motor will run without the 
requirement for an external start signal. This feature is 
useful for engineers carrying out works/ tests on the 
extractor without the need for the laser / auxiliary signal 
being present.   

Filter Blocked / System Fail Signal 

With this option the extraction system will output a signal to 
alert the user when the extractor has failed or when the 
filters are blocked. 

 

This feature will not directly stop the extractor from running 
correctly, but if fitted this feature should be terminated 
correctly before power is applied to the extraction system. 
 

Connection specification 

This signal is available via the Green and White cores of the 
signal cable. The system will provide a volt free Open / 
Closed signal that can be connected to an external interface, 
beacon or warning device following the specification below. 
The signal needs to be connected to a double insulated DC 
power supply. 

 

Maximum input voltage: 24V AC 

 

 

Maximum current load: 3A @ AC 
OR

 

 

Maximum input voltage: 24V DC

 

 

Maximum input load: 3A @ DC

 

Filter Signal 

When the filters become blocked or the system develops a 
fault the connection between the Green & White cables will 

become “Open”

 

When the extraction system is running normally the 
connection between the Green & White cables will become 

“Closed”

 

 

 

 

 

 

 

 

 

 

03 

Summary of Contents for BOFA AD 350

Page 1: ...VER 3 0 01 2020 AD 350 USER MANUAL...

Page 2: ...anel 1 01 02 Important safety notes Safety labels 2 01 Unpacking and unit placement 3 01 Turning extractor on adjusting airflow 5 01 02 Cleaning the unit Filter replacement 6 Consumable spares filter...

Page 3: ...Overview Control Panel Feet Clips Handles 01 1...

Page 4: ...Overview Air Inlet Mains Inlet Signal Cable Inlet Air Outlet Motor Cooling ON OFF Switch 02 1...

Page 5: ...Overview Flow Adjustment Company Branding Filter Blocked Filter 75 full System Running Clean VOC Alarm 03 1...

Page 6: ...supply before removing the pump motor access panel 2 Use only as described in this manual 3 Connect the system to a properly grounded outlet Dangers to eyes breathing and skin Once used the filters w...

Page 7: ...t the extraction unit including Company name Address Contact number Extractor model Unit serial number Operating voltage range Maximum current load Operating frequency Year of Manufacture Relevant app...

Page 8: ...gases or with particulates which can be pyrophoric can spontaneously ignite without implementation of additional precautions It is essential that nozzles or other extraction fume capture devices and h...

Page 9: ...0 mm space is available around any vented panels on the extractor to ensure adequate airflow 2 Check the filter is located in its correct position before replacing the lid and securing the clips Cauti...

Page 10: ...uld be kept to a minimum where possible to prevent the fume being blown away from the nozzle High speed lines may need bigger scoops or nozzles both sides of the product because of the turbulence caus...

Page 11: ...replaced by a BOFA engineer as an electrical safety test may be required after replacement The unit MUST be connected to a properly earthed outlet If your system was ordered with any optional extras p...

Page 12: ...ther DC voltage input or the Volt free input The override feature can be toggled On Off by a switch mounted on the internal motor access panel see below for switch location Switch in On position In th...

Page 13: ...correct flow is maintained to compensate for any loss in performance caused by the added restriction of the partially blocked filters The extractor and all pipe work must be fully installed and conne...

Page 14: ...e of unauthorised replacement filters may result in a potentially dangerous situation and or damage to the extractor unit and will invalidate the manufacturer s warranty Cleaning the unit The powder c...

Page 15: ...e detailed below 1 Isolate the electrical supply to the extractor 2 Undo the two clips on the sides of the unit and remove the motor section using the two handles on the sides of the lid 3 Lift the fi...

Page 16: ...Date Engineer Combined Filter Date Engineer Filter disposal The combined filter is manufactured from non toxic materials Filters are not re usable cleaning used filters is not recommended The method o...

Page 17: ...E UL cUL Size Metric mm Imperial inches Height 590 23 2 Depth 465 18 3 Width 405 15 9 Filters Filter Type Surface area Efficiency Pre Filter 6m2 95 0 9 microns HEPA Filter Combined filter 2 1 m2 99 99...

Page 18: ...Dorset BH17 7DU UK Tel 44 0 1202 699 444 Email sales bofa co uk German Office Sudring 62 D 21465 Wentorf bei Hamburg Germany Tel 49 0 40 739 3735 15 Email vertrieb bofa co uk BOFA Americas Inc 303 S...

Page 19: ......

Page 20: ...ocal Exhaust Ventilation Systems Company System Designation System Installation Date Designated Person Inspection and Maintenance Schedules 1 Daily checks 2 Weekly inspection of process enclosure extr...

Page 21: ...not recorded 2 Weekly Inspection Weekly inspection by supervisor of physical condition of extract devices nozzles enclosures hoses and extraction unit for damage change parts added or removed and corr...

Page 22: ...s and extraction unit for damage change parts added or removed and correct operation etc Check also that daily inspections have been completed Tick boxes to confirm system ok change Add details of any...

Page 23: ...ges to Engineering Manager Record any remedial actions taken Month number Date System ok System Change Details of change repairs etc Initial 1 2 3 4 5 6 7 8 9 10 11 12 4 Yearly Inspection Annual servi...

Reviews: