Maintenance  

 
 
 
 
 
 
Maintenance UK 
 

It is a legal requirement, under regulation 9 of the COSHH 
regulations that all local exhaust ventilation systems are 
thoroughly examined and tested at least once every 14 
months (typically carried out annually). The approved code 
of practice recommends that a visual check should be 
carried out at least once a week. 
 
COSHH requires the annual inspection and testing to be 
carried out by a competent person and specifies that 
documentation results are recorded in a log.  
 
Contact the seller for more information about inspection 
and certification.  
 

Maintenance General 
 

User maintenance is limited to cleaning the unit and filter 
replacement, only the manufacturers trained maintenance 
technicians are authorised to carry out component testing 
and replacement. Unauthorised work or the use of 
unauthorised replacement filters may result in a potentially 
dangerous situation and/or damage to the extractor unit 
and 

will invalidate the manufacturer’s warranty.

 

 

Cleaning the unit 

 
The stainless steel units should be cleaned with a 
proprietary stainless steel cleaner, in accordance with the 

manufacturer’s user instructions.

 

 
The powder coat finish can be cleaned with a damp cloth 
and non-aggressive detergent, do not use an abrasive 
cleaning product as this will damage the finish. 
 
The cooling inlets and outlets should be cleaned once a year 
to prevent build-up of dust and overheating of the unit. 

 
 
 

Filter Information 

 
A log of filter changes should be maintained by the user. 
The filters require attention when the display shows the 
configuration shown on the next page or when the extractor 
no longer removes fume efficiently. 
 
It is recommended that a spare set of filters are kept on site 
to avoid prolonged unit unavailability. Part numbers for 
replacement filters can be found on the filters fitted in your 
system.  
 
To prevent overheating, units should not be run with a 
blocked filter condition, or with dust obstruction of Inlets / 
Outlets. 

 
Fire Risk Warning 
 

In the very rare event that a burning ember or spark is drawn 
into the fume extraction unit, it may be possible that the 
filters will ignite. 

Whilst any resultant fire would typically be retained within 
the fume extraction unit, the damage to the extractor would 
be significant. 

It is therefore essential to minimise this risk by undertaking 
an appropriate assessment to determine:- 

a)

 

Whether additional fire protection equipment should be 
installed.  

b)

 

Appropriate maintenance procedures to prevent the risk 
of build-up of debris which could potentially combust 

This unit should not be used on processes where sparks 
could occur, with explosive dusts and gases, or with 
particulates which can be pyrophoric (can spontaneously 
ignite), without implementation of additional precautions.  

It is essential that nozzles or other extraction/ fume capture 
devices and hoses/pipework are cleaned regularly to prevent 
the build-up of potentially ignitable debris

 

 

 

 

 

 

01 

Summary of Contents for 30105519-1313

Page 1: ...AD Nano USER MANUAL V1 May 15...

Page 2: ...npacking and unit placement 3 01 02 Connecting to power supply Optional interfacing 4 01 Turning extractor on 5 01 02 Important safety notes Safety labels 2 01 02 Cleaning the unit Filter replacement...

Page 3: ...Overview Mains Isolation Switch Control Panel Lockable Castors Door Latches Combined Filter Combined Filter Lever Pre Filter 01 1...

Page 4: ...Overview Mains Inlet Signal Cable Inlet Optional Exhaust Outlet Air Outlet Air Inlet 02 1...

Page 5: ...Overview Main Isolation Switch Company Branding Filter Blocked Filter 75 full System Running Clean 03 1...

Page 6: ...moving the pump motor access panel 2 Use only as described in this manual 3 Connect the system to a properly grounded outlet Dangers to eyes breathing and skin Once used the filters within the AD Nano...

Page 7: ...acture Relevant approval markings logos PLEASE NOTE If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment maybe compromised Fire Risk Warning...

Page 8: ...t should be used and with regard to appropriate safety precautions See Appendix for product weight details Ensure that 500 mm space is available around any vented panels on the extractor to ensure ade...

Page 9: ...nit should not be connected to the mains The supply cord should only be replaced by a BOFA engineer as an electrical safety test may be required after replacement The AD Nano MUST be connected to a pr...

Page 10: ...PCB Red cable V Black cable V When the extractor is provided with the correct DC voltage the motor will start and maintain the set flow rate Refer to section 5 for how to set the flow when the DC volt...

Page 11: ...images below to identify the switch your AD Nano unit uses Powder Coated Version Press the main isolation switch to the On position Refer to section 1 for switch location by depressing the I side of t...

Page 12: ...prevent build up of dust and overheating of the unit Filter Information A log of filter changes should be maintained by the user The filters require attention when the display shows the configuration...

Page 13: ...orn when changing filters To remove and replace the pre filter follow the procedure detailed below 1 Isolate the electrical supply to the unit 2 Open the door of the unit 3 Remove the lower pre filter...

Page 14: ...tured from non toxic materials Filters are not re usable cleaning used filters is not recommended The method of disposal of the used filters depends on the material deposited on them For your guidance...

Page 15: ...l Below 60dB A at typical operating speed Size Metric mm Imperial inches Height 797 31 4 Depth 435 17 2 Width 377 14 9 Filters Filter Type Surface area Weight Efficiency Pre Filter 6 0 m F8 Combined F...

Page 16: ...Creekmoor industrial Estate Poole Dorset BH17 7DU UK Phone 44 0 1202 699 444 BOFA Americas 303 S Madison Street Staunton Illnois 62088 USA Phone 1 618 205 5007 BOFA International GmbH Sudring 62 D 21...

Reviews: