17
Donaldson Company, Inc.
Filter Removal
1. Start at the top access port.
2. Remove access cover by lifting latch handle and
lifting cover to remove from yoke.
If the access cover clamp fails to operate smoothly,
apply a lubricant to the riveted pivot points and to the
clamp rod where it passes through the outside of the
cover. Wipe off over spray.
3. Break the seal between the filter cartridge and the
sealing surface.
4. Slide the filter out the access port along the
suspension yoke and dispose of properly.
5. Clean the sealing surface with damp cloth.
Clean dust from gasket sealing
area to ensure a positive filter
gasket seal.
6. Check for an accumulation of dust in the storage
area and empty as necessary.
Filter Installation
1. Slide the new filter cartridge onto each suspension
yoke.
Note: Insert the filter gasket-end first.
2. Wipe cover gaskets clean and replace covers by
attaching cover to yoke hook and firmly latching
cover handle.
Replace access covers carefully by securing them
using the handle provided. Keep fingers away from
the sealing surface to avoid pinching.
Check that access covers
are seated and seal properly.
Gaskets must be compressed to ensure an
airtight seal.
3. Reset exhaust damper control to fully closed
position.
4. Turn electrical power and compressed air supply ON
before starting collector.
Dust Disposal
1. Empty dust container(s) as necessary to minimize
dust in the hopper.
2. Replace or reinstall dust container(s).
Compressed Air Components
1. Periodically check the compressed air components
and replace damaged or worn components as
necessary.
2. Drain moisture following the manufacturer’s
instructions.
3. With the compressed-air supply ON, check the
cleaning valves, solenoid valves, and tubing for
leaks. Repair or replace as necessary.