5.1 Ceiling support installation: 

 Use and install 

only parts furnished by the manufacturer of  the 
chimney.

5.2  Chimney lengths installation: 

Continue 

with the installation of the chimney by 
positioning lengths with the male end up.  The 
attic insulation must never be in contact with the 
chimney.  Allow at least 2" (50 mm) for air space 
between the chimney and any combustible 
material.

5.3 Minimum chimney height above the roof:

 

(Drawing 3):

 Extend the chimney at least 3 feet 

(1 m) above the roof or 2 feet (610 mm) above 
any construction element within 10 feet (3 m) of 
the chimney.

5.4  Flashing water tightness:

 Install a metal 

roof flashing with a storm collar where the 
chimney pass meets the roof. Seal the joint 
between the chimney and the storm collar and the 
joint between the roofing and the flashing.

4.2  Maximum allowed offsets:

 Don't install 

more than 4 elbows in the chimney.  Offsets 

5.5   Roof braces: 

Any chimney that extends 

cannot be more than 30 degrees from the vertical 

more than 6 feet (2 m) above the roof needs to be 

axis.  The sum of all offsets (elbows) must never 

laterally strengthened with a pair of telescopic 

exceed the number 120.  For example,  maximum 

roof braces.

allowed offsets would include: two offsets of 30-
degree  (4 elbows x 30 degrees =120) or an offset 

5.6   Chimney top:

 Install a chimney round top at 

of 30 degrees plus another one of 15 degrees (2 

the end of the chimney.

elbows x 30 d 2 elbows x 15 degrees = 
90).

4.3  Radiation shield/firestop:

 Install a radiation 

shield/firestop every time the chimney passes 

6.1   Stove pipe:

 Always install the pipes with the 

through a combustible floor or ceiling.

male end up so that any condensation water can 
drip and stay inside the pipe. 

4.4  Chimney weight:

  The weight of the 

chimney must be supported at regular intervals 
according to the manufacturer's instructions. 

The 

weight of the chimney must never be 
supported by the fireplace.

 In addition, offset 

supports must be installed above and as close as 
possible to each offset (elbow) in the chimney.   

5.  Factory-built chimney installation

6.  Stone pipe installation

Page 6

10 feet  (3 m) Radius

2 f

ee

t m

in

 (6

10

 m

m

) m

in

.

3 f

ee

t  (

1 m

) m

in

.

Warning: Lateral roof braces need to
be installed when the unsupported 
chimney height above the roof 
is more than 6 feet  (2 m).

Chimney minimum height above
the roof

DRAWING  3

REV.  2014-11

Summary of Contents for CFS SERIES

Page 1: ...BAR Les foyers DON BAR Fireplaces inc Shop and Showroom 741 St Vallier Ouest Quebec Quebec G1N 1E2 Phone 418 686 9114 Fax 418 686 9117 Website www don bar com Email don bar don bar com CFS SERIES WOO...

Page 2: ...3 Page 11 Page 18 Page 19 Page 20 PART 5 Warranty Page 1 FIREPLACES This document in its entirety is the intellectual property of Les Foyers Don Bar inc Any unauthorized use will expose its author or...

Page 3: ...e flap installation 3 Before beginning the 9 2 Humidifier tray installation 9 3 Removable ash shelf 3 1 Choosing the best location 3 1 1 Chimney 3 1 2 Chimney minimum height 3 1 3 Minimum clearances f...

Page 4: ...INSTALL IN A MOBILE HOME DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE ALWAYS PROVIDE A SOURCE OF FRESH AIR IN THE ROOM AN EXTERIOR FRESH AIR SOURCE MAY BE REQUIRED DO NOT ALTER...

Page 5: ...easures 2 4 Professional installation For your security enlist the services of a professional fireplace fitter for the installation 2 5 Before your first fire Before lighting your first fire read the...

Page 6: ...Do not connect this fireplace to a chimney that is connected to another heating device 3 1 2 Chimney minimum height 15 feet 4600 mm for proper operation This length is measured from the floor where t...

Page 7: ...st never laterally strengthened with a pair of telescopic exceed the number 120 For example maximum roof braces allowed offsets would include two offsets of 30 degree 4 elbows x 30 degrees 120 or an o...

Page 8: ...of combustible plastics The stove pipe must be a double wall stove pipe approved by ULC UL See pages 9 and 10 for authorized diameters and minimum clearances to combustible walls The clearances vary d...

Page 9: ...bers Drawing 6 The joints of the floor protection shall be perfectly fitted or filled with grout The floor protection must extend at least 18 460 mm in front of the fireplace door and 8 200 mm on each...

Page 10: ...7 8 15 31 1 2 48 1 4 24 16 22 3 4 6 7 8 22 3 4 31 1 2 48 1 4 24 16 22 3 4 6 7 8 19 14 692 1226 502 502 527 175 490 200 150 mm 27 1 4 48 1 4 19 3 4 13 20 3 4 6 7 8 26 27 1 4 48 1 4 19 3 4 13 20 3 4 6 7...

Page 11: ...200 150 mm 36 900 mm Ceiling front wall or combustible material Outlet 8 reducible to 6 Outlet 8 reducible to 6 Outlet 8 reducible to 6 12 305 mm 12 305 mm 12 305 mm Stove pipe minimum clearances 381...

Page 12: ...uels 3 3 Recommended wood species 9 1 Firescreen 3 4 Green wood 11 Anti smoke flap 9 1 Anti smoke flap installation 4 The fire 4 1 Opening the high efficiency HE smoke damper 13 Humidity and condensat...

Page 13: ...hot and blazing fire is wanted then open the air intake fully 1 3 Smoke outlet control This sliding valve is a part the of the high efficiency HE deflector system Drawing 22 It is located in the midd...

Page 14: ...e inadequate chimney height exterior structures harmful to the chimney draft or capable of causing smoke returns an indoor moisture level that is too high and causes ice build up in the flue and reduc...

Page 15: ...moke rain as long as necessary to allow it to dry Dry damper You will also be able to close gradually wood is easy to identify it is cracked at the ends the air intake control to increase the heating...

Page 16: ...toring before installation To fireplace safely always keep a poker on hand prevent rusting always store the fireplace and its Heat resistant gloves are also recommended and components in a dry space c...

Page 17: ...d directly from Don Bar Fireplaces Note the glass panes are not warrantied against breaking Warning Never replace a broken door glass with an ordinary or tempered glass it will shatter and may cause s...

Page 18: ...even infiltrate the chimney insulation To avoid these problems it is necessary to maintain a 30 35 humidity level inside the house 10 Firescreen installation 11 Anti smoke flap 12 Humidity and conden...

Page 19: ...per Deflector without the sliding damper Rod and plate assembly for the sliding damper Chimney adaptor Standard Parts Sliding plate for air intake control Hearth plate Anti smoke flap Insert door incl...

Page 20: ...on t reuse your fireplace firewood until a professional has inspected it A chimney fire Don t let creosote built up in the chimney can overheat the chimney components wrap it Don t burn coniferous con...

Page 21: ...arrantydoesnotcover time this is regarded as normal repair or the replacement of any part maintenance However all the 10 1 Brokenglass coveredbythewarranty original parts shipped with the 10 2 Damages...

Reviews: