ALARM CODES
The
Evolution EV AC
boiler has an electronic circuit that performs continuous self-testing to detect
any operating failures in the boiler. When the electronic control detects malfunctioning, this is
indicated by an alarm code flashing on the display. The following list describes the alarm codes that
may appear:
CODE
ALARM
DESCRIPTION
Pressure
The pressure in the installation has dropped to below 0.5 bar. The boiler will
cut out. To unblock it, fill the installation at a pressure of 1 - 1.5 bar. This alarm
may be set off due to the water having been drained from the boiler or leakage
in the installation.
If this alarm occurs repeatedly, you should contact the nearest official technical
assistance service.
Temperature
The boiler has exceeded the safety temperature of 110 ºC. The boiler will cut
out. To unblock it, press the safety thermostat button when the temperature
has dropped.
If this alarm occurs repeatedly, you should contact the nearest official technical
assistance service.
Burner
The burner has cut out. To unblock it, press the illuminated button on the
burner
(1)
.
If this alarm occurs repeatedly, you should contact the nearest official technical
assistance service.
Boiler sensor
The boiler sensor is damaged or disconnected. Contact your nearest official
technical assistance service to have it replaced.
DHW sensor.
The DHW sensor is damaged or disconnected. Contact your nearest official
technical assistance service to have it replaced.
SRS2/EV flow sensor.
The underfloor heating sensor is damaged or disconnected. Contact your
nearest official technical assistance service to have it replaced.
Pressure sensor
The pressure sensor
(9)
is damaged or disconnected. Contact your nearest
official technical assistance service to have it replaced.
Solar collector sensor
The solar collector sensor is damaged or disconnected. Contact your nearest
official technical assistance service to have it replaced.
Lower solar hot water
tank sensor
The lower solar hot water tank sensor is damaged or disconnected. Contact
your nearest official technical assistance service to have it replaced.
Upper solar hot water
tank sensor
The upper solar hot water tank sensor is damaged or disconnected. Contact
your nearest official technical assistance service to have it replaced.
Wrong switch
position alarm
The position of the switches does not correspond to the actual boiler model.
Card connection
alarm
Communication failure between the underfloor heating electronic card and
the boiler control board.
Overpressure
This indicates that the water pressure in the boiler is over 2.5 bar, warning that
the installation is in overpressure status. Boiler functioning will NOT cut out. To
restore normal boiler functioning, drain the boiler until it reaches a pressure of
1 – 1.5 bar.
If this warning occurs repeatedly, you should contact the nearest official
technical assistance service.