Evolution Solar HDX
10
3.8
Removal of combustion products
The combustion product exhaustion ducts must be installed by qualified personnel and must
comply with current legislation and standards.
The Evolution Solar HDX boiler is a sealed oil-fired boiler, and the combustion products are
therefore removed through an outlet pipe, with a separate air intake from outside. We recommend
that the position of the outside exhaustion duct is as shown in the figures and in the table below:
Exhaustion duct position
Minimum distance
(mm)
A under a cornice
300
B between two horizontal ducts
1000
C from an adjacent window
400
D between two vertical ducts
1500
E from an adjacent ventilation grille
600
F under a balcony (*)
300
G under a window
600
H under a ventilation grille
600
I from a recess in the building
300
J from a corner of the building
300
K from the ground
2500
L from a vertical or horizontal duct or outlet (**)
300
M from a frontal surface at a distance of 3 metres from the fume outlet
2000
N as above, but with an opening
3000
(*) Providing the width of the balcony is not over 2000 mm.
(**) If the pipe is made of materials sensitive to the action of the flue gases, this distance should be over 500 mm.
Note: Spanish law also stipulates that the end of the exhaustion duct must be at a distance of at least 400 mm from any air intake
opening, and from the wall.
IMPORTANT: All accessories used for combustion product removal and air intake are to be
those supplied by DOMUSA TEKNIK.