3.9 Jumper Settings

D-DMEV100

JUMPERS

INSTALLATION

AIRFLOW

1

2

3

ü

Through Wall

6 l/s

ü

Through Wall

8 l/s

ü

ü

Through Wall

13 l/s

ü

ü

In Room

6 l/s

ü

ü

In Room

8 l/s

ü

ü

ü

In Room

13 l/s

D-DMEV150

JUMPERS

INSTALLATION

AIRFLOW

1

2

3

Through Wall

6 l/s

ü

Through Wall

8 l/s

ü

Through Wall

13 l/s

ü

ü

Through Wall

15 l/s

ü

Through Wall

17 l/s

ü

ü

Through Wall

21 l/s

ü

ü

Through Wall

25 l/s

ü

ü

ü

Through Wall

29 l/s

3.10 Humidity Sensor & Timer Settings

The fan is equipped with a humidity sensor, whose threshold is 
adjustable from 50% to 95% relative Humidity via dedicated trimmer, 
and with a timer which is adjustable from 0 to approx. 30 minutes via 
dedicated trimmer (Figure 25).

The fan runs continuously at selected trickle speed (set by the jumper 
switch combination (Section 3.9), increases its speed in case the 
percentage of relative Humidity exceeds the settable threshold, and 
can anyway be boosted with a dedicated ON/OFF switch (or pIr, CO2…
sensor) or with a light switch (Figure 24). Trickle speed can be set to off 
(Section 3.9).

To deactivate the humidistat function, turn the trimmer HY completely 
clockwise.

Automatic humidistat operation: when the percentage of relative 
Humidity exceeds the settable threshold, fan speed automatically 
increases to “comfort boost” speed, (intermediate between the selected 
trickle speed and the boost speed). When the percentage of relative 
Humidity goes below the threshold, the fan continues to function at 
“comfort boost” speed for a factory set period of time then returns to 
selected trickle speed.

Operation with external switch: (Figure 24). When the external switch is 
turned on, the fan is boosted (max speed). After the external switch is 
turned off, the fan continues to run at boost speed for a settable period 
of time, then it returns to selected trickle speed (or to “comfort boost” 
speed in case automatic humidistat operation is on). The front cover LeD 
indicates when the external switch is on. 

The over-run timer function is activated only if the external switch has 
been on for at least 60 seconds.

+

-

HY

TIMER

+

-

JUMPERS

25 

3.11 Installation Completion

26 

CLICK

27 

28 

29 

671982  

|  

SepTemBer 2021

pAGe 6

Summary of Contents for D-DMEV

Page 1: ...etc If any abnormalities in operation are detected disconnect the device from the mains supply and contact a qualified technician immediately Use original spare parts only for repairs The electrical system to which the device is connected must comply with regulations Before connecting the product to the power supply or the power outlet ensure that The data plate voltage and frequency corresponds t...

Page 2: ...he appropriate window kit which is not included Attention do not mount the product on the window without this kit 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains important information on the safe and appropriate assembly transport commiss...

Page 3: ...cy aerodynamic fan with winglet blades to optimise quietness and efficiency Single phase EC Brushless motor with integral thermal protection Motor mounted on high quality ball bearings The fan is double insulated no earth connection is required Trickle speed selectable during installation Option to boost from trickle or from off through LS connection Installation type selection available through w...

Page 4: ...iew Model D DMEV100 D DMEV150 A 164 218 B 70 97 C 46 52 D 116 149 ØE 99 148 Weight 0 6 1 2 Dimensions 7 3 2 Installation Preparation 8 9 10 11 D DMEV100 ø99mm D DMEV150 ø149mm Ø 12 13 3 3 Surface Cable Installation 4xø5mm 8A 14 9A 15 671982 September 2021 PAGE 4 ...

Page 5: ...1 5 mm2 3 x 0 5 1 5 mm2 HT 3 x 0 5 1 5 mm2 4 x 0 5 1 5 mm2 3 6 Wiring Diagram Wiring 24 3 7 Installation Type Setting Installation type can be selected using JUMPER 1 between the following options through wall or ducted Section 3 9 3 8 Trickle Speed Setting Trickle speed can be selected using JUMPER Section 3 9 671982 September 2021 PAGE 5 ...

Page 6: ...light switch Figure 24 Trickle speed can be set to off Section 3 9 To deactivate the humidistat function turn the trimmer HY completely clockwise Automatic humidistat operation when the percentage of Relative Humidity exceeds the settable threshold fan speed automatically increases to comfort boost speed intermediate between the selected trickle speed and the boost speed When the percentage of Rel...

Page 7: ...components can be segregated into mixed plastic and widely recycled Cardboard packaging wood and other paper components can be largely recycled or fully processed in energy from waste centres Filter Disposal Cardboard framed filters should be fully processed in energy from waste centres contact your local civic amenity site household waste recycling centre regarding metal wire framed filters Remai...

Page 8: ...sions of equipment and the right is reserved to make such changes without prior notice 671982 September 2021 PAGE 8 Domus Ventilation Block C Van Court Caerphilly CF83 3ED United Kingdom Email vent info domusventilation co uk Tel 03443 715 523 www domusventilation co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimensions of ...

Reviews: