background image

Replacement of evaporator door gasket on RM360,
RM460, RM660

1. Remove the door as previously described.

2. Unscrew the hinge plates (A fig. 13).

3. Put shutter on a flat surface with the sealing

gasket up.

4. Pry the shutter front away from the inner

pan by means of a screwdriver.

CAUTION: It is of great importance that the

screw driwer is applied in front of one of

the plastic tongues (B fig. 13) which hold
the inner panel and the shutter front to-
gether.

5. Replace the sealing gasket round the in-

ner panel and snap the inner panel with

sealing gasket into the shutter front

until the tongues snap in position.

6. Mount the shutter as described above.

Fig.13

THE ABSORPTION COOLING UNIT

Sealed system construction

The sealed system of the absorption refrigerator If an excessive vaporizing of the ammonia within the

is constructed of welded steel piping which con-

boiler occurs due to the reasons above, the liquid

tains the refrigerant charge. The charge consists mixture in the boiler becomes very w e a k  and the pump
of ammonia, hydrogen and water. There are no mo-

will cease to operate, which means that the circula-

ving parts associated with the absorption system. tion of liquid stops with the result that the eva-

porator inside the cabinet ceases to produce coo-

ling.

When servicing an absorption system refrigerator, Such a blockage of the unit in the liquid circuit
do not puncture or break the piping. Should a ist most usually made evident by signs of overhea-
break occur and ammonia contact the skin, wash the ting on the vapour pipe leading from the boiler to

affected area immediately with clear water. Do not the condenser, the paint on this pipe being bliste-
attempt to open the valve on the absorber vessel. red and the metal becoming discouloured.
The valve is covered with a plastic can and should
never be removed. To remedy this fault it is recommended to remove the

OPERATION ANALYSIS FOR COOLING UNIT

It is obviously important that all external fac-
tors affecting the unit should be checked properly

before a unit is condemned as faulty and that empha-

sis has been placed upon the necessity for correct
installation, upright refrigerator, correct heat in-

put,

baffle position, etc.

Check the size and the

wattage of the electric heater and make sure that

the heater element is inserted to its full length
in its pocket. If the electric heater is only part-
ly inserted, the heat distribution will be incorrect,
causing an excessive vaporizing of the ammonia within
the boiler when operating on electricity. The same
symptom can show up with too much or too little

unit or refrigerator complete whenever possible and
to allow sufficient time to- cool down the unit. Turn

the unit or refrigerator upside down several times,
so that the liquid in the absorber vessel can be

mixed with the liquid in the boiler. This procedure
will restore the liquid balance to the unit.

The temperatures on various parts of a unit vary
continuously when it is operating on thermostatic

control and it is impossible to base a judgment on
the symptoms given unless the refrigerator has been

operating continuously on fully correct heat input
for at least 5 hours,

and preferably 12 hours, prior

to examination. In many cases this can be arranged

by a telephone call to the customer, asking him to
switch the thermostat to "MAX" on the day before the

heat input either on electric or on gas operation inspection call. If after 12 hours' operation on
and also if the refrigerator had been operating in "MAX"  the performance is satisfactory, the unit is
an off-level position or with inadequate ventila-

not at fault unless the complaint is one of varying

tion. or intermittent performance. In this connection

Summary of Contents for RM360

Page 1: ...P 7895 SW Hunziker Rd Portland OR 97223 Phone 503 620 9510 DOMETIC SALES CORP 2920 Avenue E East Alington TX 76011 P h o n e 817 277 72 1 DOMETIC SALES CORP East Oak Ridge Dr Rt 9 Box I7 A Hagerstown...

Page 2: ...e 10 The absorption cooling unit page 10 Operation analysis for cooling unit page 10 Cooling unit replacement RM360 460 660 page 11 Cooling unit replacement RM760 page 12 The gas electric equipment pa...

Page 3: ...r wire length in feet 3 Standard CSA Z240 6 2 C22 2 No 148 electrical requirements for recreational vehicles AWG Ventilation The installation shall be made in such a manner as to separate the combusti...

Page 4: ...osure as shown in Fig 2 Be careful not to damage the sealing strip applied to the floor of the enclosure when the refrigerator must be blocked The heat produced at the rear of the refrigerator will ot...

Page 5: ...21 9 16 22 3 4 32 5 16 6 21 13 16 6 23 3 4 1 1 4 RM660 40 13 16 6 23 24 11 16 6 40 21 9 16 22 3 4 40 3 16 6 21 13 16 6 23 3 4 1 1 4 RM760 52 23 24 11 16 51 3 16 21 9 16 22 3 4 51 3 8 21 13 16 6 23 3 4...

Page 6: ...lame Blow Out If trouble is encountered with the flame blowing out under specially windy conditions try to avoid the wind blowing against the wall where vent outlets are located If the trouble persist...

Page 7: ...d regularly by turning off the refrigerator Empty the re frigerator leaving the drip tray under the finned evaporator and the cabinet and freezer doors open If desired defrosting may be speeded up by...

Page 8: ...edge of the panel is fitted into the bottom groove 5 Between the upper edge of the panel and the door frame there is now a gap which should be covered by the decoration strip Put the strip across the...

Page 9: ...e middle hinge and the travel latch should change position Replacement of evaporator door on RM360 RM460 RM660 Fig 11 and 12 1 2 3 4 5 Pry the spring housings B away from the li ning so that it snaps...

Page 10: ...iscouloured The valve is covered with a plastic can and should never be removed To remedy this fault it is recommended to remove the OPERATION ANALYSIS FOR COOLING UNIT It is obviously important that...

Page 11: ...ual rise in tem on the evaporator inside the cabinet a smell of perature towards the boiler end ammonia may bee noticeable COOLING UNIT REPLACEMENT RM360 RM460 RM660 Remove the refrigerator from its r...

Page 12: ...rse above procedure CAUTION 1 Be sure to apply sealing permagum 8 on the unit mounting plate Fig 16 2 Be sure to apply proper amount of Thermal Mas tic on the evaporator coil 9 3 When fitting the evap...

Page 13: ...ame failure safety device 6 Bypass screw 7 Gas Electric thermostat 8 Pressure test gage connection 9 Capillary tube for thermostat 10 Shut off value 11 Piezo igniter 12 Firing tip 13 Flue baffle Fig 2...

Page 14: ...ssembly of gas electric equipment 1 2 3 4 5 6 7 Press the plastic latch leftwards in Fig 22 Pull the relay out if any Snap off the fuse holder Press the spring Pull the shut off valve out Press the ga...

Page 15: ...RATORS S Y M P T O M C A U S E P z Note It will be noted in this tabulation that T1z 48 u 8 8 2 2 several causes can be responsible for the one c rl 8 c z S effect The real cause or causes should be d...

Page 16: ...ss of elimination investigating each possible cause starting at the top of the tabulation and proceeding to the bottom Not adequate ventilation Refrigerating unit not level Heater faulty wrong voltage...

Page 17: ...LTS DC 12VOLTS DC N L 115 VOLTS AC THERMOS TAT 0 JUNCTION BLOCK 0 TERMINAL BLOCK GREEN GREEN YELLOW Fig 25 Wiring Diagram for Product No 926 63 01 RM760 115VOLTS AC Fig 26 Wiring Diagram for Product N...

Page 18: ...n g Diagram f o r Product No 926 69 01 926 70 01 926 71 01 RM360 RM460 RM660 I 115 VOLTS AC m 6 BLACK j GREEN GREEN YEL LOW N_ l Lr 7 I 8 I zzz SWITCH I THERMOSTAT 0 JUNCTION BLOCK HEATER e TERMINAL B...

Page 19: ......

Reviews: