background image

25

EN

Elite Control 

Troubleshooting

8  Troubleshooting

The following table describes some common 

occurrences that are not a result of defective 

workmanship or materials.

Problem

Possible Causes

Recommended Solution

The system does 

not power up.

The air conditioning unit circuit breaker is off. 

Turn on the air conditioning unit circuit breaker at the ship’s panel.

The display is not turned on. 

Turn on the display.

The terminal strip is miswired. 

Check the wiring diagram and correct if necessary.

The input-line voltage is insufficient. 7

•  Check the power source (shore/generator) for proper voltage. 
•  Check the wiring and terminals for proper sizes and connections. 
•  Verify with a voltmeter that the power at the unit is the same as the 

power source.

An electrical component has failed. 

A technician should inspect the display, cable, and circuit board. Look for 

a red light on the circuit board. 

The system runs 

continuously.

The unit is not able to reach the set point.

Close all the port holes and hatches. Adjust the set point so it is not too 

low for cooling or too high for heating.

The seawater temperature is too high for 

cooling or too low for heating. 

Seawater temperature will directly affect the air conditioning unit’s 

efficiency. This air conditioning unit can effectively cool your boat in water 

temperatures up to 90 °F (32 °C) and heat (if reverse-cycle option is 

installed) in water as low as 40 °F (4 °C).

The optional inside air temperature sensor is 

not located properly. 

•  Verify the display location with the criteria found in the installation 

section of this manual.

•  Install an optional inside air temperature sensor if necessary. If an 

optional inside air temperature sensor is already installed in the air 

stream, ensure it does not touch anything warm (like the condenser 

coil).

The de-icing feature is not enabled.

Enable de-icing in the parameters. If ice still forms immediately, revisit the 

above possible causes.

 

I

Ice on a fan coil can be removed quickly by running the unit in HEAT 

mode.

There is a lack of 

airflow.

The airflow is blocked or restricted.

•  Remove any obstructions in the return-air stream.
•  Clean the return-air filter and grille. 
•  Check for crushed or restricted ducting. Ducting must be as straight, 

smooth, and taut as possible.

The fan speed is set to manual low.

•  If the fan speed is set to manual low, raise the speed to a higher setting 

or set to automatic mode. 

•  Or, increase the minimum low speed in the program parameters.

The fan coil may be iced.

Refer to “The fan coil is iced.” in this table.

The fan coil is iced. The humidity level is set too high.

Close the hatches and doors.

The supply air is short-cycling.

•  Redirect the supply air so that is not blowing in or near the return-air 

stream. 

•  Seal any air leaks on the duct.

The airflow is blocked or restricted

Refer to “There is a lack of airflow.”in this table.

The fan runs too slow.

Set the fan speed to automatic mode or increase the manual fan speed. 

Or, increase the minimum low speed in the program parameters.

The system runs continuously.

Close hatches and doors, raise set point, turn on de-icing.

Summary of Contents for Elite Control Series

Page 1: ...E CONTROL UNITS L 5507 Form No 341204 20200325 2020 Dometic Corporation WARNING Cancer and Reproductive Harm www P65Warnings ca gov Elite Control Series EN Elite Control Installation and Operating Man...

Page 2: ...Dealer Locations Visit www dometic com Read these instructions carefully These instructions MUST stay with this product 1 Explanation of Symbols and Safety Instructions This manual has safety informat...

Page 3: ...ems and chilled water systems CW The 5 button display panel has 33 programmable parameters automatic and manual fan speeds standard and optional sensor inputs and fits both Vimar Idea and Eikon switch...

Page 4: ...Function Temperature LED Display Displays the inside set point outside and water temperatures Fan Speed Indicates the fan speed as high medium or low AUTO Automatic Fan Mode Located below the fan spe...

Page 5: ...Sensor optional 1 4 4 Operational Specifications Set Point Operating Range 65 F to 85 F 18 C to 29 C Ambient Temperature Operating Range Displayed 5 F to 150 F 15 C to 66 C Sensor Accuracy 2 F 77 F 1...

Page 6: ...lection Jumper JP2 Low Pressure Switch Jumper Run Capacitor Low Pressure Switch High Pressure Switch Optional DC Blower Comp L1 Pump L1 Pump L2 0 10 VDC GND Fan L1 Comp L2 Compressor Display Jacks for...

Page 7: ...Water Inlet Temperature Sensor Optional Outside Air Temperature Sensor JP5 Temperature Sensor Selection Jumper Ground Fan Water Valve Electric Heat Strip Fan Run Capacitor L2 L2 L2 AC L2 L1 L1 L1 L1 O...

Page 8: ...optional inside air temperature sensor is required if installing the display panel in a cabinet enclosed space or any area where the accurate sensing of the room temperature would be impaired This se...

Page 9: ...play OFF Wait a minimum of five minutes 3 Turn the air conditioner circuit breaker ON I IIf the seawater pump is on a separate circuit breaker be sure to turn it ON 4 Turn the display ON 5 Press the F...

Page 10: ...ed Water System Operation CW Systems Only In CW systems the water valve does not open unless the water temperature is adequate to heat or cool the cabin The adequate heating or cooling water temperatu...

Page 11: ...re in 10 minute intervals during a cooling cycle Depending on the parameter value and the change in room temperature during these monitoring intervals the control performs various actions to prevent i...

Page 12: ...lected or when the unit is in an AUTOMATIC mode heating cycle Only the heating system operates If the ambient temperature rises above the set point the system will not automatically switch to the COOL...

Page 13: ...o advance from automatic to manual fan operation Press and release the Fan button to cycle through the manual fan speeds from low to high Press and release the Fan button to return to automatic fan op...

Page 14: ...ait 30 seconds Clear the fault history log press simultaneously the POWER and DOWN buttons while viewing the fault history log Display the compressor run time hour meter press the DOWN button This met...

Page 15: ...resumes operating as last programmed The control has factory default values stored in permanent memory memorized factory default settings that can be recalled if you have any programming difficulties...

Page 16: ...tage the units at least five seconds apart P 4 Inside Air Temperature Sensor Calibration x x Ambient Temperature Ambient Temperature 10 F 6 C Calibrate the sensor to display the correct room temperatu...

Page 17: ...ssor shutdown periods combined with a one speed increase in fan speed and by periodic HEAT mode cycles with the fan turned off P 8 Optional Pump Sentry x OFF OFF ON Select 100 F to 150 F 38 C and 66 C...

Page 18: ...ng an optional electric heater that exceeds this load it is necessary to install an additional contactor that is rated to handle the full load of the electric heater P 14 Fan Motor Selection x x SC SC...

Page 19: ...0 CAN Bus Unit ID x x dIS Unit ID 59 after enabling and power cycling 0 255 Enables all units with a CAN Bus adapter installed to be networked together and communicate with each other or the ship s CA...

Page 20: ...x x OFF OFF 95 F to 140 F in 5 increments 35 C to 60 C in 2 8 increments Set the maximum supply air discharge temperature allowed Enabling this parameter has no effect unless parameter P 13 is enabled...

Page 21: ...heater is not installed the ON time of the bypass valve will extend by operating to 1 F lower than the set point This cycle continues until the cabin s relative humidity is less than the humidity set...

Page 22: ...onds prior to the manual or automatic exit from the programming mode The control enters OFF mode after exit 7 4 5 IdentifyingProgrammingFaultCodes To protect the unit certain fault conditions trigger...

Page 23: ...ludes the failsafe actions of the previous level and detects all other faults but they are not displayed The system shuts down for two minutes or until the fault is cleared whichever is longer The sys...

Page 24: ...Set Point Temperature Differential P 24 Dehumidification Mode Minimum Temperature P 25 Auto Fan Speed Temperature Differential P 26 Supply Air High Temperature Limit P 27 Seawater Low Limit Adjustmen...

Page 25: ...erature sensor is not located properly Verify the display location with the criteria found in the installation section of this manual Install an optional inside air temperature sensor if necessary If...

Page 26: ...if the reverse cycle option is available water temperatures must be 40 F 4 C or higher There is a loss of refrigerant gas Check the air conditioning unit for a refrigerant oil leak Call for service Fo...

Page 27: ...If the overload on the compressor is internal wait several hours for it to cool before testing A low pressure fault is present The unit does not have a low pressure switch but the JP2 jumper on the c...

Page 28: ...r temperature The system may cycle on high pressure if the seawater temperature is above 55 F 13 C The high pressure switch is defective or a wire is loose Contact a servicing dealer to test the high...

Page 29: ...uilt in temperature sensor replace the display or add an optional inside air temperature sensor Install a different display cable Ensure that the damaged jack socket in the display head or on the circ...

Page 30: ...cling waste bins whenever possible Consult a local recycling center or specialist dealer for details about how to dispose of the product in accordance with all applicable national and local regulation...

Page 31: ...31 EN Elite Control...

Page 32: ...om dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices A complete list of Dometic companies which comprise the Dometic Group can be found in the public fili...

Reviews: