background image

17

EN

Elite Control 

Operation

Parameter

Name

DX

CW

Factory Default

Parameter Range

P-7

De-icing Cycle

x

OFF

OFF

1 = ON with 5 °F (3 °C) Display Sensor Differential

2 = ON with 7 °F (4 °C) Display Sensor Differential

Select the parameter setting for the de-icing feature depending on whether you are using the 

display built-in temperature sensor or the optional inside air temperature sensor. 
•  If using an optional inside air temperature sensor., set this parameter to 1 to turn the de-icing feature 

ON, or to OFF to disable. 

•  If using the display built-in temperature sensor, choose one of the two selectable behavior modes: 

 

– 1: assumes the display built-in temperature sensor may be reading the room temperature as 

much as 5 °F (3 °C) greater than the actual evaporator temperature (standard). 

 

– 2: for more extreme installations - assumes the display built-in temperature sensor may be 

reading the room temperature as much as 7 °F (4 °C) greater than the actual evaporator 

temperature. 

•  The setting of 2 should only be used if a setting of 1 does not prevent evaporator ice from forming. 

 

I

The following applies to software revision #A13 and older. 

 

De-icing is accomplished by switching the reversing valve to HEAT mode while the system 

is cooling. The valve remains energized for the programmed cycle time. The cycle is 

programmable to OFF or to a period of one, two,or three minutes. 

 

I

The following applies to software revision #A15 and newer. 

 

De-icing is accomplished by closely monitoring the room air temperature in 10-minute intervals 

during a cooling cycle. Depending on the parameter value and the change in room temperature 

during these monitoring intervals, the control performs various actions to prevent ice from 

forming or to melt ice that has already formed. These actions include short compressor shutdown 

periods combined with a one-speed increase in fan speed and by periodic HEAT mode cycles 

with the fan turned off.

P-8

Optional Pump Sentry

x

OFF

OFF

ON = Select 100 °F to 150 °F 

(38 °C and 66 °C)

Set this parameter setting when the optional pump sentry water sensor is installed to monitor the 

condenser coil temperature and to shut down the pump and compressor when the coil temperature 

rises above the programmed value. This sensor is plugged into the H2O OUT sensor jack on the 

control board. 

Program a temperature between 100 °F and 150 °F (38 °C and 66 °C), depending on seawater 

temperature and the system type. Refer to the sensor installation instructions for detail. The setting 

increments are in °F even when the control is set to display °C. 

P-9

Display Brightness 

Control

x

x

4 (Dimmest)–18 (Brightest)

Set this parameter setting between 4 and 18. 

A dark cabin requires a setting of 4. A very bright cabin requires a setting of 12–18.

P-10

Fahrenheit or Celsius 

Selection

x

x

F

F = Fahrenheit Displayed

C = Celsius Displayed

A =  Automatic Selection Based on Voltage 

50 Hz = Celsius 

60 Hz = Fahrenheit

Select °C for Celsius. (Celsius readings are displayed in tenths, for example 22.2°). The default setting is °F. 

P-11

Cycle Pump with 

Compressor

x

CYC

CYC = Cycle with Compressor

Con = Continuous Pump

Select cycled or continuous pump operation:
•  CYC: increases the pump life and conserves electricity by cycling ON and OFF with the compressor. 
•  Con: programs the pump to operate continuously whenever the system is on.

P-12

Reverse Automatic Fan 

Speeds During Heating

x

x

rEF

nOr = Normal Fan Operation

rEF = Reversed Fan in HEAT Mode

Reverse the automatic fan speeds during HEAT mode to improve heat output in cooler climates. 
•  When set to rEF, the fan speeds up as the set point is approached. The fan switches to low speed 

when the set point is satisfied and the water valve or compressor cycles OFF.

•  When set to nOr, the fan operates the same as during cooling, which represents normal fan operation. 

Summary of Contents for Elite Control Series

Page 1: ...E CONTROL UNITS L 5507 Form No 341204 20200325 2020 Dometic Corporation WARNING Cancer and Reproductive Harm www P65Warnings ca gov Elite Control Series EN Elite Control Installation and Operating Man...

Page 2: ...Dealer Locations Visit www dometic com Read these instructions carefully These instructions MUST stay with this product 1 Explanation of Symbols and Safety Instructions This manual has safety informat...

Page 3: ...ems and chilled water systems CW The 5 button display panel has 33 programmable parameters automatic and manual fan speeds standard and optional sensor inputs and fits both Vimar Idea and Eikon switch...

Page 4: ...Function Temperature LED Display Displays the inside set point outside and water temperatures Fan Speed Indicates the fan speed as high medium or low AUTO Automatic Fan Mode Located below the fan spe...

Page 5: ...Sensor optional 1 4 4 Operational Specifications Set Point Operating Range 65 F to 85 F 18 C to 29 C Ambient Temperature Operating Range Displayed 5 F to 150 F 15 C to 66 C Sensor Accuracy 2 F 77 F 1...

Page 6: ...lection Jumper JP2 Low Pressure Switch Jumper Run Capacitor Low Pressure Switch High Pressure Switch Optional DC Blower Comp L1 Pump L1 Pump L2 0 10 VDC GND Fan L1 Comp L2 Compressor Display Jacks for...

Page 7: ...Water Inlet Temperature Sensor Optional Outside Air Temperature Sensor JP5 Temperature Sensor Selection Jumper Ground Fan Water Valve Electric Heat Strip Fan Run Capacitor L2 L2 L2 AC L2 L1 L1 L1 L1 O...

Page 8: ...optional inside air temperature sensor is required if installing the display panel in a cabinet enclosed space or any area where the accurate sensing of the room temperature would be impaired This se...

Page 9: ...play OFF Wait a minimum of five minutes 3 Turn the air conditioner circuit breaker ON I IIf the seawater pump is on a separate circuit breaker be sure to turn it ON 4 Turn the display ON 5 Press the F...

Page 10: ...ed Water System Operation CW Systems Only In CW systems the water valve does not open unless the water temperature is adequate to heat or cool the cabin The adequate heating or cooling water temperatu...

Page 11: ...re in 10 minute intervals during a cooling cycle Depending on the parameter value and the change in room temperature during these monitoring intervals the control performs various actions to prevent i...

Page 12: ...lected or when the unit is in an AUTOMATIC mode heating cycle Only the heating system operates If the ambient temperature rises above the set point the system will not automatically switch to the COOL...

Page 13: ...o advance from automatic to manual fan operation Press and release the Fan button to cycle through the manual fan speeds from low to high Press and release the Fan button to return to automatic fan op...

Page 14: ...ait 30 seconds Clear the fault history log press simultaneously the POWER and DOWN buttons while viewing the fault history log Display the compressor run time hour meter press the DOWN button This met...

Page 15: ...resumes operating as last programmed The control has factory default values stored in permanent memory memorized factory default settings that can be recalled if you have any programming difficulties...

Page 16: ...tage the units at least five seconds apart P 4 Inside Air Temperature Sensor Calibration x x Ambient Temperature Ambient Temperature 10 F 6 C Calibrate the sensor to display the correct room temperatu...

Page 17: ...ssor shutdown periods combined with a one speed increase in fan speed and by periodic HEAT mode cycles with the fan turned off P 8 Optional Pump Sentry x OFF OFF ON Select 100 F to 150 F 38 C and 66 C...

Page 18: ...ng an optional electric heater that exceeds this load it is necessary to install an additional contactor that is rated to handle the full load of the electric heater P 14 Fan Motor Selection x x SC SC...

Page 19: ...0 CAN Bus Unit ID x x dIS Unit ID 59 after enabling and power cycling 0 255 Enables all units with a CAN Bus adapter installed to be networked together and communicate with each other or the ship s CA...

Page 20: ...x x OFF OFF 95 F to 140 F in 5 increments 35 C to 60 C in 2 8 increments Set the maximum supply air discharge temperature allowed Enabling this parameter has no effect unless parameter P 13 is enabled...

Page 21: ...heater is not installed the ON time of the bypass valve will extend by operating to 1 F lower than the set point This cycle continues until the cabin s relative humidity is less than the humidity set...

Page 22: ...onds prior to the manual or automatic exit from the programming mode The control enters OFF mode after exit 7 4 5 IdentifyingProgrammingFaultCodes To protect the unit certain fault conditions trigger...

Page 23: ...ludes the failsafe actions of the previous level and detects all other faults but they are not displayed The system shuts down for two minutes or until the fault is cleared whichever is longer The sys...

Page 24: ...Set Point Temperature Differential P 24 Dehumidification Mode Minimum Temperature P 25 Auto Fan Speed Temperature Differential P 26 Supply Air High Temperature Limit P 27 Seawater Low Limit Adjustmen...

Page 25: ...erature sensor is not located properly Verify the display location with the criteria found in the installation section of this manual Install an optional inside air temperature sensor if necessary If...

Page 26: ...if the reverse cycle option is available water temperatures must be 40 F 4 C or higher There is a loss of refrigerant gas Check the air conditioning unit for a refrigerant oil leak Call for service Fo...

Page 27: ...If the overload on the compressor is internal wait several hours for it to cool before testing A low pressure fault is present The unit does not have a low pressure switch but the JP2 jumper on the c...

Page 28: ...r temperature The system may cycle on high pressure if the seawater temperature is above 55 F 13 C The high pressure switch is defective or a wire is loose Contact a servicing dealer to test the high...

Page 29: ...uilt in temperature sensor replace the display or add an optional inside air temperature sensor Install a different display cable Ensure that the damaged jack socket in the display head or on the circ...

Page 30: ...cling waste bins whenever possible Consult a local recycling center or specialist dealer for details about how to dispose of the product in accordance with all applicable national and local regulation...

Page 31: ...31 EN Elite Control...

Page 32: ...om dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices A complete list of Dometic companies which comprise the Dometic Group can be found in the public fili...

Reviews: