Installation
Dometic BR342
16
EN
➤
Tighten all four (4) mounting bolts EVENLY to 4.5 to 5.5 Nm.
NOTICE!
Tighten mounting bolts to correct torque specifications. Overtightening could damage unit’s base pan or
ceiling template. Not enough torque will allow an inadequate roof seal, and could cause a leak.
➤
Fix the return air sensor to the tie fix on the ceiling template so it is positioned in the return air stream.
➤
Feed the communication wire through the hole in the ceiling plate as shown below and connect the 2 ends.