Dometic 620615.321 Installation & Operating Instructions Manual Download Page 6

6

FRAME

14-1/4" (±1/8”)

OPENING

AC POWER
SUPPLY WIRE

DUCT

FRAME

DUCT

ROOF

INSULATION

DUCT

CEILING

DUCT

14-1/4" (±1/8”)

OPENING

INSULATION

SIDE VIEW

(TOWARD BACK OF RV)

TOP VIEW

(BACK OF RV)

LOW VOLTAGE WIRES:

12VDC
Furnace
Load Shed
Sensors

FRAME

CCC, CONTROL CABLE(S)
or 7-Wire Analog Cable

FIG. 7

4.

Air Distribution System Sizing & Design  (See Chart
On Page 15)

The Installer of this air conditioner system must design
the air distribution system for this particular application.
Several requirements for this system MUST be met for
the air conditioner to operate properly. These require-
ments are as follows:

a.

The duct material must meet or exceed any
agency or RVIA Standard that may be in exist-
ence at the time the RV is produced.

b.

All discharge air ducts must be properly insu-
lated to prevent condensation from forming on
their surfaces or adjacent surfaces during op-
eration  of the air conditioner. This insulation
must be R-7 minimum.

c.

Ducts and their joints must be sealed to prevent
condensation from forming on adjacent sur-
faces during operation of the air conditioner.

d.

Return air openings must have 40 square inches
minimum free area including the filter.

It is the responsibility of the installer to insure
the duct-work will not collapse or bend dur-
ing and after the installation. Dometic Corpo-
ration will not be liable for roof structural or
ceiling damage due to improperly insulated,
sealed or collapsed duct-work.

CAUTION

Duct size

Duct layout

Register size

Register location

Receiver location

These items must be determined in conjunction with the
Air Distribution System and Sizing and Design Require-
ments listed in the chart on page 15. Terminate the start
of the duct at the back edge of the 14-1/4" x  14-1/4" (±1/
8" opening)

Important: 

Alternate configurations and methods

may be used which still allow the air conditioner to
operate properly; however, these alternate configura-
tions and methods must be approved by the Dometic
Corporation in writing. The following instructions are
based upon the use of Dometic Return Air Kits
3105007.XXX, 3105935.XXX,  or 3308120.XXX Genesis
Air Filtration System. The  3107180.006 Bolt/Cover Kit
has the mounting bolts and cover for the AC junction
box for use with these kits.

D.

Wiring Requirements

1.

Route a copper 12 AWG, with ground, 115 VAC
supply line from the fuse or circuit breaker box to the
roof opening.

a.

This supply line must be located in the front

portion of the 14-1/4" x 14-1/4" (±1/8") opening.

b.

The power MUST be on a separate 20 Amp time

delay or HACR circuit breaker.

c.

Make sure that at least 15" of supply wire

extends into the roof opening. This ensures
easy connection at the junction box.

d.

Wiring must comply with all National, State and

Local Wiring Codes.

e.

Use a steel sleeve and a grommet or equivalent

methods to protect the wire where it passes into
the opening.

2. Route a dedicated 12 VDC supply line (18 -22 AWG)

from the RV's converter or battery to the roof open-
ing.

a. This supply line must be located in the front

portion of the 14-1/4" x 14-1/4" (±1/8") opening.

b. Make sure that at least 15" of supply wire

extends into the roof opening.

CAUTION

It is the responsibility of the installer of this
air conditioner system to ensure structural in-
tegrity of the RV roof. Never create a low spot
on the roof where water will collect. Water
standing around the air conditioner may leak
into the interior causing damage to the prod-
uct and the RV.

e.

Return air to the air conditioner must be filtered
to prevent dirt accumulation on air conditioner
cooling surface.

5.

Air Distribution System Installation
a.

Dometic Corporation recommends the basic
configuration shown on page 16, for installing
this air conditioner system. We have found by
testing, that this configuration works best in
most applications of this air conditioner sys-
tem. It is the responsibility of the Installer of this
system to review each RV floor plan and deter-
mine the following:

620615, 620625 & 620626 Installation & Operating Instructions

Summary of Contents for 620615.321

Page 1: ...s manual must be read and un derstood before installation adjust ment service ormaintenanceisper formed This unit must be installed by a qualified service technician Modification of this product can b...

Page 2: ...at gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening D Condensation...

Page 3: ...ating Rated Load Locked Rated Load Locked Speed Static R 22 Oz Wire Size Protection Weight Generator BTU HR Amps Rotor Amps Rotor Max Min Max Min User Pounds Size Cooling Amps Amps W C Supplied 1Unit...

Page 4: ...of vent is available or another location is desired the following is recom mended a For one unit installation The air conditioner should be mounted slightly forward of center front to back and centere...

Page 5: ...ditionerandmustbe finished in accordance with NFPA Standard 501C Section 2 7 2 Do Not Cut RoofStrucure OrRafters Good Rafters Supported By CrossBeams Good Location Between Roof Rafters 2 RoofVentRemov...

Page 6: ...nate configura tions and methods must be approved by the Dometic Corporation in writing The following instructions are based upon the use of Dometic Return Air Kits 3105007 XXX 3105935 XXX or 3308120...

Page 7: ...serve the following general rules in determiningthelocationandsubmitlocationto Dometicforapproval Locate the Receiver 54 above the floor NEVERexposeittodirectheatfromlamps sun or other heat producing...

Page 8: ...by slightly lift ing See FIG 12 b Remove return air cover and ceiling template from the 3105007 XXX or 3105935 XXX kit car ton FIG 12 Center Unit From Below Roof Gasket Flat Four Conductor Cable RJ 1...

Page 9: ...Below Roof Gasket FIG 14 DC Power Supply Receiver Leads Furnace Furnace Tstat Con nection From A C EVENLY tighten the bolts to a torque of 40 to 50 inch pounds This will compress the roof gasket to ap...

Page 10: ...tor in the junc tion box b Installing Foam Divider Locate the foam divider and insert it corner to corner in the 14 1 4 x 14 1 4 1 8 opening with the adhesive tape up Do not remove paper to expose adh...

Page 11: ...er duct installation refer to all Non Center Duct Installations Section 1on page 10 Important A duct adapter not supplied must be installed between the unit discharge and the customer installed cen te...

Page 12: ...the return air open ing above the center duct before ceiling tem plate c Install Ceiling Template Apply a piece of foam weather stripping not supplied to the upper side of ceiling tem plate to make a...

Page 13: ...assure they don t vibrate off d Push the wires into the box e Install the cover onto the junction box I Decorative Cover Installation Installing unit with 3105007 XXX or 3105935 XXX Return Air Cover...

Page 14: ...e red positive 12VDC supply wire See FIG 23 b Connect the black wire from the air conditioner and the black wire from the filter indicator light with the black negative 12VDC supply wire See FIG 23 No...

Page 15: ...uct System Only Depth 2 0 In Min 2 0 Max Width 8 0 In Min 8 0 In Max Total Duct Length 15 0 Ft Min 40 Ft Max Duct Length Short Run 1 3 Total Length Register Requirements Number Required Per Run 4 Min...

Page 16: ...er Required Roof Rafters Roof Rafters Note Duct Size is Inside Dimensions Note Duct Size Is Inside Dimensions Short Duct Run Minimum 1 3 Total Duct Length Short Duct Run Minimum 1 3 Total Duct Length...

Page 17: ...tery symbol will appear in the dis play window b When the low battery condition exists and the remote sends a signal to the receiver it may be possible for the control system to go to the default sett...

Page 18: ...played a High Speed continuous fan operation b Low Speed continuous fan operation 3 The receiver will beep when each change is com pleted The GREEN LED will light H Room Temperature Display 1 Press th...

Page 19: ...batteries are installed the clock will display 0 00 b Clock shows only military time c Push the clock button the clock display should blink I FEEL I FEEL d Press and hold the UP or DOWN but ton to set...

Page 20: ...NO TO 115 VAC 1O 60 Hz TO 115 VAC 1O 60 Hz HEAT ACCESSORY WHT BLK BLK ELEMENT LIMIT 3 1 SWITCH WHT BLK OL WHT FREEZE BLK BLK NOT AVAILABLE ON SOME ON SOME MODELS T5 T6 T9 T10 T7 T8 COUPLERS IN LINE I...

Reviews: