Dometic 620615.321 Installation & Operating Instructions Manual Download Page 5

5

 AIR CONDITIONER DIMENSIONS
(On Top Of Vehicle)

FIG. 4

1-1/4"

1-1/2"

1-3/4"

1-1/2"

17"

17"

20-7/8"

3"

2"

2"

18-1/2"

3"

Air Grill Perimeter

14-1/4 x 14-1/4 (±1/8")
Opening

Genesis

C. Roof Preparation

1.

Opening Requirments - Before preparing the ceiling
opening, the type of system options must be de-
cided upon. If a furnace is to be connected, wires
must be run from the furnace to the Dometic A/C.
Read all of the following instructions before begin-
ning the installation.
If a roof roof vent opening will not be used a 14-1/4"
x 14-1/4" (±1/8") opening must be cut through the
roof and ceiling of the RV. This opening must be
located between the roof reinforcing members.

There may be electrical wiring between the
roof and the ceiling. Disconnect 115 volt AC
power cord and the positive (+) 12 volt DC  ter-
minal at the supply battery. Failure to follow
this instruction may create a shock hazard
causing death or severe personal injury.

The 14-1/4" x 14-1/4" (±1/8") opening is part of the

return air system of the Air Conditioner and must be
finished in accordance with NFPA Standard 501C
Section 2.7.2.

Do Not Cut
Roof Strucure
Or Rafters

Good-Rafters
Supported By
Cross Beams

Good Location-
Between Roof
Rafters

2.

Roof Vent Removal

a.

Unscrew and remove the roof vent.

b.

Remove all caulking compound around open-
ing.

c.

Seal all screw holes and seams where the roof
gasket is located. Use a good grade of all
weather sealant.

d.

If the opening exceeds 14-3/8" x 14-3/8", it will
be necessary to install spacers.

e.

If the opening is less than 14-1/8" x 14-1/8", it
must be enlarged.

3.

New Opening-(Installation Other Than Vent Open-
ing)
a.

Mark a 14-1/4" x 14-1/4" (±1/8") square on the
roof and carefully cut the opening.

b.

Using the roof opening as a guide, cut the
matching hole in the ceiling.

d.

The opening created must be framed to provide
adequate support and prevent air from being
drawn from the roof cavity. Lumber 3/4" or more
in thickness must be used. Remember to pro-
vide an entrance hole for power supplies, fur-
nace wiring and a four-conductor control cable.

3/4" Min.

Leave Access For
Power Supply Wiring

Frame Opening So It
Won't Collapse When
Bolting  Down

15" min.

FIG. 5

FIG. 6

620615, 620625 & 620626 Installation & Operating Instructions

Summary of Contents for 620615.321

Page 1: ...s manual must be read and un derstood before installation adjust ment service ormaintenanceisper formed This unit must be installed by a qualified service technician Modification of this product can b...

Page 2: ...at gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening D Condensation...

Page 3: ...ating Rated Load Locked Rated Load Locked Speed Static R 22 Oz Wire Size Protection Weight Generator BTU HR Amps Rotor Amps Rotor Max Min Max Min User Pounds Size Cooling Amps Amps W C Supplied 1Unit...

Page 4: ...of vent is available or another location is desired the following is recom mended a For one unit installation The air conditioner should be mounted slightly forward of center front to back and centere...

Page 5: ...ditionerandmustbe finished in accordance with NFPA Standard 501C Section 2 7 2 Do Not Cut RoofStrucure OrRafters Good Rafters Supported By CrossBeams Good Location Between Roof Rafters 2 RoofVentRemov...

Page 6: ...nate configura tions and methods must be approved by the Dometic Corporation in writing The following instructions are based upon the use of Dometic Return Air Kits 3105007 XXX 3105935 XXX or 3308120...

Page 7: ...serve the following general rules in determiningthelocationandsubmitlocationto Dometicforapproval Locate the Receiver 54 above the floor NEVERexposeittodirectheatfromlamps sun or other heat producing...

Page 8: ...by slightly lift ing See FIG 12 b Remove return air cover and ceiling template from the 3105007 XXX or 3105935 XXX kit car ton FIG 12 Center Unit From Below Roof Gasket Flat Four Conductor Cable RJ 1...

Page 9: ...Below Roof Gasket FIG 14 DC Power Supply Receiver Leads Furnace Furnace Tstat Con nection From A C EVENLY tighten the bolts to a torque of 40 to 50 inch pounds This will compress the roof gasket to ap...

Page 10: ...tor in the junc tion box b Installing Foam Divider Locate the foam divider and insert it corner to corner in the 14 1 4 x 14 1 4 1 8 opening with the adhesive tape up Do not remove paper to expose adh...

Page 11: ...er duct installation refer to all Non Center Duct Installations Section 1on page 10 Important A duct adapter not supplied must be installed between the unit discharge and the customer installed cen te...

Page 12: ...the return air open ing above the center duct before ceiling tem plate c Install Ceiling Template Apply a piece of foam weather stripping not supplied to the upper side of ceiling tem plate to make a...

Page 13: ...assure they don t vibrate off d Push the wires into the box e Install the cover onto the junction box I Decorative Cover Installation Installing unit with 3105007 XXX or 3105935 XXX Return Air Cover...

Page 14: ...e red positive 12VDC supply wire See FIG 23 b Connect the black wire from the air conditioner and the black wire from the filter indicator light with the black negative 12VDC supply wire See FIG 23 No...

Page 15: ...uct System Only Depth 2 0 In Min 2 0 Max Width 8 0 In Min 8 0 In Max Total Duct Length 15 0 Ft Min 40 Ft Max Duct Length Short Run 1 3 Total Length Register Requirements Number Required Per Run 4 Min...

Page 16: ...er Required Roof Rafters Roof Rafters Note Duct Size is Inside Dimensions Note Duct Size Is Inside Dimensions Short Duct Run Minimum 1 3 Total Duct Length Short Duct Run Minimum 1 3 Total Duct Length...

Page 17: ...tery symbol will appear in the dis play window b When the low battery condition exists and the remote sends a signal to the receiver it may be possible for the control system to go to the default sett...

Page 18: ...played a High Speed continuous fan operation b Low Speed continuous fan operation 3 The receiver will beep when each change is com pleted The GREEN LED will light H Room Temperature Display 1 Press th...

Page 19: ...batteries are installed the clock will display 0 00 b Clock shows only military time c Push the clock button the clock display should blink I FEEL I FEEL d Press and hold the UP or DOWN but ton to set...

Page 20: ...NO TO 115 VAC 1O 60 Hz TO 115 VAC 1O 60 Hz HEAT ACCESSORY WHT BLK BLK ELEMENT LIMIT 3 1 SWITCH WHT BLK OL WHT FREEZE BLK BLK NOT AVAILABLE ON SOME ON SOME MODELS T5 T6 T9 T10 T7 T8 COUPLERS IN LINE I...

Reviews: