domat UC010
-
pull the display part and remove it from the bottom.
Do not bend the display part too much, the connector pins could be damaged. The locks
are only at the sides of the display part, not at the top nor bottom.
Operation
The following settings are defaults. The engineer may set another way of fancoil
control, disable some functions etc., so the text below is a description of the default
functionality of the controller rather than the user operation manual.
Temperature correction:
Turn the knob clockwise to increase setpoint, turn it counterclockwise to decrease
setpoint. The maximum correction range can be modified over the bus e.g. with the
ModComTool configuration tool.
Fancoil stage setting:
Push the knob shortly (<1 s). Every push changes the fancoil stage cyclically: Stage 1
–
Stage 2
–
Stage 3
–
Off
–
Auto. When changing between the Comfort and Standby
modes, the controller falls back into automatic fancoil stage control according to the
control deviation.
Operation mode change:
The operation mode in the Hotel mode (used for fancoils in hotels and offices) is
changed over bus communication or by activating digital inputs. The DI1 switches
between the Comfort and Standby modes (e.g. card reader), while DI2 brings the
controller into the Off mode (e.g. window contact). The time scheduler is used with
Residential mode only.
Time schedule settings:
Switch to the time schedule settings mode with a long push (>1 s). The controller
switches to settings mode (clock icon).
Turn the knob to select the weekday (1 to 7). Then short push to confirm the selection.
Turn the knob to select the event (large number 1 to 6). Each event displays the mode
activated by this event.
Short push to confirm the event selection. Turn the knob to select the operation mode
(Day, Night, Off, Event inactive) invoked by this event. If the event is not active, the
operation mode is not changed at the set time.