Devices are to be connected under dead-voltage condition. Devices must 
only be connected to safety extra-low voltage. Consequential  damages 
caused by a fault in this device are excluded from warranty or liability. These 
devices must be installed and commissioned by authorised specialists. The 
technical data and connecting conditions shown on the device labels and in 
the mounting and operating instructions delivered  together with the device 
are exclusively valid. Deviations from the catalogue representation are not 
explicitly mentioned and are possible in terms of technical progress and 
continuous improvement of our pro ducts. In case of any modifications made 
by the user, all warranty claims are  forfeited. Operating this device close 
to other devices that do not comply with EMC directives may influence 
functionality. This device must not be used for monitoring applications, 
which serve the purpose of protecting persons against hazards or injury, or 
as an EMERGENCY STOP switch for systems or machinery, or for any other 
similar safety-relevant purposes.
Dimensions of housing or housing accessories may show slight 

 

tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original packing 
will be accepted.

Our “General Terms and Conditions for Business“ together with the 
“General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including 

 

supplementary clause “Extended Retention of Title“ apply as the 

 

exclusive terms and conditions“.

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and  
standards applicable for the place of measurement (e.g. such as welding 
instructions, etc.). Particularly the following shall be regarded:
–  VDE  ⁄  VDI directive technical temperature measurements, measurement 

set - up for temperature measurements.

–  The EMC directives must be adhered to. 
–  It is imperative to avoid parallel laying of current-carrying lines.

We recommend to use shielded cables with the shielding being  attached at 
one side to the DDC  ⁄  PLC.Before mounting, make sure that the existing 
thermometer‘s technical parameters comply with the actual conditions at 
the place of  utilization, in particular in respect of:
–  Measuring range 
–  Permissible maximum pressure, flow velocity 
–  Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

CONNECTING CONDITIONS
Output:   0  - 10  V

The output voltage follows linear to the temperature signal applied at  
the input terminals and generates a proportional output signal of 0 - 10 V. The 
voltage outputs are short-circuit proof against ground wire. Applying voltage 
supply to the output terminals will destroy the device.

Output:   4 ... 20 mA

In case of the 4 ... 20 mA measuring transducer, display and evaluating 
 

elements are connected in series in the current loop. The measuring 

 

transducer thereby liWiths the flowing current in variance of the input signal. 
4 mA are for the measuring transducer‘s internal current consumption. The 
apparent ohmic resistance can either be connected in the plus or minus path 
of the measuring transducer. In case of an apparent ohmic resistance in the 
plus path, power supply and resist.

SAFETY REGULATIONS

These devices shall only be used for their intended purpose. Respective 
safety regulations issued by the VDE, the states, their control authorities, 
the TÜV and the local energy supply company must be observed. The buyer 
has to ensure adherence to the building and safety regulations and has to 
avoid all dangers of any kind. We do not assume any warranty for faults or 
damages arising or resulting from improper use of our equipment or from 
non-observance of operating instructions. These instruments must be 

 

installed by authorised specialists only!

Preferably shielded cables should be used in order to prevent damages  ⁄  
errors. It is imperative to avoid laying parallel with current-carrying lines. 
EMC directives must be adhered to.

Notes on commissioning:

This device was calibrated, adjusted and tested under standardised conditions. 
When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at 
regular intervals. 

Commissioning is mandatory and may only be performed 

by qualified personnel! 

G  

Installation and Commissioning

G  

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 

and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be 

observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the 

TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent 

perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve-

ment of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation 

by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read installation and commissioning and all notes provided therein are to be regarded!

Summary of Contents for THERMASGARD RTM

Page 1: ...ng transducers calibratable with multi range switching and active output 6000 2620 0000 1XXD1 26200 2020 D1 V103 06 2020 Gratulujeme Zakoupili jste produkt německé kvality Congratulations You have bought a German quality product Domat Control System s r o U Panasonicu 376 530 06 Pardubice Stare Civice CZ Česká republika Tel 420 461 100 823 Fax 420 226 013 092 info domat cz www domat int com ...

Page 2: ...THERMASGARD RTM G Rozměry Kryt Baldur1 Dimensional drawing Housing Baldur1 Rozměry Kryt z nerezové oceli Dimensional drawing Housing stainless steel T K ø 6 0 85 85 27 2 25 ø 6 0 75 72 75 72 ...

Page 3: ... uprostřed zařízení zatlačte směrem dolů a mírně nadzdvihněte spodní část krytu Odejměte vrchní část krytu vpřed To open the housing set a screwdriver 2 0 in the groove at centre press down and lift up the bottom frame slightly Pull top cover forward and hold it Kryt Baldur Housing ...

Page 4: ...Barva bílá podobná RAL 9010 Volitelně z nerezové oceli V2A 1 4301 Rozměry krytu 85 x 85 x 27 mm Baldur 1 75 x 75 x 25 mm nerezové oceli Elektrické připojení 0 14 1 5 mm pomocí šroubových svorek Montáž Na stěnu nebo na krabici pod omítku Ø 55 mm základna se 4 otvory pro montáž do svisle nebo vodorovně instalované krabičky pod omítku se vstupy kabelů vzadu s předem určeným bodem zlomu pro vstup kabe...

Page 5: ...jet střídavým proudem i zařízení s výstupem 0 10 V Výstupní signál lze měřit měřícím přístrojem Výstupní napětí je měřeno proti nulovému potenciálu O V vstupního napětí Pokud je toto zařízení napájeno stejnosměrným napájecím napětím musí být vstupní napětí UB použito pro napájení 15 36 V ss a UB nebo GND pro uzemnění Pokud je napájeno více zařízení jedním napájecím zdrojem o napětí 24 V musí být z...

Page 6: ...okyny Odchylky od katalogové prezentace nejsou uvedeny samostatně a jsou možné z hlediska technického pokroku a neustáleho zlepšování našich produktů Změny zařízení provedené uživatelem ruší všechny nároky vyplývající ze záruky Provoz v blízkosti zařízení které neodpovídá směrnici EMC může ovlivnit funkci čidla Toto zařízení nesmí být používáno jako bezpečnostní prvek k ochraně osob před nebezpečí...

Page 7: ......

Page 8: ... white similar to RAL 9010 optional stainless steel V2A 1 4301 Dimensions 85 x 85 x 27 mm Baldur 1 75 x 75 x 25 mm stainless steel Electrical connection 0 14 1 5 mm via terminal screws Installation wall mounting or on in wall flush box Ø 55 mm base with 4 hole for mounting on vertically or horizontally installed in wall flush boxes for cable entry from the back with predetermined breaking point fo...

Page 9: ... a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on AC supply voltage The output signal is to be tapped by a measuring instrument Output voltage is measured her against zero potential O V of the input voltage When this device is operated on DC supply voltage the operating voltage inpu...

Page 10: ...energy supply company must be observed The buyer has to ensure adherence to the building and safety regulations and has to avoid all dangers of any kind We do not assume any warranty for faults or damages arising or resulting from improper use of our equipment or from non observance of operating instructions These instruments must be installed by authorised specialists only Preferably shielded cab...

Page 11: ...stech jejich použití nezaručují však určité vlastnosti produktu Jelikož produkty mohou být nasazovány za nejrůznějších podmínek a zatížení které nemůžeme ovlivnit musí zákazník nebo uživatel vždy provést korekci pro konkrétní případ aplikace Respektujte vlastnická práva Bezchybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statemen...

Page 12: ... O N 30 C 60 C OFF OFF O N 0 C 40 C O N O N OFF 0 C 50 C OFF O N OFF 0 C 100 C O N OFF OFF 0 C 150 C OFF OFF OFF 12 3 1 2 4 5 3 ON pasivní senzor pasivní senzor UB 24 V st ss Výstup 0 10 V ve C UB GND interní senzor pasivní senzor max min 10K Offset DIP 12 3 1 2 4 5 3 ON pasivní senzor pasivní senzor UB 24 V ss Výstup 4 20 mA ve C n c interní senzor pasivní senzor DIP max min 10K Offset 12 3 1 2 4...