Installation and Commissioning

G  

Resistance characteristics of passive temperature sensors  (see last page)

In order to avoid damages  ⁄ errors, preferably shielded cables are to be used.  
Laying measuring cables parallel with current-carrying  cables must in any case be avoided. EMC directives shall be  observed! 
These instruments must be installed by authorised specialists only!

ATTENTION,  NOTE !
Testing current influences the thermometer‘s measuring accuracy 
due to intrinsic heating and therefore, should never be greater than  
as specified below:

Standard values for testing current:
Sensor current, maximum ................................................................. I 

max.

Pt1000   (thin-layer)  .................................................................. < 0,6 mA
Pt100       (thin-layer)  .................................................................. < 1,0 mA
Ni1000  (DIN),  Ni1000 TK5000  ............................................. < 0,3 mA
NTC xx  ............................................................................................ < 2 mW
LM235Z ............................................................................. 400  µ A … 5 mA
KTY 81 - 210  .................................................................................... < 2 mA

Limiting deviation according to classes:
Tolerances at 0 °C:

Platinum sensors (Pt100, Pt1000): 
DIN EN 60751, class B ................................................................± 0.3 K
1 ⁄  3 DIN EN 60751, class A ........................................................± 0.1 K

Nickel sensors: 
NI1000 DIN EN 43760, class B .................................................± 0.4 K
NI1000 1 ⁄  2 DIN EN 43760, class B.........................................± 0.2 K
NI1000 TK5000 ...........................................................................± 0.4 K

Devices are to be connected under dead-voltage condition. Devices 
must only be connected to safety extra-low voltage. Consequential 
 

damages caused by a fault in this device are excluded from 

 

warranty or liability. These devices must be installed and commissioned 
by authorised specialists. The technical data and connecting conditions 
shown on the device labels and in the mounting and operating instruc-
tions delivered  together with the device are exclusively valid. Deviations 
from the catalogue representation are not explicitly mentioned and are 
possible in terms of technical progress and continuous improvement 
of our pro ducts. In case of any modifications made by the user, all  
warranty claims are  forfeited. Operating this device close to other  
devices that do not comply with EMC directives may influence functionality. 
Thisdevice must not be used for monitoring applications, which serve the 
purpose of protecting persons against hazards or injury, or as an  
EMERGENCY STOP switch for systems or machinery, or for any other 
similar safety-relevant purposes.

Dimensions of enclosures or enclosure accessories may show slight 
tolerances on the specifications provided in these instructions. 

Modifications of these records are not permitted. 

In case of a complaint, only complete devices returned in original 
packing will be accepted.

Our “General Terms and Conditions for Business“ together with the 
“General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including  
supplementary clause “Extended Retention of Title“ apply as the  
exclusive terms and conditions“.

Notes on installation:

Mounting shall take place while observing all relevant regulations and 
standards applicable for the place of measurement (e.g. such as  
welding instructions, etc.). Particularly the following shall be regarded:
– VDE ⁄ VDI directive technical temperature measurements,  

measurement set - up for temperature measurements.

– The EMC directives must be adhered to.
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with  

the shielding being attached at one side to the DDC ⁄ PLC.

Before mounting, make sure that the existing thermometer‘s technical 
parameters comply with the actual conditions at the place of utilization, 
in particular in respect of:
– Measuring range
– Permissible maximum pressure, flow velocity
– Installation length, tube dimensions
– Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

Attention! In any case, please observe the mechanical and  
thermal load limits of the protective tubes according to DIN 
43763 or according to specific S+S standards!

Notes on commissioning:

This device was calibrated, adjusted and tested under standardised 
conditions. 
When operating under deviating conditions, we recommend performing 
an initial manual adjustment on-site during commissioning and 

 

subsequently at regular intervals.

Commissioning is mandatory and may only be performed by 
 qualified  personnel! 

Summary of Contents for THERMASGARD ATF Series

Page 1: ...room temperature sensors with passive output ATF1 ATF2 s with SS02 ATF2 6000 2080 0000 1XXD1 20800 2020 D1 V104 03 2020 Domat Control System s r o U Panasonicu 376 530 06 Pardubice Stare Civice CZ Česká republika Tel 420 461 100 823 Fax 420 226 013 092 info domat cz www domat int com Gratulujeme Zakoupili jste produkt německé kvality Congratulations You have bought a German quality product ...

Page 2: ...THERMASGARD ATF G Rozměry ATF1 Dimensional drawing ATF01 ATF01 IP 54 ATF1 IP 65 39 49 ø 4 3 37 8 14 8 M16x1 5 107 72 64 64 ...

Page 3: ...THERMASGARD ATF G Rozměry ATF2 Dimensional drawing 14 8 37 8 M16x1 5 ø 11 40 107 72 65 ø 6 39 49 ø 4 3 64 64 bez without SS02 s with SS02 ...

Page 4: ...x 400 μA 5 mA LM235Z Kryt plast odolný vůči UV záření material polyamid vyztužený 30 skleněnými kuličkami barva bílá podobná RAL 9016 ATF01 s naklapovacím krytem ATF1 s rychloupínacími šrouby kombinace s drážkou hlavou Phillips ATF2 s rychloupínacími šrouby kombinace s drážkou hlavou Phillips Rozměry krytu 72 x 64 x 37 8 mm Tyr 1 Tyr 01 Průchodka kabelu M 16 x 1 5 vyměnitelné s odlehčením tahu max...

Page 5: ... zabudováno v krytu Dostupné jsou různé druhy krytů např s vnější objímkou čidla viz snímač ATF2 Uzavřené snímače se běžně dělí na snímače pod omítku FSTF a povrchovou montáž RTF ATF a verze pro použití v interiérech a vlhkém prostředí Svorky se nacházejí na desce uvnitř krytu U trubkových a vestavěných čidel teploty rozlišujeme čidla s výměnnou měřící vložkou a bez výměnné měřící vložky Připojova...

Page 6: ...okolností se vyvarujte paralelní pokládky se silovým vedením pokyny a nařízení pro elektromagnetickou kompatibilitu EMC doporučuje se použití stíněných kabelů se stíněním připojeným jednostranně na straně PLC či vstupních modulů Před instalací se ujistěte že technické parametry daného teploměru nejsou v rozporu s aktuálními podmínkami v místě měření především měřicí rozsah maximální přípustný tlak...

Page 7: ......

Page 8: ...type 2 wire connection 4 wire connection on PT100 PT1000A optional on other sensors Testing current 0 6 mA Pt1000 1 0 mA Pt100 0 3 mA Ni1000 Ni1000 TK5000 2 0 mW NTC xx 400 μA 5 mA LM235Z Enclosure plastic UV stabilised material polyamide 30 glass globe reinforced colour traffic white similar to RAL 9016 ATF01 with snap on lid ATF1 with quick locking screws slotted Phillips head combination ATF2 w...

Page 9: ...tion On enclosure type sensors the temperature sensor is embedded in a respective enclosure Different designs of enclosures are available e g with an external sensor sleeve see outside temperature sensor ATF2 Enclosure type sensors are normally distinguished into in wall FSTF and on wall RTF ATF types and indoor and wet room versions Connection terminals are placed on a plate inside the connecting...

Page 10: ...the purpose of protecting persons against hazards or injury or as an EMERGENCY STOP switch for systems or machinery or for any other similar safety relevant purposes Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions Modifications of these records are not permitted In case of a complaint only complete devices returned i...

Page 11: ...chybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under a wide range of diffe...

Page 12: ...461 1760 1625 4 3552 3817 3930 120 130 149 8 1498 1833 3676 4008 130 140 153 6 1536 1909 3802 4166 140 150 157 3 1573 1987 3929 4280 150 NTC 1 8 kOhm NTC 2 2 kOhm NTC 3 kOhm NTC 5 kOhm NTC 10 kOhm NTC 10 kPRE NTC 20 kOhm NTC 50 kOhm C Ω Ω Ω Ω Ω Ω Ω Ω C 50 50 40 39073 806800 2017000 40 30 22301 27886 53093 88488 175785 135200 413400 1033500 30 20 13196 16502 29125 48541 96597 78910 220600 551500 20...

Reviews: