domat R560 

11/2018 Subject to technical changes. 

 

 

 

R560  

Universal analogue input module 

 

 

 

 

 

 

Summary 

The R560 is a microprocessor controlled, communicative module with 8 analogue 
inputs  with  variable  measuring  range:  voltage,  resistance,  temperature,  current 
loop).  The  module  uses  a  RS485  bus  for  communication,  and  can  be  easily 
integrated in a variety of supervision and control systems. 
 

Application 

 

Building and industrial control systems 

 measuring of temperature, 

pressure, and other values  

Function 

The  module  incorporates  8  analogue  inputs.  The  input  signals  are  processed  and 
multiplexed  into  a  16  bit  A/D  converter.  Each  input  is  rangeable  separately  (see 
Technical  data),  and  inputs  can  also  be  used  as  0  to  20  mA  current  measurement 
inputs if the corresponding DIP switch is activated. 
 
The  module  communicates  by  means  of  RS485  data  bus.  The  Modbus  RTU 
communication protocol ensures smooth and easy integration in a variety of control 
and  data  acquisition  systems.  It  connects  to  process  stations  (PLCs)  directly  or 
through the M012 interface (RS485 to RS232 converter with galvanic isolation).  
 
Removable  connectors  are  used  for  all  signals  as  well  as  for  data  line  so  that 
mounting is fast and easy. The module has a DIN rail clip. 
 
The  communication  circuits  are  protected  against  overvoltage  and  galvanically 
isolated  from  other  parts  of  the  module.  If  the  module  is  terminating  the 
communication bus, i.e. it is the first or last in line, a terminating 120 

 resistor may 

be switched on by activating the BUS END switches. Two LEDs located inside of the 
housing enable fast diagnostics 

 power and communication. 

 

Summary of Contents for R560

Page 1: ... to 20 mA current measurement inputs if the corresponding DIP switch is activated The module communicates by means of RS485 data bus The Modbus RTU communication protocol ensures smooth and easy integration in a variety of control and data acquisition systems It connects to process stations PLCs directly or through the M012 interface RS485 to RS232 converter with galvanic isolation Removable conne...

Page 2: ...may be used for temperature measurement with Pt100 Pt1000 Ni1000 5000 and Ni100 6180 passive sensors Linearisation must be done in controllers Domat PLC for example just like at e g MCIO2 module In the R560 module there is recalculation to C for the Pt1000 sensor only Sampling 10 samples s Effective resolution 16 bit Measurement error The measurement deviation for all measured variables is 0 25 of...

Page 3: ...dication RUN orange LED system cycle OK LED flashes periodically 1 s ON 1 s OFF ERROR LED flashes in other pattern LED is still ON or OFF TxD red LED RS485 transmitting data at COM1 flashing transmitting data OFF no data traffic PWR green LED power supply ON power OK OFF no power applied weak or damaged power supply DIP switches ADR AUTO if all switches are OFF the address is used according to Mod...

Page 4: ... to technical changes domat R560 0 20 mA For current measurement 0 20 mA on individual channels switch the particular DIP switch to ON The 0 20 mA range must be also set over Modbus e g using Domat ModComTool Connection ...

Page 5: ... 3 Addressing The Modbus address can be set as follows hardwarewise using DIP switches The switches increase their bit weight from right to left see image with example where address of 21 is set by activation of switches 4 6 and 8 with bit weight of 16 4 and 1 respectively Valid settable range is 1 to 254 Address 0 all switches OFF means that the address is set as entered in the Modbus table Addre...

Page 6: ...s set to 0 All changes apply after the module is switched off and on again Safety note The device is designed for monitoring and control of heating ventilation and air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks re...

Page 7: ...domat R560 11 2018 Subject to technical changes 7 Changes in versions 07 2017 First datasheet version 10 2017 Added measurement error value new image 02 2018 Added Safety note 11 2018 Minor changes ...

Reviews: