background image

G  

Mounting and Installation 

Rev.  2020 - V35

ATTENTION!   

There is no universally uniform standard, which could be applied to a 

VOC sensor

 (Volatile Organic Compounds). The monitored air contains a large 

number of substances to which the sensor responds, and gas mixtures are adjusted. Therefore this sensor does not act selectively, but rather 
 reflects the overall air quality. In principle, one also cannot state precisely what is "bad air" or what is "good air" because this is a purely subjective 
sensation. 
The gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air 
surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay. It is essential to choose an installation 
location for the device in which the air stream flows around the sensor. Otherwise the gas exchange may be considerably delayed or prevented.  

Automatic calibration of air quality  (default) 

The automatic background logic is a self-calibrating mechanism that is suitable for use in applications in which the air quality regularly drops to 
fresh air level. This should typically occur during times in which the rooms are unoccupied. 

The sensor reaches its normal accuracy after 24 hours of continuous operation in an environment that has been subjected to a fresh air supply. 
The deviation errors remain minimal if the sensor is exposed to fresh air at least 4 times within 28 days. 
The device needs continuous operating cycles of more than 24 hours to operate correctly.

Manual calibration of air quality 

After connecting the device, ensure continuous operation for at least 2 hours using air defined as "normal" air quality.  
Manual calibration can be started by pressing the button position, irrespective of the DIP 3 -switch. 

The calibration procedure is started by pressing the "ZERO" button (for approx. five seconds).  
This is signalled via the flashing LED. 

Then calibration takes place. During this phase, the LED is continuously active and a 600 second countdown runs. 

Putting in operation 

After switching on the device, a self-test and tempering period follows.  
This process takes around 30 - 50 minutes, depending on the ambient conditions. 
It is imperative to perform manual calibration once this process is completed. 

Switching point setting 

A switching point between 10 % and 95 % of the measuring range can be selected using the SET potentiometer.  
A potential-free changeover contact is available as a switch output.

Offset 

The VOC measured value can be adjusted subsequently using the offset potentiometer.
The adjusting range is ± 10 % of the measuring range.

Traffic light indicator   

RLQ - W - A

VOC content

LED  1 

green

LED  2 

green

LED  3 

yellow

LED  4 

yellow

LED  5 

red

0 %

25 %

5 %

50 %

10 %

75 %

15

 %

100 %

20 %

25 %

25 %

50 %

30 %

75 %

35

 %

100 %

40 %

25 %

45 %

50 %

50 %

75 %

55

 %

100 %

60 %

25 %

65 %

50 %

70 %

75 %

75

 %

100 %

80 %

25 %

85 %

50 %

90 %

75 %

95

 %

100 %

100 %

Once the aforementioned values have been reached, the respective LED 

becomes active (with increasing luminosity of 25 %, 50 %, 75 % and 100 %); 

LEDs that are already active continue to be illuminated.

DIP switches 

RLQ - W

VOC   sensitivity

DIP 1

DIP 2

LOW

OFF

OFF

MEDIUM  (default)

O N

OFF

HIGH

OFF

O N

VOC automatic zero point

DIP 3

deactivated

OFF

activated  (default)

O N

Output

DIP 4

Voltage 0 -10 V  (default)

OFF

Current  4...20 mA

O N

Traffic light  (5x LEDs)

DIP 5

deactivated

OFF

activated

O N

DIP switches 

RLQ - SD

VOC   sensitivity

DIP 1

DIP 2

LOW

OFF

OFF

MEDIUM  (default)

O N

OFF

HIGH

OFF

O N

Summary of Contents for AERASGARD RLQ-SD

Page 1: ...C and measuring transducer self calibrating with multi range switching and active switching output RLQ W A RLQ W RLQ SD RLQ W VA 6000 3430 0000 1XXD1 34300 2020 D1 V104 08 2020 Domat Control System s r o U Panasonicu 376 530 06 Pardubice Stare Civice CZ Česká republika Tel 420 461 100 823 Fax 420 226 013 092 info domat cz www domat int com Gratulujeme Zakoupili jste produkt německé kvality Congrat...

Page 2: ...SGARD RLQ W AERASGARD RLQ SD G Rozměry Kryt Baldur1 Dimensional drawing Housing Baldur1 T K ø 6 0 85 85 27 2 Rozměry Kryt z nerezové oceli Dimensional drawing Housing stainless steel ø 6 0 100 97 100 97 25 ...

Page 3: ... Zapojení RLQ SD 1 2 3 UB 24V st ss Výst kvalita vzduchu 0 10V UB GND Zapojení RLQ W 1 2 3 12 11 13 UB 24V st ss Výst kvalita vzduchu 0 10V 4 20mA UB GND Rozp kont Spín kont C O 24V 1A Schematic RLQ W diagram 1 2 3 12 11 13 UB 24V AC DC Output air quality 0 10V 4 20mA UB GND Breaker changeover 24V 1A Normally open contact Schematic RLQ SD diagram 1 2 3 UB 24V AC DC Output air quality 0 10V UB GND ...

Page 4: ...duch RLQ SD 0 10 V pevný RLQ W 0 10 V nebo 4 20 mA pracovní odpor 800 Ω volitelný pomocí DIP přepínačů s offsetovým potenciometrem 10 z měřicího rozsahu Výstup relé RLQ SD bez přepínacího kontaktu RLQ W s bezpotenciálovým přepínacím kontaktem 24 V 1 A spínací bod nastavitelný 0 100 z výstupního signálu Přesnost měření typicky 20 z konečné hodnoty podle kalibračního plynu Životnost 60 měsíců za pod...

Page 5: ...avenou na normální Manuální kalibraci lze spustit stisknutím tlačítka ZERO po dobu cca 5 sekund bez ohledu na polohu přepínače DIP 3 Započetí procesu kalibrace je indikováno blikáním LED Následně proběhne kalibrace Následně proběhne kalibrace Během této fáze LED stále svítí a běží odpočet 600 sekund Uvádění do provozu Po zapnutí zařízení se provede automatický test a čidlo je temperováno Tento pro...

Page 6: ...ní v blízkosti jiných zařízení která neodpovídají směrnicím EMC může ovlivnit jeho funkčnost Toto zařízení nesmí být používáno jako bezpečnostní prvek pro monitorovací aplikace které slouží k ochraně osob před nebezpečím zraněním nebo jako NOUZOVÝ VYPÍNAČ pro systémy stroje anebo pro jiné podobné účely kde selhání může vést ke škodám na majetku zdraví či životním prostředí Rozměry krytu nebo přísl...

Page 7: ......

Page 8: ...ir 10 V polluted air RLQ SD 0 10 V fixed RLQ W 0 10 V or 4 20 mA working resistance 800 Ω selectable via DIP switches with offset potentiometer 10 of the measuring range Relay output RLQ SD without changeover contact RLQ W with potential free changeover contact 24 V 1 A switchpoint can be adjusted from 0 100 of the output signal Measuring accuracy typically 20 of final value referred to calibratin...

Page 9: ...the device ensure continuous operation for at least 2 hours using air defined as normal air quality Manual calibration can be started by pressing the button position irrespective of the DIP 3 switch The calibration procedure is started by pressing the ZERO button for approx five seconds This is signalled via the flashing LED Then calibration takes place During this phase the LED is continuously ac...

Page 10: ...ct sun irradiation or heat irradiation by similar sources powerful lamps halogen spotlights must absolutely be avoided Operating this device close to other devices that do not comply with EMC directives may influence functionality This device must not be used for monitoring applications which serve the purpose of protecting persons against hazards or injury or as an EMERGENCY STOP switch for syste...

Page 11: ...práva Bezchybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under a wide range...

Page 12: ...AERASGARD RLQ W AERASGARD RLQ SD G Kryt Baldur Housing ...

Reviews: