background image

15

LG 5925 / 26.02.18 en / 972

•  According to

 

-

Performance Level (PL) e and category 4 to EN ISO 13849-1

 

-

SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 

 

-

Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511

•  According to EN 50156-2 for furnaces

•  Output: max. 4 NO contacts, see contacts

•  LG 5925.54: 1 semiconductor output

•  Single and 2-channel operation

•  Line fault detection on On-button

•  Manual restart or automatic restart, switch S2

•  With or without cross fault monitoring in the E-stop loop, switch S1

•  LG 5925.54: with cross fault monitoring in the E-stop loop

•  LED indicator for state of operation

•  LED indicator for channel 1 and 2

•  Removable terminal strips

•  Wire connection: also 2 x 1.5 mm

2

 stranded ferruled, or 

  2 x 2.5 mm

2

 solid DIN 46 228-1/-2/-3/-4

•  As option with pluggable terminal blocks for easy exchange 

  of devices

 

- with screw terminals

 

- or with cage clamp terminals

•  Width: 22.5 mm

0243372

Protection of people and machines

•  Emergency stop circuits on machines

•  Monitoring of safety gates

•  Usage in furnace application in continuous operation acc. to EN 50156-1
•  Safe disconnection of the complete fuel supply in furnace applications 
  according to EN 50156-1 section 10.5.5.2

LED "Netz": 

on when supply connected

LED K1/K2: 

on when relay K1 and K2 energized

push button ON

emergency-stop

K1

K2

M6665

LG 5925

LG 5925.54

A1(+)A2(-)

S11

S12 S22

S33 S34

33 41

23

13

M6666

S21

34 42

24

14

K2

K2

K1

Power

24V

K1

K1

K2

Overvoltage and

short circuit prot.

Monitoring logic

A1(+)A2(-)

S11

S12 S22

S34

33 41

23

13

M9754

S21

34 42

24

14

K2

K2

K1

Power

24V

K1

K1

K2

Overvoltage and

short circuit prot.

Monitoring logic

K1/K2

+

58

A025518

Canada / USA

Function Diagram

Approvals and Markings

Applications

Indicators

Block Diagrams

Safety Technique

SAFEMASTER
Emergency Stop Module
LG 5925

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.

Summary of Contents for Safemaster LG 5925

Page 1: ...AFEMASTER Not Aus Modul LG 5925 0262658 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays dold com www...

Page 2: ...5 Schaltbilder 6 Anschlussklemmen 6 Hinweise 6 Technische Daten 6 Technische Daten 7 UL Daten 7 Standardtype 7 Bestellbeispiel 7 Vorgehen bei St rungen 8 Wartung und Instandsetzung 8 Kennlinie 8 Kennl...

Page 3: ...olgen Deshalb muss in den Betriebs arten mit automatischem Start eine bergeordnete Steuerung einen automatischen Start nach einem Not Aus verhindern Durch ffnen des Geh uses oder eigenm chtige Umbaute...

Page 4: ...4 LG 5925 26 02 18 de 972...

Page 5: ...emmen oder mit Federkraftklemmen 22 5 mm Baubreite Ein Taster Not Aus K1 K2 M8574 Schutz von Personen und Maschinen Not Aus Schaltungen von Maschinen berwachung von Schiebeschutzgittern Einsatz in Feu...

Page 6: ...A pro Kontakt siehe Summenstromgrenzkurve LG 5925 03 S33 A1 S11 A2 S34 13 S12 14 41 23 S21 24 42 33 S22 34 M10536 S12 S22 S33 S34 A1 S11 A2 S21 K1 K2 13 23 33 41 14 24 34 42 Leitungsschlusserkennung...

Page 7: ...ite x H he x Tiefe LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x 121 mm Die Sicherheitsfunktionen des Ger tes wurden nicht durch die UL untersucht Die Zulassung bez...

Page 8: ...50 200 Schaltspannung VDC M2028_e Sicheres Abschalten kein stehender Lichtbogen max 1 Schaltspiel s Fehler m gliche Ursache LED Netz leuchtet nicht Versorgungsspannung nicht angeschlossen Querschluss...

Page 9: ...verst rkt werden Die Funktion der externen Sch tze wird durch Einschleifen der ffnerkontakte in den Einschaltkreis Klemmen S33 S34 berwacht Bitte Hinweis Ger teprogrammierung beachten Schalterstellun...

Page 10: ...14 Ein Zweikanalige Not Aus Schaltung mit Querschlusserkennung Bitte Hinweis Ger teprogrammierung beachten Schalterstellung S2 Handstart Geeignet bis SIL3 Performance Level e Kat 4 L1 M9759 N Not Aus...

Page 11: ...gency Stop Module LG 5925 0262658 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com...

Page 12: ...nection Terminals 16 Notes 16 Technical Data 16 Technical Data 17 UL Data 17 Standard Type 17 Ordering Example 17 Troubleshooting 18 Maintenance and repairs 18 Characteristics 18 Characteristics 18 Ap...

Page 13: ...evice is under supply voltage AUTOMATIC START According to IEC EN 60 204 1 part 9 2 5 4 2 and 10 8 3 it is not allowed to restart automatically after emergency stop Therefore the machine control has t...

Page 14: ...14 LG 5925 26 02 18 en 972...

Page 15: ...p terminals Width 22 5 mm 0243372 Protection of people and machines Emergency stop circuits on machines Monitoring of safety gates Usage in furnace application in continuous operation acc to EN 50156...

Page 16: ...and S2 are used These are loca ted behind the front cover see unit programming The setting with or without cross fault monitoring on E stop buttons is made with S1 not for LG 5925 54 The LG 5925 54 ha...

Page 17: ...LH 5925 AC DC 24 V 375 g Dimensions Width x height x depth LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x 121 mm The safety functions were not evaluated by UL Listin...

Page 18: ...64 I 2 A 2 150 200 256 100 0 10 20 30 40 60 50 T C 0 0 1 0 3 0 5 1 3 5 10 switching current A 50 100 150 250 200 switching voltage VDC M5834_c safe breaking no continuous arcing max 1 switching cycle...

Page 19: ...S11 S33 S34 S12 S22 S21 LG5925 13 23 14 24 K4 K4 K5 K5 on Single channel emergency stop circuit This circuit does not have any red undancy in the emergency stop control circuit Note Refer to Unit pro...

Page 20: ...S22 S21 LG5925 13 14 on 2 channel emergency stop circuit with cross fault detection Note Refer to Unit programming Switches in pos S2 manual start Suited up to SIL3 Performance Level e Cat 4 L1 M10096...

Page 21: ...dule d arr t d urgence LG 5925 0262658 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www do...

Page 22: ...ristiques techniques 26 Caract ristiques techniques 27 Donn es UL 27 Versions standard 27 Exemple de commande 27 Diagnostics des d fauts 28 Entretien et remise en tat 28 Courbe caract ristiques 28 Co...

Page 23: ...apr s un Arr t d urgence Losqu un d marrage automatique est toutefois demand il est nec ssaire de assurer qu une commande prioritaire effectue le blocage apr s une action d arr t d urgence L ouverture...

Page 24: ...24 LG 5925 26 02 18 fr 972...

Page 25: ...bornes ressorts ou avec bornes vis Largeur utile 22 5 mm 0247145 Protection des personnes et des machines Couplages Arr t d urgence des machines Contr le des grilles de protection coulissantes Pour un...

Page 26: ...d arr t d urgence s effectue au moyen de l interrupteur S1 sauf pour le LG 5925 54 qui u a pas le switch S1 et qui est toujours avec reconnaissance de C C transversaux L interrupteur S2 permet de choi...

Page 27: ...LG 5925 24 V AC DC 210 g LG 5925 54 24 V AC DC 220 g LG 5925 230 V AC 275 g Dimensions largeur x hauteur x profondeur LG 5925 22 5 x 90 x 121 mm LG 5925 PC 22 5 x 111 x 121 mm LG 5925 PS 22 5 x 104 x...

Page 28: ...stiques Courbes caract ristiques Diagnostics des d fauts Entretien et remise en tat 0 0 1 0 3 0 5 1 3 5 10 Courant de commutation A 50 100 150 250 200 Tension de commutation VDC M2034_d D clenchement...

Page 29: ...La fonction des contacteurs externes est contr l e en bouclant les contacts ouverture dans le circuit d enclenchement bornes S33 S34 Bien tenir compte du paragraphe Programmation du module Pos interr...

Page 30: ...6_b N A2 A1 S11 S33 S34 S12 S22 S21 LG5925 13 14 arr t d urgence marche Couplage Arr t d urgence 2 canaux sans d tection des courts circuits transversaux Bien tenir compte du paragraphe Programmation...

Page 31: ...2 2 x AWG 20 to 16 A 10 12 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 A 12 mm 1 x 0 5 4 mm2 1 x AWG 20 to 12 M10249 A A 8 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 2 x 0 5 1 5 mm2 2 x AWG 20 to 16 A 8 mm 1 x 0 5 2...

Page 32: ...niers amovibles 1 Mise hors tension de l appareil 2 Enfoncer un tourne vis dans la fente entre la face avant et le bornier 3 Tourner le tourne vis pour lib rer le bornier 4 Tenir compte du fait que le...

Page 33: ...an das Ger t im High Demand Mode Intervall f r zyklische berpr fung der Sicherheitsfunktion Demand to our device based on the evaluated neccessary safety level of the application at High Demand Mode I...

Page 34: ...34 LG 5925 26 02 18 de en fr 972 DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Page 35: ...35 LG 5925 26 02 18 de en fr 972 DE Notizen EN Notice FR Note...

Page 36: ...36 LG 5925 26 02 18 de en fr 972 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Reviews: