Doepke

Operating Instructions

Dupline DTS 1 Temperature Sensor 

7. General Information

The DTS 1 temperature sensor is a component of the Dupline installation system and al-
lows the conversion of analog temperature values for transmission on the Dupline bus.
The DTS 1 transmits the temperature data on one free encodable Dupline channel and
does not need an external power supply since this is provided by the Dupline bus.
The DTS 1 is suitable for indoor and outdoor usage and allows unobtrusive installation
due to it’s dimensions.

8. Coding

With the DHK 1 hand encoder the analog data channel can be assigned any address be-
tween A1 and P8 via the M12-plug connector. The connection between the DHK 1 and
the DTS 1 is using the optional M12 encoding cable DKP 3. The allocation of the channel
is as follows:

Functions which are not required should remain uncoded. Encoding the DTS 1 requires
neither a power supply nor the Dupline signal. Although the coding is permanently re-
tained, it may always be overwritten.

9. Putting into Service

Installation may only be carried out by an authorized technician. The DTS 1 is suitable for
direct installation at walls or other objects. The DTS 1 has to be exposed directly to the
air flow to get a proper measuring value. Therefore, an installation in switch socket boxes
is not recommended.
Observe the connections of the M12 cable used when installing. If M12 connection ca-
bles with multiple wires are used, all unused wires must be connected with the Dupline
signal conductor  (Dupline -).
All leads to be connected must be dead. Connections between the Dupline signal and
earth potential will cause malfunctions and are not permissible. In addition, check for the
correct polarity of the Dupline signal.
The following table illustrates the connection configuration:

The assignment of a 2-wire M12 cable looks as follows:

Channel

Description

Channel

Description

1

Temperature data

5

Not assigned

2

Not assigned

6

Not assigned

3

Not assigned

7

Not assigned

4

Not assigned

8

Not assigned

Pin

Description

Pin

Description

1

Dupline signal cond.+ ()

2

Dupline signal cond. - (Dupline-)

Wire

Description

Wire

Description

Brown

Dupline signal cond.+ ()

Blue

Dupline signal cond. - (Dupline-)

Summary of Contents for Dupline DTS 1

Page 1: ...nleitung Operating Instructions Inhaltsverzeichnis 1 Allgemeines 2 2 Kodierung 2 3 Inbetriebnahme 2 5 Technische Daten 3 4 Garantie 3 6 Anschlussschema 4 Table of Contents 7 General Information 5 8 Co...

Page 2: ...orgungsspannung sowie ohne Dupline Signal vorgenommen werden Sie bleibt dauerhaft erhalten kann aber jederzeit berschrieben werden 3 Inbetriebnahme Die Installation darf nur von einer autorisierten Fa...

Page 3: ...stenlosen Ersatz Bei ffnen des Ger tes erlischt der Ga rantieanspruch 5 Technische Daten Draht Beschreibung Draht Beschreibung Braun Dupline Signalleiter Dupline Blau Dupline Signalleiter Dupline Drah...

Page 4: ...B x H x T in mm Material Polycarbonat hellgrau Allg technische Daten Betriebstemperatur 30 C 60 C Schutzart Normen IP67 Bestellnummer bezeichnung 09 501 112 DTS 1 09 501 140 DKM 1 M12 Kabel 2 m gerade...

Page 5: ...s be overwritten 9 Putting into Service Installation may only be carried out by an authorized technician The DTS 1 is suitable for direct installation at walls or other objects The DTS 1 has to be exp...

Page 6: ...The guarantee is not ap plicable to damage incurred during transport or caused by short circuit or overloading In the event of defects in workmanship or material which are discovered within the guar...

Page 7: ...approx 0 35 C Bit Measuring error 2 Operating Voltage Rated operating voltage Not required supplied by Dupline signal line Terminals Type M12 socket connection Housing Type Flat pack design Dimension...

Page 8: ...n den Sie sich bitte an In case of queries concerning this product or the Dupline system plea se contact Doepke Schaltger te GmbH Co KG Stellmacherstra e 11 D 26506 Norden Germany Tel 49 0 4931 1806 0...

Reviews: