Removing the Receptacle Box–
For a successful Docking Drawer Slim USB charging outlet installation, it is
NOT
necessary to remove the
receptacle box from the cable management arms. However, if the receptacle box needs to be removed,
please follow these steps to disconnect/reconnect the receptacle box from the cable management arms.
1.
Remove the cable arm ground connection
inside the receptacle box by removing the
green ground screw and ring terminal as
shown.
DO NOT
remove the ground wire
that goes to the receptacle.
4.
Mount the power cord bracket in the correct
location on the back wall behind the drawer
as shown in the drawing.
5.
Install the drawer in the cabinet, and hold on
to the end of the arm assembly.
6.
Pass the wires from the cable management
arms into the receptacle box and reattach
the bracket using the screwdriver and
(2) #10 screws.
7.
Secure the receptacle box to the back of the
drawer using the installer supplied hardware.
8.
Reconnect the black wire from the circuit
breaker to the black wire from the cable
management arm using the blue wire nut.
9.
DO NOT FORGET TO REATTACH THE
GROUND WIRE INSIDE THE RECEPTACLE
BOX. TORQUE SCREW TO 16-18 IN-LBS.
ENSURE THAT THE CIRCUIT BREAKER IS
WIRED IN SERIES WITH THE LINE (BLACK)
WIRE. SEE WIRE DIAGRAM.
2.
Remove the blue wire nut connecting the
black wire from the cable chain to the black
wire going to the circuit breaker.
3.
Use a Phillips head screwdriver to remove the
(2) #10 screws from inside the receptacle box.
This will allow the cable arm bracket to be
disconnected from the receptacle box.
MAKE SURE BOTH GROUND SCREWS
ARE SECURELY CONNECTED!
TORQUE TO 16-18 IN-LBS
DO NOT REMOVE