DMTech FP9000L-2 Installation, Setup And Operation Download Page 7

Instructions for installation, setup and operation - FP9000L-2/4/6/8

 

 

Page 

7

 of 

16

 

 

2

 

Information and 

management 

Levels 1 

and 2 

Keyboard entry mode: 
- Changing the access level; 
- Disable mode; 
- Test mode. 

3

 

Information and 

management 

Levels 1 

and 2 

Keyboard entry mode: 
- Changing the access level. 
- Disable mode 
- Test mode 

 

 

5. PANEL INSTALATION AND SETUP 

5.1 Panel assembly. 

 

Unpack the panel; 

 

Mount the dowels at the appointed place for fixing the panel; 

 

Attach the panel to the dowels through the three holes on the chassis  

It  is  recommended  that  the  panel  should  not  be  installed  near  heat  sources  (radiators,  air 

conditioners, etc.). 

 

The connecting wires are mounted, using the hole in the box. 
 

5.2. Connecting Fire detectors. 

 

Fire  detectors  are  installed

  to  the  panel  with  the  help  of  two-wire  insulated  line  of  total 

resistance up to 100

. The recommended conductor cross-section is depending on the length of the lines, 

which are: 

 Up to 1000 m 

 

 

 

cable 2 х 0,5 mm

 Up to 1500 m 

 

 

 

cable 2 х 1,0 mm

 

Upon accession to the Fire alarm line to the panel, a check on the resistance is recommended. In 

case of proper installation in one line (fitted with finite element) between the plus and minus of the cable 
entering  the  panel,  resistance  should  be  measured  4,7k  (+/-10%).  When  measuring  the  two  wires  to 
"Earth", there should not be a link. 
 

The connection is made to the terminals of the relevant modules - "+Lx" and "-Lx" (where "x" is 

the line number) when observing the indicated polarity. (Fig.1) 

Summary of Contents for FP9000L-2

Page 1: ...dm teh com Address Pleven Bulgaria 5800 34 Gen Lt Atanas Stefanov Str DMTeh Ltd Pleven Bulgaria 34 Gen Atanas Stefanov Str office 7 Tel 359 64 801 597 e mail office dm teh com Page 1 of 21 DMTeh Ltd Pleven Fire conventional panel FP 9000L 2 4 6 8 Installation setup and operation Rev 02 16 ...

Page 2: ...e 2 of 16 P CONTENTS 3 INTRODUCTION 3 TECHNICAL PARAMETERS 5 CONTROLS AND INDICATION 6 FACTORY SET PARAMETERS 7 INSTALLATION AND PANEL SETUP 12 LEVELS OF ACCESS 13 PANEL CONDITIONS 15 CONDITIONS FOR USE STORAGE AND TRANSPORT 16 CONTENT AND COMPLEX OF DELIVERY 16 WARRANTY ...

Page 3: ... of lines 2 4 6 or 8 Optional Maximum number of fire detectors in a line 32 Type of the joining line biconductional Plume maximum resistance 100 Current thresholds in the lines Interruption from 1 to 4 mA Duty mode from 4 to 16 mA Fire from 17 to 70 mA Fire direct without delay outputs from 40 to 70 mA Short circuit 70 mA Lines functional characteristics Verification quantity before entering Fire ...

Page 4: ...ation with 2 lines 40 mA to 24 VDC Configuration with 4 lines 50 mA to 24 VDC Configuration with 6 lines 60 mA to 24 VDC Configuration with 8 lines 70 mA to 24 VDC Time needed in security mode when mains power supply is down with battery 12V 5Ah Configuration with 2 lines 120h Configuration with 4 lines 90h Configuration with 6 lines 80h Configuration with 8 lines 72h Time needed in security mode ...

Page 5: ...t without batteries 1 25 kg Safety degree IP30 EN 60529 The panel meets standarts EN 54 2 1997 EN 54 2 1997 A1 2006 EN 54 2 1997 AC 1999 EN 54 4 1997 EN 54 4 1997 A1 2002 EN 54 4 1997 A2 2006 EN 54 4 1997AC 1999 EN 50130 4 2011 EN 55022 2006 А1 2007 EN 60950 1 2006 А11 2009 3 CONTROLS AND INDICATION LED indicators Indicators Function POWER Constant green light FIRE Common indicator flashing or con...

Page 6: ...Level 1 EARTH Indicator case of damage grounded conductor 1 2 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 7 8 Individual indicators for Fire and line failure Fire is lit with red light fault lights up with yellow light When disabled and line test there is an indication of the respective condition BUTTONS Button Panel condition Access level Действие на органа за управление RESET Fire Level 2 Exit from Fire con...

Page 7: ...nnecting wires are mounted using the hole in the box 5 2 Connecting Fire detectors Fire detectors are installed to the panel with the help of two wire insulated line of total resistance up to 100 The recommended conductor cross section is depending on the length of the lines which are Up to 1000 m cable 2 х 0 5 mm2 Up to 1500 m cable 2 х 1 0 mm2 Upon accession to the Fire alarm line to the panel a...

Page 8: ...d automatic fire detector If a MCP to make alarm state over 40mA the panel will recognize it and will include sirens without delay Number of checks The factory setting is for 2 checks After the first activation the panel resets the line for 3 seconds and awaits a second response in the next 60 seconds If there is a response in this period the panel enters Fire condition This setting is recommended...

Page 9: ... are made by means of terminals mounted on the printed circuit board Fig 2 Fig 2 Total consumption of the voltage powering the external devices terminal 28 VDC and the consumption of the controllable outputs shall not exceed 1 0 A in the heaviest mode 5 3 1 Installation of the executive devices to the panel s controllable outputs Terminals Out x Out x controllable potential outputs responding at F...

Page 10: ...ntacts for Fault REL Fault and Fire REL Fire conditions When in Fault condition of the panel output REL Fault is activated immediately regardless of the type of fault The output may not be disabled or delayed Upon entering the panel s condition Fire no matter what line output REL FIRE be activated immediately The output may not be disabled or delayed Fig 4 REL Fault terminals REL Fault C REL Fault...

Page 11: ... series To the positive terminal of the battery join the red wire and the negative to the blue wire The overall voltage of both batteries must be greater than 17 6 V otherwise the panel does not recognize them Thermal sensor in the panel place in the battery With it you monitor the temperature and control the mode battery charge If everything is done correctly and the lines parameters are within t...

Page 12: ... Replacing a burnt fuse on off communication through interface RS485 delay outputs Add additional relay module M9000R 2 4 6 8 Access Level 4 This is the level of access for persons who are trained and authorized by the manufacturer to repair the panel and modify the software Special means are required to enter this level 8 CONDITIONS OF PANEL FP9000L panel operates in five conditions Duty Fire Fau...

Page 13: ...or external devices Fault in network or transmission device When systemic failure processor can not continue Exit for this kind of fault can only be accomplished by turning off the power and subsequent repair All damage except for the system kind lead to switching off some periphery Exiting this condition happens automatically to 100 seconds after dropping out removal of the fault When in fault Lo...

Page 14: ...d Disable indicator flashes 4 With button 1 is selected the line or controllable outputs 5 With button T is confirmed 6 Combination 2222 out of the programming mode Disable LED indication light indicators DISABLE lights up with a constant yellow light 1 2 3 4 5 6 7 8 local line indicator lights up with flashing yellow light OUTS flashes when a disabled controllable output Beeper indication not aff...

Page 15: ...о C Relative humidity storage to 80 working to 93 Transport The panel is transported in covered vehicles in factory packing and in the above atmospheric conditions 10 DELIVEERY COMPOSITION AND COMPLEXITY SET Fire Station FP 9000L 1 qty EOL resistor 4 7k 0 5W for configuration with 2 lines FP9000 2 2 qty for configuration with 4 lines FP9000 4 4 qty for configuration with 6 lines FP9000 6 6 qty for...

Page 16: ...ne by authorized persons The requirements for operation conditioned in this instruction were met Defects are not caused by natural phenomena and accidents of thr plug socket DMTeh wishes you splendid work For any questions may contact the company s technical staff DMTeh by email e mail office dm teh com ...

Reviews: