5. PANEL INSTALATION AND SETUP
5.1 Panel assembly.
Unpack the panel;
Mount the dowels at the appointed place for fixing the panel;
Attach the panel to the dowels through the three holes on the chassis
It is recommended that the panel should not be installed near heat sources (radiators, air
conditioners, etc.).
The connecting wires are mounted, using the hole in the box.
5.2. Connecting Fire detectors.
Fire detectors are installed
to the panel with the help of two-wire insulated line of total
resistance up to 100
. The recommended conductor cross-section is depending on the length of the lines,
which are:
Up to 1000 m
cable 2 х 0,5 mm
2
Up to 1500 m
cable 2 х 1,0 mm
2
Upon accession to the Fire alarm line to the panel, a check on the resistance is recommended. In
case of proper installation in one line (fitted with finite element) between the plus and minus of the cable
entering the panel, resistance should be measured 4,7k (+/-10%). When measuring the two wires to
"Earth", there should not be a link.
The connection is made to the terminals of the relevant modules - "+Lx" and "-Lx" (where "x" is
the line number) when observing the indicated polarity. (Fig.1)