Instructions for installation, setup and operation - FP9000L-2/4/6/8
Page
12
of
16
In access level 2 are available are following features:
Exit from Fire condition;
suppression of the outputs, activated when Fire;
involuntary activation of the controllable outputs;
suppression of built- in sounder.
Switching from
Level 2 to Level 1 and vice versa
happens after a combination of buttons and the
relevant information on the led indicator "Level Access".
The selection happens with a combination of buttons
1-2-3
.
With this combination is passed from the
access level 1 to 2 and vice versa.
LED indicator "LA" reflects the state respectively. In light we have access Level 2, if notq
Access Level
1
.
Access level 3
In Level 3 is reached by entering a opening the front cover of the panel.
Available are the following panel’s features:
all possibilities from Levels 1 and 2
Replacing a burnt fuse;
on / off communication through interface RS485;
delay outputs;
Add additional relay module M9000R – 2/4/6/8.
Access Level 4
This is the level of access for persons who are trained and authorized by the manufacturer to
repair the panel and modify the software.
Special means are required to enter this level.
8. CONDITIONS OF PANEL
FP9000L panel operates in five conditions: Duty, Fire, Fault, Disabled component and Test.
8.1. DUTY CONDITION
In Security condition, the panel is ready for indication and treatment of Fire and Fault conditions
in case of relevant events.
LED indication
– light up the indicator: "POWER" and "DEL OUTS at preset delay of connected
output.
Beeper indication
- off.
Text message indication
- displayed labeled " Security " and information about the current time.
Active buttons
- button
1,2,3
and
T
. When you press it the panel enters Information and Control
condition.
8.2. FIRE CONDITION
The panel may be in Fire condition in one or several lines.
-
LED indication
- light indicators:
-
"
FIRE
"
-
"
1 2 /3 4
/
5 6 /7 8
" Local indicator(s) for Fire in a line.