Digital Monitoring Products 

7000 Series Keypad Installation Sheet

4

7000 Series Keypad Installation Sheet 

Digital Monitoring Products

5

7073 Zone 3 Request to Exit

You can also connect a normally open PIR (or other motion sensing device) or a mechanical switch to zone 3 (White/

Orange pair) on the keypad to provide a request to exit capability to the system.  See ZONE 3 EXIT in this document.  

When zone 3 shorts, the keypad relay activates for 5 seconds.  During this time, the user can open the protected 

door to start the 40-second Soft-Shunt entry/exit timer.  If the door is not opened within 5 seconds, the relay 

restores the door to its locked state.

Note

: A zone 3 Request to Exit is inhibited for 3 seconds after the keypad reads a card and a door strike occurs.  This 

is to allow entry to the area and pass under a Request-to-Exit PIR. 

Panic Key Options

2-Button Panic Keys

All 7000 Series keypads offer a Panic key function that allows users to send Panic, Emergency, or Fire reports to 

the central station.  You must enable the Panic key function in Installer Options in order to use the Panic keys.  

See Programming Instructions later in this document.  If enabled in keypad programming, the Panic key function 

activates as soon as you apply power to the keypad.  Install the three (3) supplied icon labels below the top row of 

Select keys as shown in Figure 5.   
The user must press and hold the two Select keys for two seconds until a beep from the keypad is heard.  At the 

beep, the panel sends the following zone alarm reports to the central station: 

 

Panic 

(left two Select keys) - Zone 19 + Device Address

 

Emergency - 

non-medical (center two Select keys) - Zone 29 + Device Address

 

Fire 

(right two Select keys) - Zone 39 + Device Address

Figure 5: Panic key label placement

7/0 Panic Keys

The 7000 Series keypads also allow the user to initiate a Panic alarm by pressing the 7 and 0 (zero) keys 

simultaneously for one-half (1/2) second.  You must enable the 7/0 Panic function in Installer Options in order to use 

the 7/0 Panic keys.  See Programming Instructions later in this document.  When pressed, all 7000 Series keypads 

send a Zone Short message to the panel for the first zone of the keypad address.  
To produce a panic alarm, program the first zone of the keypad address as a Panic type zone.  Place a 1k Ohm EOL 

resistor, DMP Model 311, across the White/Brown pair of zone wires on models 7070 and 7073.  This allows a Zone 

Restore message to be sent when the keys are released. 

Note

: The 1k Ohm EOL resistor cannot be installed on 7060 and 7063 keypads.  A Zone Restore message is not sent 

when the keys are released.

Internal Speaker Operation

The 7000 Series keypads emit standard tones for key presses, entry delay, and system alerts.  The speaker also 

provides distinct burglary, fire, zone monitor, and prewarn cadences.  The keypads provide an alternate prewarn 

with alarm cadence that occurs when the status list displays a zone alarm. 

Keyboard and Logo Backlighting

The logo and keyboard light any time a key is pressed or the speaker sounds.  During an alarm condition, the 

keyboard and logo turn Red.  When all alarm conditions are cleared from the display, the Red display turns off and 

the keyboard and logo return to the user-selected brightness.  

Summary of Contents for Thinline 7060

Page 1: ... switch box DMP 695 and 696 backbox or a flat surface Figure 1 shows the keypad housing mounting hole locations Removing the Base The keypad housing is made up of two parts the front which contains the circuit board keyboard components and the base To remove the base insert a flat screwdriver into one of the openings on the bottom and twist the screwdriver while pulling the halves apart Repeat wit...

Page 2: ...nel output you can provide additional current by adding a Model 505 12 auxiliary power supply Connect all keypad black ground wires to the power supply negative terminal Run a jumper wire from the power supply negative terminal to the panel common ground terminal Connect all keypad power 12 VDC wires to the power supply positive terminal Do NOT connect the power supply positive terminal to any pan...

Page 3: ...el the keypad door strike relay activates for 5 seconds During this time the access door connected to zone 2 must be opened to start the 40 second entry exit timer and zone Soft Shunt See the timeline shown below Note The 5 second door strike is programmable when the keypad is used on an XR200 485 XR500 Series or XR2500F panel Refer to the XR500 Series Programming Guide LT 0679 or the XR200 485 Pr...

Page 4: ...on Panic left two Select keys Zone 19 Device Address Emergency non medical center two Select keys Zone 29 Device Address Fire right two Select keys Zone 39 Device Address Figure 5 Panic key label placement 7 0 Panic Keys The 7000 Series keypads also allow the user to initiate a Panic alarm by pressing the 7 and 0 zero keys simultaneously for one half 1 2 second You must enable the 7 0 Panic functi...

Page 5: ...uble conditions the volume is always at maximum level Use the left Select key to decrease the keypad volume and the right Select key to increase the volume Press the CMD key to display the Model Number MODEL NUMBER 7073 V201 030804 Model Number The LCD displays the keypad model number and the keypad firmware version and date The user cannot change this information in User Options KEYPAD ADDRESS 01...

Page 6: ...P UNSUP Keypad Mode Configure the keypad for either supervised or unsupervised operation Keypads with zones connected to them must be supervised Supervised keypads cannot share addresses with other keypads Unsupervised keypads can operate with other unsupervised keypads sharing the same address Zones cannot be used on unsupervised keypads To change the current setting press the Select key under SU...

Page 7: ...resented for arming the Home Sleep Away system After a card is presented HOME SLEEP AWAY displays The keypad waits the programmed number of seconds before automatically selecting AWAY Accessing Keypad Diagnostics If necessary refer to Access the Installer Menu on the previous page KPD KPD OPT DIAG STOP Keypad Diagnostics KPD DIAG The Keypad Diagnostic option allows you to check the display segment...

Page 8: ...lay present the credential to the reader The keypad works by reading the 4 or 5 digit user code from the data sent by the access control reader For more information refer to Entry Cards in the programming section of this document and the following User s Guide section on adding deleting and changing user codes 7063 and 7073 User s Guide There are three different sections Keypad Arming and Disarmin...

Page 9: ...are disarmed If the system is disarmed when you present your card once the card is validated all areas are armed in the AWAY mode Keypad Door Strike Area and All Perimeter Door Strike From the Status List present your card to the reader Once the system validates the card the Door Strike relay activates Home Away systems only activate the Door Strike relay when arming and disarming Figure 10 Presen...

Page 10: ... X FCC Information This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Changes or modifications made by the user and not expressly approved by the party responsible for compliance could...

Reviews: