7000 Series Keypad Installation Sheet
4
7000 Series Keypad Installation Sheet
Digital Monitoring Products
5
7073 Zone 3 Request to Exit
You can also connect a normally open PIR (or other motion sensing device) or a mechanical switch to zone 3 (White/
Orange pair) on the keypad to provide a request to exit capability to the system. See ZONE 3 EXIT in this document.
When zone 3 shorts, the keypad relay activates for 5 seconds. During this time, the user can open the protected
door to start the 40-second Soft-Shunt entry/exit timer. If the door is not opened within 5 seconds, the relay
restores the door to its locked state.
Note
: A zone 3 Request to Exit is inhibited for 3 seconds after the keypad reads a card and a door strike occurs. This
is to allow entry to the area and pass under a Request-to-Exit PIR.
Panic Key Options
2-Button Panic Keys
All 7000 Series keypads offer a Panic key function that allows users to send Panic, Emergency, or Fire reports to
the central station. You must enable the Panic key function in Installer Options in order to use the Panic keys.
See Programming Instructions later in this document. If enabled in keypad programming, the Panic key function
activates as soon as you apply power to the keypad. Install the three (3) supplied icon labels below the top row of
Select keys as shown in Figure 5.
The user must press and hold the two Select keys for two seconds until a beep from the keypad is heard. At the
beep, the panel sends the following zone alarm reports to the central station:
Panic
(left two Select keys) - Zone 19 + Device Address
Emergency -
non-medical (center two Select keys) - Zone 29 + Device Address
Fire
(right two Select keys) - Zone 39 + Device Address
Figure 5: Panic key label placement
7/0 Panic Keys
The 7000 Series keypads also allow the user to initiate a Panic alarm by pressing the 7 and 0 (zero) keys
simultaneously for one-half (1/2) second. You must enable the 7/0 Panic function in Installer Options in order to use
the 7/0 Panic keys. See Programming Instructions later in this document. When pressed, all 7000 Series keypads
send a Zone Short message to the panel for the first zone of the keypad address.
To produce a panic alarm, program the first zone of the keypad address as a Panic type zone. Place a 1k Ohm EOL
resistor, DMP Model 311, across the White/Brown pair of zone wires on models 7070 and 7073. This allows a Zone
Restore message to be sent when the keys are released.
Note
: The 1k Ohm EOL resistor cannot be installed on 7060 and 7063 keypads. A Zone Restore message is not sent
when the keys are released.
Internal Speaker Operation
The 7000 Series keypads emit standard tones for key presses, entry delay, and system alerts. The speaker also
provides distinct burglary, fire, zone monitor, and prewarn cadences. The keypads provide an alternate prewarn
with alarm cadence that occurs when the status list displays a zone alarm.
Keyboard and Logo Backlighting
The logo and keyboard light any time a key is pressed or the speaker sounds. During an alarm condition, the
keyboard and logo turn Red. When all alarm conditions are cleared from the display, the Red display turns off and
the keyboard and logo return to the user-selected brightness.