Digital Monitoring Products
693/
791/793 Installation Sheet
4
Volume Level
Set the keypad internal speaker volume level for key presses and prewarn conditions. During alarm and trouble
conditions, the volume is always at maximum level. Use the left Select key to decrease the keypad volume and the
right Select key to increase the volume. Press the COMMAND key to display the Model Number.
Model Number
The LCD displays the model number, the version and date of the keypad
Þ
rmware. The user cannot change this
information in User Options.
Keypad Address
The LCD displays the current keypad address. While in User Options, the user cannot change the keypad address.
Press the Back Arrow key to exit the User Options function.
Installer Options Menu
The Easy Entry keypads also contain a Keypad Options and Keypad Diagnostic program that allow installers and
service technicians to con
Þ
gure and test keypad operation.
You can only access the Installer Options Menu through the User Options function. After holding down the Back
Arrow and COMMAND keys for a few seconds, when the SET BRIGHTNESS prompt displays, enter the code 3577 (INST)
and press COMMAND. The display changes to KPD OPT (keypad options) KPD DIAG (keypad diagnostics) and STOP.
Keypad Options (KPD OPT)
This option allows you to set the keypad address, select supervised or unsupervised mode, change the default
keypad message, individually arm the 2-button Panic keys, and select Soft-Shunt, Request-to-Exit, and 4-digit entry
cards. To program keypad options, press the left Select key under KPD OPT. The display changes to CURRENT
KEYPAD ADDRESS: # #.
Set the CURRENT KEYPAD ADDRESS:
You can set the keypad address from 01 to 05 with the XRSuper6 and XR20, from 01 to 09 with the XR40, XR200,
XR2400F, and 01 to 16 with the XR200-485 and XR500/XR500N. The factory default address is set at 01. To change
the current address, press any Select key and then enter the new address using the appropriate number keys on the
keyboard. It is not necessary to enter a leading zero for addresses 01 to 09.
Select Supervised or Unsupervised KEYPAD MODE:
You can con
Þ
gure the keypad for either supervised or unsupervised operation. Supervise keypads that have zones
connected to them. Supervised keypads cannot share addresses with other keypads. To enhance the supervision
feature, assign an output to the Device Fail Output in panel programming and connect a device to the corresponding
output that trips when the keypad fails. This provides noti
Þ
cation at the central station and the site. The other
keypads do not display the device fail.
Unsupervised keypads can operate with other unsupervised keypads sharing the same address. Zones cannot be
used on unsupervised keypads. To change the current setting, press the Select key under SUP or UNSUP. An asterisk
appears next to the selected option.
Note
: An unsupervised address cannot be programmed for Device Fail Output.
Change the DEFAULT KEYPAD MESSAGE:
You can enter a custom message of up to 16 characters to appear on the keypad display top line whenever that line
is not used for any other purpose. Press any Select key to clear the current display and use the data entry keys to
enter a new custom display.
Entering Alpha Characters
You can use the keypad to enter alpha characters. To enter an alpha character, press the key that has the desired
letter written below it. The keypad display shows the number on that key. To change the number to a letter, press
the top row Select key that corresponds to the letter location under the key. For example, if you press key number
1, the letters for that key are A, B, and C. Press the
Þ
rst Select key for A, the second Select key for B, and the third
Select key for C.
First Letter Second Letter Third Letter Special Character
(
C
B
A
Figure 5: Entering Alpha Characters