DMP Electronics CELLCOMSL SERIES Programming Manual Download Page 33

CellComSL

 

Series Communicator Install/Programming Guide 

Digital Monitoring Products

27

APPENDIX

END - 

Press the Select key directly below END to stop the Walk Test. When the Walk Test 

ends or a 20 minute time-out expires, a final Sensor Reset occurs. The System Test End 

message is sent to the receiver along with Verify and Fail messages for each zone under 

test. Faulted zones then display on the keypad.

 

Test End Warning

When no zones have been tripped and five minutes remain on the 20 minute Walk Test 

timer, the keypad displays TEST END WARNING and the keypad tones. If no additional 

test zone trips occur, the test ends and a final Sensor Reset automatically occurs. The 

System Test End message is sent to the receiver along with Verify and Fail messages for 

each zone under WALK test. Faulted zones then display on the keypad.

 

Failed Zones Display

Each zone that did not trip at least once during the Walk Test displays on the keypad 

that initiated the test. Any Panic (PN) or Supervisory (SV) 24-hour zone that is faulted 

at the end of the Walk Test displays a trouble condition for that zone regardless of the 

message programmed for the open or short condition of the zone and a zone trouble is 

sent to the receiver. Press the COMMAND key to display the next failed zone.

18.6  Cross Zoning

Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to allow an 

intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an intruder to trip the 

devices and allow only a zone fault report be sent to the central station.

When a Cross Zoned zone trips, a FAULT report is sent to the SCS-1R or SCS-VR Receivers. When two Cross Zoned 

zones trip within the Cross Zone Time, both zones send ALARM signals to the receiver. For example, if zones 1 and 

2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the receiver for zone 1. If zone 1 trips and 

zone 2 trips within the Cross Zone Time, an ALARM report is sent to the receiver for zone 1 and zone 2.

Note:

 To operate correctly, all cross-zone zones need to be programmed as the same zone type.

18.7  Zone Type Descriptions

This section describes applications for the default zone types in Zone Information programming.

NT

 (Night Zone) - Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs 

and glassbreak detectors.

DY

 (Day zone) - Used for emergency doors or fire doors to sound the keypad buzzer and display the zone name 

when the zone is faulted. Day zones also will send alarm reports to the receiver during the system’s armed 

periods.

EX

 (Exit zone) - Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an exit 

delay timer to allow a user to exit an area after the arming process has started.

PN

 (Panic zone) - Used for connecting to mechanical devices that allow a user to signal an emergency alarm. Panic 

zones can provide either a silent or audible alarm with or without reporting to a central station receiver.

EM

 (Emergency zone) - These are used for reporting medical or other non-panic emergencies to the central 

station.

SV

 (Supervisory zone) - Used to provide 24-hour zone supervision. Typical applications are high water, and low and 

high temperature gauges.

FI 

(Fire zone) - Used for any type of powered or mechanical fire detection device. Typical applications are for 

smoke detectors, sprinkler flow switches, manual pull stations, and beam detectors.

FV

 (Fire Verify zone) - Used primarily for smoke detector circuits to verify the existence of an actual fire 

condition. When a Fire Verify zone initiates an alarm, the panel performs a Fire Reset. If any Fire zone initiates 

an alarm within 120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the 

cycle is repeated.

A1

 and

 A2

 (Auxiliary 1 and Auxiliary 2) - These zones are similar to a Night zone and are typically used to protect 

restricted areas within a protected premises. Auxiliary 2 zones do not appear in the Status List.

AR

 (Arming zone) - This zone allows you to connect a keyswitch to a zone and use it to arm and disarm the system.

TEST END WARNING

SOUTH LOBBY
ZONE: 10 

  -FAIL

Summary of Contents for CELLCOMSL SERIES

Page 1: ...CELLCOMSL SERIES CELLULAR ALARM COMMUNICA TOR INSTALL PROGRAMMING GUIDE...

Page 2: ...e installer may find the following booklet prepared by the Federal Communications Commission helpful How to identify and Resolve Radio TV Interference Problems This booklet is available from the U S G...

Page 3: ...s 6 3 4 Virtual Keypad App 6 Z Wave Setup 7 User Code Level Master only 7 5 1 Add Z Wave Devices ADD 7 5 2 List Z Wave Devices LIST 7 5 3 RENAME Z Wave Devices 7 5 4 STATUS of Z Wave Devices 8 5 5 Rem...

Page 4: ...Reports 15 8 10 Supervisory Trouble Reports 15 8 11 Opening Closing and User Reports 15 8 12 Test Report 15 8 13 First IP Address 15 8 14 First IP Port 16 8 15 Second IP Address 16 8 16 Second IP Por...

Page 5: ...rmation 21 14 1 Area Information 21 14 2 Area Number 21 14 3 Area Name 21 14 4 Automatic Arming 21 14 5 Automatic Disarming 21 Zone Information 21 15 1 Zone Information 21 15 2 Zone Number 21 15 3 Zon...

Page 6: ...stics program 26 18 4 Using the 984 Command Function 26 CELL 26 18 5 Using the Walk Test 26 Walk Test 26 Trip Counter for Walk Test STD 26 Test End Warning 27 Failed Zones Display 27 18 6 Cross Zoning...

Page 7: ...applications What is Included The CellComSL Series Cellular Alarm Communicator includes the following PCB with Enclosure 3 7 VDC 800 mAh Lithium Ion Battery Hardware Pack System Components 1 1 Termin...

Page 8: ...2 Battery Connection BAT J26 Installation Safety Ground Yourself Before Handling the Communicator To discharge static touch any grounded metal such as the control panel enclosure before touching the...

Page 9: ...t board and is used to reset the communicator microprocessor After resetting the communicator begin programming within 30 minutes If you wait longer than 30 minutes reset the communicator again 1 6 Lo...

Page 10: ...holes See Figure 11 Mount the enclosure in a secure dry place away from metal objects to protect the communicator from damage due to tampering or the elements It is not necessary to remove the PCB wh...

Page 11: ...2 CONTROL PANEL TIP CONTROL PANEL RING 12 VDC Aux Output Ground Burglary Panel The panel or separate power supply must be 12 Volt Regulated and Power Limited Telephone Jack Connector Z1 Z2 BELL BELL I...

Page 12: ...llComSLCZ only configure Rooms CellComSLCZ only turn Outputs on and off and add edit or remove Users Use 18 22 AWG for Power Supply connection Z3 Z4 Z4 GND OUT1 OUT2 CONTROL PANEL TIP CONTROL PANEL RI...

Page 13: ...S BUTTON ON DEVICE TO ADD displays press the program button on the Z Wave device See the Z Wave device s documentation for more information 5 When the device information is received by the system the...

Page 14: ...en removed 5 6 Favorites FAV Z Wave devices can be grouped together to create a Favorite This option allows you to program up to 20 Favorites in your system and then ADD EDIT OR REMOVE up to 25 Z Wave...

Page 15: ...he new temperature and press COMMAND 6 Press any Select key and the keypad displays FAN SETTING 7 Press any Select key and ON AUTO displays Press the Select key under the desired new setting to change...

Page 16: ...User Menu 2 Press COMMAND until ZWAVE SETUP displays 3 Press any Select key The keypad displays ADD LIST REMOVE 4 Press COMMAND again to display FAV XFER REDISC Select XFER The keypad displays XFER W...

Page 17: ...der of the Introduction explains starting and ending a programming session 6 2 Getting Started Ground Yourself Before Handling the Panel Touch any grounded metal before touching the communicator to di...

Page 18: ...ads Each time you need to press a Select key the keypad displays the function or options above one of the keys or in the Select Area Displaying choices above individual Select keys or in Select Areas...

Page 19: ...ions are either shown as a number a blank or a NO or YES To change a number or blank to a new number press any top row Select key or touch any Select Area The current option is replaced with a dash Pr...

Page 20: ...O leaves existing zone information intact YES sets all zones in the system to UNUSED 7 6 Clear Communication NO Leaves existing communication programming intact YES Clears communication to factory def...

Page 21: ...heck in option Default is 0 Note If Cell Check in option is used additional cell charges may apply 8 7 Fail Time Fail Time allows the SCS 1R or SCS VR receiver to miss a defined number of check ins be...

Page 22: ...eports to be sent to this receiver Default is NO 8 19 Supervisory Trouble Reports YES enables Supervisory Trouble Trouble Restoral Force Armed Late to Close and Fault reports to be sent to this receiv...

Page 23: ...or arming disarming authorization 9 8 Destination 3 Enter the third destination cell phone number 9 9 Destination 3 User Number If Destination 3 is a cellular number enter the user s User Number for a...

Page 24: ...a zone that has restored from an alarm or trouble is disarmed Twenty four hour zones send restorals immediately System Options 12 1 System Options This section allows you to select system wide parame...

Page 25: ...sed Bypassed zones are auto matically reset when the area they are assigned to is disarmed All 24 hour zones are reset when any area of the system is dis armed A programming Stop operation restores a...

Page 26: ...f the output is turned off manually the cut off time is reset The Cutoff Time can be 1 15 minutes Enter 0 zero to provide continuous output Note The output is cutoff within 60 seconds of the programme...

Page 27: ...ect key and enter up to 16 characters for the zone name A name must be given to each zone in the system This name can be displayed at the keypads when the zone is bad or viewed in Display Events The z...

Page 28: ...reported and the zone is disabled until you disarm the area from either a keypad or Remote Link computer 15 8 Next Zone When YES is selected the programming for the zone terminates and the display ret...

Page 29: ...nction the zone remains normal for one hour and the Reset Swinger Bypass is YES If the zone trips fewer than the specified times within one hour of the first trip the bypass trip counter returns to 0...

Page 30: ...ws you to program a special code that will then be required to gain access to the communicator s internal Programmer through the keypad Changing the Lockout Code You can change this code at any time t...

Page 31: ...System Recently Armed report S78 is sent when a burglary zone goes into alarm within two minutes of the system being armed 18 3 Diagnostics Function The communicator contains a Diagnostics function t...

Page 32: ...atus List display 18 4 Using the 984 Command Function When not in the Programming Menu the function 984 COMMAND can be entered at the keypad and a remote options menu appears This menu contains the fo...

Page 33: ...RM report is sent to the receiver for zone 1 and zone 2 Note To operate correctly all cross zone zones need to be programmed as the same zone type 18 7 Zone Type Descriptions This section describes ap...

Page 34: ...a primary controller The XFER feature allows an existing 3rd party network to be transferred into the CellComSLCZ The CellComSLCZ can support Z Wave products from different vendors and product categor...

Page 35: ...CellComSL Series Communicator Install Programming Guide Digital Monitoring Products 29 APPENDIX...

Page 36: ...803 8877 14185 Specifications Primary Power 12VDC Current Draw 180 mA Standby 120 mA Dimension Housing 5 5 W x 3 75 L x 1 H Color White Accessories XX 0000 Replacement Rechargeable Battery Listings an...

Reviews: