Digital Monitoring Products
CellComSL
Series Communicator Install/Programming Guide
4
INSTALLATION
Mounting the CellComSL Series Communicator
2.1 Selecting a Location
Install the communicator away from metal objects.
DO NOT
mount the CellComSL Series Communicator inside or
on the burglary control panel metal enclosure (See Figure 10).
Mounting the communicator on or near metal surfaces impairs performance. The enclosure for the
communicator
must be mounted using the provided #6 screws in the four mounting holes (See Figure 11). Mount the enclosure in
a secure, dry place away from metal objects to protect the communicator from damage due to tampering or the
elements. It is not necessary to remove the PCB when installing the enclosure.
Burglary Control
Panel
Metal Enclosure
Figure 11: Mounting Screw Locations
RESET
S1
LOAD
S2
B
AT
MODEL CellComSL
PROG
S N
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
Mounting Screw Locations
Figure 10: Suggested Mounting Locations
Figure 12: Wire Routing
RESET
S1
LOAD
S2
B
AT
MODEL CellComSL
PROG
S N
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
When installing component wires care must be taken to route all wires in such a manner that they will not
interfere with the Tamper switch. See Figure 12.