734N Installation and Programming Guide | Digital Monitoring Products, Inc.
Annunciator Header
The 4-pin header located on the far right of the circuit board is used to wire the Armed Status,
Remote Annunciation, and the Remote LED Control. The open collectors supply a ground for a
maximum current of 50 mA at 30 VDC. Connect a Model 300 4-wire harness to the 4-pin header for
connection of the following indicators:
AS (Armed Status)
Armed Status provides an unsupervised switched ground for a visual or audible armed status indicator
that turns on when the burglary areas are armed, such as
SYSTEM ON
or
ALL SYSTEM ON
. Connect
the wire from the 4-wire harness to an Armed Status output.
RA (Remote Annunciation)
Remote Annunciation provides an unsupervised switched ground for a remote annunciator that turns
on when the Zone 2 Bypass timer expires. Connect the wire from the 4-wire harness to a remote
annunciator. The remote annunciator silences when the RA restores. The remote annunciator (RA)
switched ground operates even if the speaker is programmed not to operate.
LC (Remote LED Control)
Remote LED Control provides an unsupervised switched ground for a visual indicator that turns on
when the 734N relay activates. Connect the wire from the 4-wire harness to an LED. The LED turns
on for the duration the door strike relay is on. HID readers optionally provide a connection for LED
reader control.