Паспорт
на пожароизвестители серия
D9000A-SR
- Break the plastic at the indicated location at the bottom of the sensor (Fig. 3).
Fig.2
Fig.3
Fig.4
- Place the detector on the base and rotate it.
- If the detector is locked to the base to unlock, insert the key to stop the specified place (Figure 4) and rotate the detector in the
direction counterclockwise;
- Perform a detector test to check the correct operation of the light indication;
- In normal operation, the LEDs will flash for 16 seconds.
Testing and support
Testing
–
apply the supply voltage to the circuit;
–
wait about a minute or until the detector flashes;
–
Follow the procedure for addressing the detector from the instruction panel on the fire panel.
–
In working condition, activate the detector with a temperature probe and / or a probe with a test spray. The two red LEDs must
always be lit..
Service support
➢
external inspection for mechanical damages and dirt - once a year;
➢
verification of performance - one a year;
➢
prophylactic cleaning - depending on the environment.
Warranty
➢
The manufacturer guarantees that the product complies with EN 54-5 and EN54-7.
➢
The warranty period is 36 months from the date of sale, provided that:
➢
- storage and transport conditions are met;
➢
- the commissioning is carried out by authorized persons;
➢
- the operating requirements set out in this manual are observed.
➢
- the defects are not caused by natural phenomena and failures of the power supply network.
➢
If a warranty repair is required, please contact us by telephone or e-mail to provide you with instructions on how to
perform your warranty obligations. The repairs are carried out at the company's service center.
Tel.: +359 64 801 597
DMTech wishes you pleasant work!
2.
Summary of Contents for D9000A SR
Page 1: ......