ISO 9001:2015 Certified Company
№ 34, етаж 5,
Тел./факс: 064 801 597
e-mail :
web : www.dm-teh.com
Адрес : гр. Плевен 5800
ул.”Николай Хайтов”№16
Instruction manual
D9000A-SR
Addressable Optical smoke detector
Тип
Характеристики
Чувствителност/Клас
D9000AI SR
Addressable Optical smoke detector with built isolator
EN 54-7
D9000A SR
Addressable Optical smoke detector
EN 54-7
1.
D9000A SR is an addressable optical smoke fire detector, designed for use in addressable fire alarm systems that support the
DMTech communication protocol. The detector is powered by the panel and can be controlled via the communication protocol. The
D9000A SR fire detector is compatible with the B9000A base
Technical data
•
DMTech protocol
•
Certified according EN 54-5, EN 54-7 and EN 54-17
•
LED indication 360° visibility
•
Built-in isolator - model D9000AI-A1R/A1S
•
Supply voltage from panel FP9000А
18-30VDC
•
Consumption
- current consumption in Duty mode
< 500μA/28VDC
- current consumption in, with communication
2.0mA
•
Maximum current in alarm mode - RI terminal
2.0 mA
•
Connecting wires
0.5mm² - 2.0mm²
•
Operating temperature
-10°C до +65°C
•
Resistance to relative humidity
(93 ± 3)% при
40°C
•
Degree of protection
IP40
•
Joining with base B9000A
•
Weight (with base)
~100g
•
Sizes (with base)
Ø100x52mm
•
Material (plastic) - ABS
Mounting of the detector
- select the location (according to the project drawings) for mounting the detector;
- Install the base with suitable dowels and screws.
- connect the electrical cables according to the attached diagram (Fig. 1);
фиг.1
- place the detector on the base and turn clockwise until the benchmarks match;
- If you want to lock the detector:
- Remove the key from the base beforehand (fig. 2).
Summary of Contents for D9000A SR