8.3 Battery monitoring
Batteries are a key component of the UPS. Their service life depends on the temperature, as well as on the charging and discharging time. High temperature and
deep discharge can shorten the battery life.
1. Keep the air temperature in the range from +15 to +25°C.
2. In case of prolonged system downtime, it is recommended to fully charge the battery once every 6 months.
3. Batteries must not not be replaced separately.
4. Under normal conditions, the battery life is about 2-5 years. If the batteries were kept in a humid, dusty environment, or in low temperature conditions, their
service life will be shortened.
Battery testing methods are described below (battery performance may decrease dramatically as the end of service life approaches, it is recommended to check
it at least once every 6 months):
1. Connect the UPS to the mains and leave it on charge for 8-10 hours.
2. Turn the system on, connect users and measure their power consumption.
3. Disconnect the mains so that the UPS switches to battery mode and control the discharge time before shutting down.
4. Check whether the discharge time corresponds to the values given in figures 4 to 5. If the discharge time decreases by more than 50%, replace the batteries.
UPS works with V.R.L.A. type lead-acid batteries, which are charged in the presence of a mains supply.
Note:
1. Before performing operations in the batteries, make sure that the UPS is turned off and disconnected from the mains.
2. Remove rings, watches and other conductive materials before performing operations.
3. Use a tool with an insulated handle and do not put metal objects on batteries.
4. It is strictly forbidden to make a connection between the positive and negative poles of the battery.
5. It is strictly prohibited to open the battery due to risk of damage.
6. It is strictly forbidden to throw batteries into the fire. The battery may explode!
7. Never dispose of the operated-off batteries in the environment.
9. Warranty and Service Information
AO DKC guarantees that its products are free from defects in the production and packaging of materials and finished products. The warranty period is 2 years
from the date of product purchase. The manufacturer provides warranty service, including through Authorized Service Centers (ASC). A warranty case is the loss
of equipment performance, provided it is properly operated and maintained during the warranty period.
In case of UPS failure for a reason covered by the warranty, the UPS must be delivered to the service center together with the product certificate included in
the delivery package. Addresses and phone numbers of authorized service centers of the manufacturer can be specified on the www.batt.dkc.ru website or by
email [email protected] .
These warranty obligations do not apply to equipment damaged by accident, as a result of negligence or as a result of its improper use, as well as to equipment
transformed or modified in any way. If there are additional components in the equipment that are not provided for by the configuration (for example, network or
other adapters), warranty claims are accepted only in case of a defect that is not a direct consequence of the use of such components, and only for components
sold by AO DKC.
With the exception of the obligations specified above, AO DKC is not responsible for direct, indirect, actual, accidental or secondary losses associated with the
use of these products. In particular, AO DKC is not liable to the buyer for any actual damage or lost benefits related to the use or inability to use the equipment,
data loss, software loss, costs of equipment and software replacement, costs of satisfying claims of third parties and other costs.
For all additional questions, you can contact the unified technical support service at:
8-800-250-52-63
www.dkc.ru