Room thermostat DK LOGIC 100
15
16. Tryb PAr4 - hysteresis
Par4
Setting range from 0.1 ° C
to 2 ° C. Factory setting 0.5 ° C.
Hysteresis.This parameter specifies the number of degrees C by which
the temperature in the room below the preset temperature must fall in
order for the thermostat to switch on the relay.
2.
Use the
"- / +"
buttons to set the hysteresis
value. Confirm with the button - after a
moment the regulator will automatically go to
the main screen view.
Input settings:
1.
Press the button for a few times till the
PAr4
symbol appears. Confirm by pressing .
t
AUTO
17. Setting a default day and night temperature
1.
Press the button ; currently set default
comfortable temperature (day) will appear on
the screen - the factory pre-set temperature is
21°C. Use the “-/+” buttons to set the parame-
ters as per the user’s request; use the to
confirm and to switch to the main screen; press
to go to the default settings of the lowered
(night) temperature
t
2.
Current default lowered (night) temperature will
be displayed on a screen - the factory pre-set
temperature is 18°C. Use the “-/+”buttons to set
the parameters as per the user's request and
use to confirm; the controller will show the
main screen taking into account the introduced
settings.
t