background image

    FloTech Thermo-Optic Sensors and Thermistor Dummy 

 

  

These instructions cover the following FloTech products: 
 
FT150 - Replacement Thermo-Optic Overfill Probe 
FT151 - Thermo-Optic Sensor with 2”NPT Probe Holder 
FT155 - Electronic 5 Channel Dummy 
FT152 – 2 Wire Thermo-Optic Retain Sensor with ½"  
 
FloTech Thermo-Optic sensor and Thermistor Dummy are 
mechanically and functionally compatible with Civacon and Scully 
Thermistor, Thermo-Optic and Thermistor Dummy components.  
These “Electronic” Thermistor sensors will provide reliable operation 
when installed as replacements to conventional “Green Tipped” 
Thermistor sensors.  FloTech Thermo-Optic sensors and electronic 
dummy provide high reliability, long life, and quick start up in cold 
weather. “Civacon” is a registered trademarks of Civacon / Dover 
Corporation. 
 

Installation 

 

1. FloTech model FT151 can be mounted in a 2" NPT female pipe 
coupling or through a 2 3/8" hole.  When mounting in a 2 3/8" hole, 
the gasket and lock nut provided are used to retain the probe holder 
in the tank shell or manhole.  After the sensor is mounted remove the 
cap. 
 
2. Loosen the probe clamp screw and adjust the probe to the correct 
level point.  This is typically 3% of compartment volume.  It is not 
recommended cutting the standard 7" sensor to a shorter length.  
This will cause insufficient time to stop the flow of product within the 
load racks reaction time.   
 
3. The actual sensing point adjustment should be determined by the 
total response time required to prevent a tank overfill condition.  The 
FloTech sensor reaction time is one half second.  The loading rack 
will also have a reaction time.  Once the probe is adjusted to the 
proper height, tighten the clamp screw. 
 
 

 Rev: Dec 2008                THERMO-OPTIC SENSORS 